when does the DW transfer pump auto start?
starts on a low discharge pressure of 96 PSIG (may cause a high pressure alarm in the MCR)
what trips the DW pumps?
DWST lo-lo level 4ft 2 in
what causes a DW system trouble alarm?
HI/LO DW header pressure (91 PSIG/ 122 psig)
HI/LO DWST level
DW transfer pump not in auto
where can DW be supplied from if DWST is out of service?
supplied form WRF but will be at a lower pressure
how is DS supplied to the units?
two PCV’s (500/502)
what does the control building have in the basement for DS?
has a back flow preventer in the basement
what are some loads on DS?
Essential spray pond makeup source
quench water in the blowdown stack
FP tanks
air compressor cooling when TC not available