when does the DW transfer pump auto start?

starts on a low discharge pressure of 96 PSIG (may cause a high pressure alarm in the MCR)

2
New cards

what trips the DW pumps?

DWST lo-lo level 4ft 2 in

3
New cards

what causes a DW system trouble alarm?

HI/LO DW header pressure (91 PSIG/ 122 psig)

HI/LO DWST level

DW transfer pump not in auto

4
New cards

where can DW be supplied from if DWST is out of service?

supplied form WRF but will be at a lower pressure

5
New cards

how is DS supplied to the units?

two PCV’s (500/502)

6
New cards

what does the control building have in the basement for DS?

has a back flow preventer in the basement

7
New cards

what are some loads on DS?

Essential spray pond makeup source

quench water in the blowdown stack

FP tanks

air compressor cooling when TC not available