NEC Article 250 ______.

is the primary governing article for the proper use and installation of grounding and bounding.

2
New cards

Suppose a loose connection has been exposed bare conductor and it contacts the edge of a metal enclosure. Is this an example of a short circuit or a ground fault?

ground fault

3
New cards

A single-phase system has two legs, Leg A and Leg B. If Leg A is carrying 50A and Leg B is carrying 45A, the current carried by the neutral is _____.

50A-45A=5A (Leg A- Leg B)

4
New cards

Assuming the use of 75 degrees Celsius copper conductors, a 200A commercial services would require?

3/0 service conductors

5
New cards

A ground rod must be installed in a coastal location and can only be driven halfway before encountering a rock shelf. One alternative is to _____.

burry the rod in a trench at least 30" (750 mm) deep

6
New cards

The EGC for a flexible metal conduit connection to a motor supplied with a 20A circuit____.

12 AWG copper

7
New cards

When using nonmetallic boxes with type NM cable, the grounding wire _____.

is not required to be connected to the box

8
New cards

When grounding at more than one building, the GEC at the second building is sized using _____.

NEC Table 250.66

9
New cards

If the voltage drop between a grounding electrode and an auxiliary potential electrode is 10V and a current of 10A is passed between an auxiliary current electrode and the grounding electrode, the resistance is __.

1 ohm

10
New cards

When completing a three-point test, the potential electrode is placed at ____.

62% of the current electrode distance

11
New cards

Item B in Figure RQ01 represents the _____.

ungrounded conductors (Hot)

12
New cards

Item E in Figure RQ01 represents the _____.

grounding electrode conductor

13
New cards

Item C in Figure RQ01 represents the _____.

grounded conductor (Neutral)

14
New cards

Item F in Figure RQ01 represents the _____.

main bonding jumper

15
New cards

The conducting connection, whether intentional or accidental, between any of the conductors of an electrical system is known as a ____.

short circuit

16
New cards

Which conductor(S) are grounded on a single-phase, three-wire, 120/240V system?

Neutral

17
New cards

Residential electrical services are grounded by connecting the grounded conductor to a grounding electrode at the _____.

neutral bus in the main panelboard

18
New cards

A single-phase system has two legs, Leg A and Leg B. If Leg A is carrying 35A and Leg B is carrying 30A, the current carried by the neutral is ____.

35A-30A=5A (Leg A - Leg B)

19
New cards

A concrete-encased electrode used for service grounding must be covered with a minimum of ____.

2" (50 mm) of concrete

20
New cards

Which of the following is an NEC violation when used as a grounding electrode?

An underground gas line

21
New cards

The maximum distance allowed by the NEC to connect a grounding conductor to a water pipe after the pipe enters the building is ___.

10' (3 m)

22
New cards

Which of the following is used to connect a ground rod with a grounding conductor?

A grounding clamp

23
New cards

All of the following are suitable materials for ground rods, except ____.

A. Stainless steel

B. galvanized steel

C. iron

D. aluminum

D. aluminum

24
New cards

Which of the following copper AWG sizes should be used for the grounding conductor for a 200A service using 3/0 copper conductors?

No. 4

25
New cards

Assuming the use of 75 degrees Celsius copper conductors, a 230A commercial services would require?

4/0 service conductors

26
New cards

When a metal water pipe is used as a grounding electrode, what must be provided around the water meter?

Bonding jumper

27
New cards

The EGC for a flexible metal conduit connection to a motor supplied with a 15A circuit is ____.

14 AWG copper

28
New cards

The main bonding jumper for 4/0 service conductors is ___.

2 AWG copper

29
New cards

If you are bounding multiple disconnects and the size of the service-entrance conductor is 3/0, the size of the bonding jumper is ____.

4 AWG copper

30
New cards

Touch voltage extends to a distance of approximately ___.

3' (1 m)

31
New cards

A short circuit is a conducting connection, whether international or accidental, between any of the _____ of an electrical system.

conductors

32
New cards

True or False? The neutral or (grounded) conductor is a system or circuit conductor that is intentionally grounded.

True

33
New cards

A conductor used to connect equipment or the grounded circuit of a wiring system to a grounding electrode is called a(n) ____ conductor.

grounding electrode

34
New cards

The two types of grounding systems are system grounding and _____.

equipment grounding

35
New cards

If the loads were only 240V on a single-phase 240V system with a center-tapped transformer, the neutral conductor would carry_______ amperes.

0

36
New cards

Systems less than 50V are required to be grounded if the supply voltage to the transformer exceeds__________ to ground.

150V

37
New cards

Circuits that cannot be grounded include certain circuits for cranes, electrolytic cells, secondary circuits on lighting systems, and isolated power systems in _______.

Healthcare Facilities

38
New cards

Systems are solidly grounded to limit the __________ during normal operation and to prevent excessive voltages due to lightning and line surges.

voltage to ground

39
New cards

Grounding methods include an underground water pipe in direct contact with the earth for no less than ___________.

10'

40
New cards

The size of the grounding electrode conductor is based on the size of the _____.

service entrance conductors

41
New cards

The size of the EGC is determined by the _____.

size of overcurrent device that is protecting the system

42
New cards

All receptacles used in residential applications must be of the___________ type.

grounding

43
New cards

Electrical ____ is the key to successful clearing of ground faults.

continuity

44
New cards

The size of the bonding jumper on the supply side is based on the size of the ____ in each raceway.

service entrance conductor

45
New cards

The two main purposes of the neutral in a grounded system are to permit utilization of power at line-to-neutral voltage and _______.

To provide low impendence return path for flow of fault current to the source and to facilitate the operation of the overcurrent devices in the circuit.

46
New cards

When a main bonding jumper is required by the NEC, the jumper ____.

cannot be less than 12.5% of the area of the largest phase conductor.

47
New cards

An acceptable grounding electrode is a(n) _____.

metal frame of a building which is effectively grounded

48
New cards

Rod, pipe, and plate electrodes must have a resistance to ground of at least ____.

25 ohms or less.

49
New cards

Ultimately, the ground fault is cleared when the ______.

Over current devices are opened

50
New cards

Which type of system is required to be grounded?

AC Systems over 1K Volts

51
New cards

The minimum length allowed for driven ground rods under normal conditions is _____.

8'

52
New cards

The minimum diameter of galvanized pipe allowed for a grounding electrode is _____.

3/4"

53
New cards

Where there is a requirement to add a second grounding electrode, the two electrodes must be spaced at least _____.

6' apart

54
New cards

A ground ring consisting of 20' of No.2 bare copper must be buried no less than _____.

2.5' below grade

55
New cards

A ground test utilizing an earth ground resistance tester is known as the _____.

3 point method

56
New cards

Grounding requirements for AC systems are contained in _____.

NEC sections 250.20 and 250.21

57
New cards

Which of the following describes bounding?

Connecting to establish electrical continuity and conductivity.

58
New cards

Plate electrodes made of copper must be at least _____.

0.06" thick

59
New cards

The unintentional electrically conducting connection between an ungrounded conductor, of an electrical circuit and the normally noncurrent-carrying conductors, metallic enclosures, metallic equipment, or the earth

Gounod Fault=

60
New cards

Equipment grounding refers to connecting the normally noncurrent-carrying metal parts of equipment to the system grounded conductor and/or _____.

The grounding electrode conductor

61
New cards

In a separately derived system, the equipment bonding jumper connects _____.

system housing to the neutral bus bar