Grounding and Bonding, Level I - 2023 Lesson 6: Grounding Electrode Conductors

0.0(0)
studied byStudied by 0 people
0.0(0)
full-widthCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/44

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

45 Terms

1
New cards

A grounding electrode conductor connects a system grounded conductor, equipment, or both to a grounding electrode or to a point on the grounding electrode system.

True

2
New cards

Which NEC table is used for sizing grounding electrode conductors and bonding jumpers between electrodes in the grounding electrode system?

B. Table 250.66

3
New cards

A grounding electrode conductor installed for a communications system is required to be sized using NEC Table 250.66.

False

4
New cards

A grounding electrode conductor is a conductive body that extends the grounding connection.

True

5
New cards

Which of the following materials is not permitted as a wire-type grounding electrode conductor?

D. Steel

6
New cards

The amount of current present in a grounding electrode conductor during normal system operation is low because the earth is a(n) ? conductor and a high-impedance path for current.

D. poor

7
New cards

Table 250.66 is used only for sizing grounding electrode conductors for alternating current (AC) services.

False

8
New cards

If a service is supplied by 4/0 AWG copper ungrounded service-entrance conductors, what is the minimum size grounding electrode conductor required for a metal underground water pipe electrode?

D. 2 AWG copper

9
New cards

If a 400-ampere service is grounded by connection to a single ground rod, what is the maximum size grounding electrode conductor required?

B. 6 AWG copper

10
New cards

What is the maximum size copper grounding electrode conductor required for a 6,000-ampere service supplied by ten 750-kcmil copper service conductors in parallel for each ungrounded service entrance phase conductor?

A. 3/0 AWG copper

11
New cards

The maximum size grounding electrode conductor required for the minimum size ring-type electrode is not less than ? .

C. 2 AWG copper

12
New cards

What is the largest size required for a copper grounding electrode conductor that is connected only to a concrete-encased electrode?

C. 4 AWG copper

13
New cards

What is the largest size required for a copper grounding electrode conductor that is connected only to a rod, pipe, or plate electrode?

B. 6 AWG copper

14
New cards

If the DC system (source) is located on the premises, the grounding electrode conductor connection is required to be made at which of the following locations?

D. Any of the above locations

15
New cards

Grounding electrode conductors in sizes 6 AWG or larger must generally be protected in RMC, IMC, Schedule 80 PVC, RTRC-XW, EMT, or cable armor where installed in locations where they are exposed to physical damage.

True

16
New cards

Grounding electrode conductors are not permitted to be installed by routing them through metal framing members.

False

17
New cards

Grounding electrode conductors are generally required to be installed without a splice or joint.

True

18
New cards

Where a splice is made in a grounding electrode conductor, which of the following methods are permitted?

D. Any of the above

19
New cards

All grounding electrode conductors in sizes smaller than ? must be protected from physical damage by installation in raceway or cable armor.

A. 6 AWG

20
New cards

An aluminum or copper-clad aluminum grounding electrode conductor that is installed external to buildings or equipment is not permitted to be connected to a grounding electrode at a distance less than ? from the earth.

D. 18"

21
New cards

A single grounding electrode conductor connected to the grounding electrode system is permitted for a service, or individual grounding electrode conductors are permitted to be run from each electrode to the service equipment enclosure.

True

22
New cards

When installing grounding electrode conductor taps from a common grounding electrode conductor to each separate service disconnecting means enclosure, the minimum size required for the grounding electrode conductor taps is based on the ?

D. size of the largest ungrounded service conductor in each enclosure using Table 250.66

23
New cards

When using the common grounding electrode conductor tap method for grounding services with separate disconnecting means enclosures, the minimum size required for the common grounding electrode conductor is not less than 3/0 AWG copper or 250 kcmil aluminum.

False

24
New cards

Grounding electrode conductor connections are required to be accessible in all but which of the following locations?

D. All of the above

25
New cards

Where a metal underground water pipe is used as a grounding electrode, a bonding jumper is required for electrical continuity around any water meters, filtering equipment, or similar equipment.

True

26
New cards

Where a metal underground water pipe is used as a grounding electrode, if the grounding electrode conductor is a 3/0 AWG copper, what is the minimum size required for the required bonding jumper around any water meters, filtering equipment, or similar equipment?

C. 3/0 AWG copper

27
New cards

The interconnected metal structural frame of a building shall be permitted to be used as a conductor to interconnect electrodes of the grounding electrode system, or it is permitted to be used as a grounding electrode conductor.

True

28
New cards

Grounding electrode conductor connections are required to be made using any but which of the following?

I. Exothermic welding

II. Listed clamps

III. Listed lugs

IV. Listed pressure connectors

V. Other listed means

VI. Sheet metal screws

VII. Wrapping the conductor around the nut and bolt connection

B. VI. and VII.

29
New cards

More than one grounding electrode conductor is not permitted to be connected to a grounding electrode using a single clamp, unless the single clamp is ? for use with multiple conductors.

C. listed

30
New cards

Where a grounding electrode conductor is installed in a ferrous metal raceway that is not electrically continuous from the service cabinet to the grounding electrode, it must be made electrically continuous by bonding the contained grounding electrode conductor to both ends of the raceway.

True

31
New cards

A single grounding electrode conductor installed in a ferrous metal raceway must not exceed ? of the cross-sectional area of the raceway.

D. 53%

32
New cards

A grounding electrode conductor installed in a nonferrous metal raceway (such as aluminum conduit) is not required to be bonded to both ends of the raceway where it enters and emerges from the raceway.

True

33
New cards

Protection for grounding electrode conductors can be achieved by using Schedule 80 PVC in construction that is not fire rated.

True

34
New cards

Grounding electrode conductors are permitted to have which of the following physical characteristics?

D. Any of the above

35
New cards

Grounding electrode conductors must not be installed in lengths longer than ? .

D. There is no length restriction in the NEC; it is a design issue.

36
New cards

Referring to the drawing, what is the minimum-size copper grounding electrode conductor required for this service?

D. 1/0 AWG

37
New cards

Referring to the drawing, what is the minimum size copper grounding electrode conductor required for this service?

2 AWG

38
New cards

A 6 AWG or larger copper grounding electrode conductor that is exposed to physical damage shall be protected by any of the following except ? .

D. reinforced thermosetting resin conduit (RTRC)

39
New cards

Where a grounding electrode conductor for a 4,000-ampere service is connected only to two ground rod electrodes, the grounding electrode conductor is not required to be larger than 6 AWG copper.

True

40
New cards

Grounding electrode conductors smaller than 6 AWG shall be protected by installation in all but which of the following wiring methods?

C. FMT

41
New cards

Grounding electrode conductors and grounding electrode bonding jumpers in contact with the earth must comply with the burial depths in Table 300.5.

False

42
New cards

If a grounding electrode conductor is protected from physical damage with PVC conduit, the conduit is required to be Schedule 80.

True

43
New cards

Aluminum or copper-clad aluminum grounding electrode conductors are permitted within ? of the earth where installed in the bottom of an electrical enclosure that is listed for the environment.

D. Any of the above

44
New cards

Which of the following nonmetallic raceways is recognized in the NEC for protection of grounding electrode conductors from physical damage?

C. Schedule 80 PVC

45
New cards

Where a length of reinforcing rod (rebar) is used as a concrete-encased electrode, rebar extensions that exit from the concrete shall be permitted to be exposed to the earth without the use of corrosion protection.

False

Explore top flashcards

Basic Spanish
Updated 27d ago
flashcards Flashcards (22)
lang big vocab 1-3
Updated 627d ago
flashcards Flashcards (46)
chemistry ch 11
Updated 1071d ago
flashcards Flashcards (65)
Bio 160 - First exam
Updated 948d ago
flashcards Flashcards (200)
Unit 2 Test
Updated 20d ago
flashcards Flashcards (32)
English Vocab
Updated 40d ago
flashcards Flashcards (44)
Basic Spanish
Updated 27d ago
flashcards Flashcards (22)
lang big vocab 1-3
Updated 627d ago
flashcards Flashcards (46)
chemistry ch 11
Updated 1071d ago
flashcards Flashcards (65)
Bio 160 - First exam
Updated 948d ago
flashcards Flashcards (200)
Unit 2 Test
Updated 20d ago
flashcards Flashcards (32)
English Vocab
Updated 40d ago
flashcards Flashcards (44)