Where must you connect a hose in order to recover liquid refrigerant?

The liquid line.

2
New cards

After a leak repair of a supermarket rack using 300 Ibs. of R-22 and a successful initial verification test, when must a follow-up leak verification test be conducted?

Within 10 days.

3
New cards

After refrigerant liquid has been recovered from the appliance, any remaining vapor is;

Removed by the recovery system.

4
New cards

How can you speed up the removal of the refrigerant charge from a system?

Cooling the recovery cylinder to lower its pressure.

5
New cards

When could a reciprocating compressor be damaged if energized?

When the discharge service valve is closed.

6
New cards

Starting in 2019, what leak rate triggers the EPA requirement that commercial refrigeration systems containing 50 pounds or more of R-22 be repaired?

20%

7
New cards

For what refrigerant is an equipment room refrigerant detector NOT required under ASHRAE

Standard 15 provided the mechanical ventilation system in the machinery room runs continuously.

R-717

8
New cards

An initial leak verification test failed after repairing a leak in a rack refrigeration system for a supermarket using a CFC refrigerant. What would be the next step(s)?

Conduct additional repairs within the 30-day repair window or mothball the appliance.

9
New cards

Identify the best method to charge a system that has both an air-cooled condenser and evaporator with a nameplate charge of 80 pounds.

Liquid charge through the liquid-line service valve.

10
New cards

It is best practice to use dry nitrogen to break the vacuum when dehydrating by the triple evacuation method. However, it;

Requires a pressure regulator.

11
New cards

Every refrigerating system must be protected by which of the following?

A pressure relief device.

12
New cards

What action must an owner/operator take if a supermarket system containing 50 or more pounds of R-22 leaks more than 125% of its full charge in a calendar year.

Submit a report to EPA describing efforts to identify leaks and repair the appliance.

13
New cards

What is a moisture indicating sight glass useful for?

Checking for moisture in the refrigerant.

14
New cards

Which part of a belt-driven non-hermetic compressor is most likely to leak if the compressor has not been used for several months?

Rotating shaft seal.

15
New cards

You are changing out the compressor of a system containing 40 pounds of R-404A. In addition to isolating the compressor, which of the following procedures should you follow?

Evacuate the isolated section of the system to 0 psig and if system pressure does not rise after a few minutes, remove the compressor.

16
New cards

Which of the following refrigerants would be used in a low pressure appliance?

R-123

17
New cards

What steps should be taken before using a recovery unit to remove a charge?

The recovery unit oil should be changed and recovery cylinder evacuated.

18
New cards

Your recovery/recycling machine has R-22 refrigerant in it. You now have to recover refrigerant from a R-410 unit. What must be done before recovery?

Change the recovery cylinder on the recovery machine.

19
New cards

Before making a major repair, technicians must evacuate an appliance or component containing more than 200 pounds of R-410A to which of the following levels?

10 inches of Hg vacuum

20
New cards

Refrigerant cannot be recovered without isolating a parallel compressor system because of;

 An open equalization connection.