NFPA 72 Fire Alarm Test

0.0(0)
studied byStudied by 1 person
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
Card Sorting

1/456

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

457 Terms

1
New cards

Supervisory signals of a FA panel indicate what?

an off normal condition

2
New cards

Initiating devices can be considered to be ––––– devices.

input

3
New cards

Conventional FA initiating device circuits and notification device circuits fall under which classes (4)?

Supervised, non–supervised, alarm, and trouble

4
New cards

Four common FA initiating devices.

–Heat Detector\n–Smoke Detector\n–Manual Station\n–Flame Detector

5
New cards

This FA circuit does not use a monitoring current to monitor the integrity of the circuit.

SLC (Signaling Line Circuit)

6
New cards

What is the minimum number of adequate power supplies required for FA systems?

Two

7
New cards

There are 2 operating principals for heat detections they are –––––

Fixed Temperature and Rate of Rise

8
New cards

What is the correct mounting height for a wall mounted combination notification appliance? ––––– AFF and/or ––––– from the ceiling

–80–96"\n–6"

9
New cards

What is the correct mounting height and distance from the door for a manual station?––––– AFF and ––––– from the door

3 1/2' to 4 1/2'\n5

10
New cards

Notification appliances can be considered to be ––––– devices.

output

11
New cards

Smoke detectors can be mounted on both walls and ceilings. When mounting a detector on a wall, how far from the ceiling should the top of the detector be placed?

4 to 12"

12
New cards

What is the listed spacing of a spot type smoke detector?

none

13
New cards

Pressure switches are normally used to indicate flow on wet standpipe sprinkler systems T/F?

False

14
New cards

Supervisory switches mounted on a sprinkler stand pipe must cause a supervisory signal at the panel within how many turns of the hand wheel?

within the first 2 turns

15
New cards

Is "T" tapping a signaling line circuit permitted?

yes

16
New cards

Which code standard applies to FA systems?

NFPA–72

17
New cards

Activation of a suppression system connected to a FA system must cause what type of signal?

Alarm

18
New cards

Vane type water flow switches are equipped with an adjusted delay device to compensate for water surges and pressure fluctuations, what is the max allowable delay time?

90 seconds

19
New cards

NFPA 72 recommends using a distance of ––––– as a guide for spacing smoke detectors.

30 feet

20
New cards

An audible and visual signal shall be activated on a FA system when the normal power supply is reduced by what percent?

15%

21
New cards

After a FA system has been modified, repaired or the site specific software database has been altered, what must be performed?

a reacceptance test

22
New cards

A company or contractor who services FA systems or protective signaling systems must obtain a ––––– which covers this type of work?

State Contractor's License

23
New cards

What governs the installation procedures of a FA system?

NFPA 72

24
New cards

No FA system of FA devices may be installed in Nevada unless they are listed by?

Underwriters Laboratory (UL)

25
New cards

How many supervisory devices can be installed on one zone or initiating device circuit (IDC)?

20

26
New cards

A contractor or licensee must employ at least one qualified person who holds a ––––– to install and service protective signaling systems in order for their license to remain valid.

Certificate of Registration

27
New cards

Faults in other systems or components shall not affect the operation of FA system T/F?

True

28
New cards

If you change your address you must notify the State Fire Marshall in writing within how many days?

7

29
New cards

If you change your address, in addition to notifying the State Fire Marshall you must pay the associated fee, what is it?

$11

30
New cards

A coded FA system must automatically transmit at least ––––– rounds of the devices associated number.

3

31
New cards

Smoke detectors shall not be installed within how many feet of a supply register?

3

32
New cards

All FA systems and associated devices must be maintained and inspected in accordance with Table –––––

14.4.2.2 (2010)

33
New cards

You Certificate of Registration is valid from?

January 1st to December 31st

34
New cards

If you do not renew your Certificate of Registration before the expiration date what happens? (3)

You must reapply, pay fees, and re–test

35
New cards

If you provide service relating to the installation or maintenance of FA systems and you want to cancel a service contract, how many days written notice must you give before the cancellation is valid?

30 days

36
New cards

Before you can start work of a FA system installation what must be performed first? It must be approved by ––––

authority having jurisdiction

37
New cards

When a combination system is installed, FA signals must ––––– over any other signal.

take precedence

38
New cards

A permanent record of the time, date and location of all signals and restorations received and the action taken shall be maintained for at least ––––– and shall be made available to the State Fire Marshall.

1 year

39
New cards

All cables used in FA systems shall be installed in accordance with which code?

NFPA 70

40
New cards

All FA system devices must be installed in accordance with which code?

NFPA 72

41
New cards

All FA system trouble conditions must produce an audible and visual signal at the FACP. T/F?

True

42
New cards

Location of initiating devices, shall consider conditions such as high or low temperatures, humidity or sources of smoke that can lead to nuisance alarms. T/F?

True

43
New cards

In a system with a tone generator, the State Fire Marshal Regulations require that the tone be ––––– and ––––– enough to ––––– a sleeping person.

–unique\n–distinctive\n–awaken

44
New cards

An area covered by notification appliances that are activated simultaneously is called a ––––––

notification zone

45
New cards

May a device or system having materials different from those detailed in applicable standards be approved by the AHU if found to be equivalant?

yes

46
New cards

An over current protective device of suitable capacity capable of interrupting the maximum short circuit shall be provided in each ground conductor. T/F?

False

47
New cards

Automatic Extinguishment is a function of a FA system. T/F?

False

48
New cards

If ceiling heights allow, audible wall mounted devices shall have thier tops above the finished floor at heights of not less than ––––– and below the finished ceiling at heights not less than –––––

–90"\n–6"

49
New cards

A single fault on the SLC channel shall not cause an alarm signal at the FACP. T/F?

True

50
New cards

A single fault on the SLC channel shall cause a trouble signal. T/F?

True

51
New cards

For the purpose of alarm annunciation, each floor of the building is not considered a separate zone. T/F?

False

52
New cards

A distributor or installer of a protective signaling system must present the Atate Fire Marshal with evidence of his/her ability to respond for any needed repair and restoration within ––––– hours of being notified by the fire department.

24

53
New cards

Actuation of alarm notification appliances or emergency voice communications and annunciation at the protected premises shall occur within ––––– after the activation of an initiating device.

10 seconds

54
New cards

Notification of the –––––– shall be made prior to alteration of equipment or wiring.

authority having jurisdiction

55
New cards

Shunt type auxiliary systems shall be arranged so that one auxiliary transmitter does not serve more than 125,000 sq feet total area. T/F?

False

56
New cards

According to the State Fire Marshal regulations, who is responsible for determining that the number and placement of loudspeakers as part of protective signaling systems meet the requirements of applicable standards?

The building architect

57
New cards

The operation of all fire safety functions shall be verified by an operational test at the time of system acceptance. T/F?

True

58
New cards

An actuating device held or locked in the activation position shall prevent the activation and transmission of all other messages. T/F?

False

59
New cards

Self powered boxes shall have sufficient power for uninterrupted operation for a period of not less than ––––– months.

6

60
New cards

The transmitting device shall be located as required by the AHJ. T/F?

True

61
New cards

What shall be required where in duct smoke detectors are installed in concealed locations more than 10 feet AFF or in arrangements where the detector's alarm or supervisory indicator is not visible to responding personnel? (2)

A sign indicating the duct detectors location and a remote alarm or supervisory indicator

62
New cards

In a coded, wired reporting system, using a constant current (100 milliamp) system, all devices connected in series with any alarm circuit shall function when the alarm circuit current is reduced to ––––– % of normal.

70%

63
New cards

100,000 sq ft is the largest area any one zone shall be. T/F?

True

64
New cards

If an intermittent trouble signal is used, it shall sound at least every 10 seconds with a minimum duration of 1/2 second. T/F?

True

65
New cards

What is a document that acknowledges the features of installation, operation, performance, service and equipment with representation by the property owner, system installer, system supplier, service organization, and the AHJ called?

Record of certification

66
New cards

A 1/3 octave filter has a bandwidth that comprises a frequency range with a factor of 2 1/3. The octave filter can be subdivided into three 1/3 octave bands. T/F?

True

67
New cards

A defined area within the protectged premises. A ––––– can define an area from which a signal can be received, an area to which a signal can be sent, or an area in which a form of control can be executed.

zone

68
New cards

A public FA reporting system is called a ––––– FA system.

Municipal

69
New cards

The decision to designate a standard as a ––––– is based on such factors as the size and scope of the document, its intended use and form of adoption and whether it contains substantial enforcement and administrative positions.

Code

70
New cards

A ––––– is a standard taht is an extensive compilation of provisions conveying a broad subject matter that is suitable for adoption into law independently.

code

71
New cards

–––– is a fire detector that detects either abnormally high temperature or rate of temperature rise, or both.

Heat detector

72
New cards

The location of the equipment needed to relay signals between supervising stations, subsidiary stations, and protected premises is a –––––

Repeater station

73
New cards

A ––––– is an assembly that incorporates the detector, the control equipment, and the alarm–sounding device in one unit operated from a power supply either in the unit or obtained at the point of installation.

Single station alarm

74
New cards

If an intermittent signal is used, it shall sound at least once every 10 seconds, with a 1/2 second minimum duration, this applies to ––––– signals.

trouble

75
New cards

An –––––– system is one in which signaling devices such as transponders are employed to transmit status signals of each initiating device or initiating device circuit within a prescribed time interval so that the lack of receipt of such a signal can be interpreted as a trouble.

active multiplexing

76
New cards

–––––– is the maximum number of discrete elements of FA systems permitted to be used in a particular configuration.

Loading Capacity

77
New cards

A ––––– is a publicly accessible FA box that can also be operated by 1 or more remote initiating devices or an aux. fire system used to send an alarm to the public fire service communiciations center.

Master box

78
New cards

A ––––– is a detector comprising of an assembly that incorporates a sensor, control components, and alarm notificaton appliance in one unit that is operated from a power source either located in the unit or obtained at the point of installation.

Single Station Alarm Device

79
New cards

A –––– is a single station alarm capable of being interconnected to one or more additional alarms so that the actuation of one caused the appropriate alarm signal to operate in all interconnected alarms.

Multiple Station Alarm

80
New cards

A ––––– is a system component that provides an interface between signaling line circuits, initiating device circutis, or control units and the transmission channel.

Transmitter

81
New cards

A –––––– is a fire alarm system component such as a bell, horn, speaker, light or test display that provides audible, tactile, or visible outputs, or any combination thereof.

Notification appliance

82
New cards

The ––––– is the root mean square A–weighted, sound pressure level measured over the period of time that any person is present, or a 24 hour period, whichever time is lesser.

Average Ambient Sound Level

83
New cards

––––– is an audible or visible signal that conveys several discrete bits or units of information.

Coded

84
New cards

A –––––– is a device that responds when its operating element becomes heated to a predetermined level.

Fixed–Temperature Heat Detector

85
New cards

An ––––– is the bandwidth of a filter that comprises a frequency range of a factor of 2.

Octave

86
New cards

A ––––– is a document that acknowledges the features of installation, operation, service, and equipment with representation by the property owner, syste installer, system supplierm service organization, and AHJ.

Record of Completion

87
New cards

Visual and audible means to indicate a ––––– % or greater reduction of normal power supply shall be provided.

15

88
New cards

Reacceptance testing shall be performed after any of the following (3) –––––

–Added or deleted system components\n–Modification, repair or adjustment to system hardware or wiring,\n–Any change to site specific software

89
New cards

In order to perform service work on a protective signaling system, the company must obtain a state contractor's license which covers this type of work. T/F?

True

90
New cards

An over current protective device of suitable current carrying capacity capable of interrupting the max short circuit shall be provided in each ground conductor? T/F?

False

91
New cards

A licensee must employ at least one person qualified and who holds a certificate of registration card to install and service protective signaling systems in order for the license to remain valid. T/F?

True

92
New cards

Faults in other systems or components shall not affect the operation of the fire warning system. T/F?

True

93
New cards

No fire system device or component of any fire system may be installed in Nevada unless listed by –––––

UL (Underwriters Laboratory)

94
New cards

The number of supervisory devices permitted to be connected to a signal initiating device circuit shall not exceed –––––

20

95
New cards

If you have a change of address, you must per state law, notify the Office of the State Fire Marshal in writing within ––––– days and pay the fee of –––––.

7\n$11

96
New cards

For the purpose of alarm annunciation, each floor of the building is not considered as a separate zone. T/F?

False (it is)

97
New cards

Each coded radio box shall automatically transmit a test message at least once in each ––––– hour period.

24

98
New cards

A distributor or installer of protective signaling systems may install a system without a license issued by the State Fire Marshall. T/F?

False

99
New cards

Location of initiating devices, shall consider conditions such as high or low temperatures, humidity or sources of smoke that can lead to nuisance alarms. T/F?

True

100
New cards

In a system with a tone generator, the State Fire Marshall Regulations require that the tone be –––––

unique and distinctive enough to awaken a sleeping person.