DT-1
Alarm: high temp reflector outlet (55C)
DT-3
Alarm: High temp d20 cleanup (50C)
GT-3
Alarm: abnormal recombiner temp (<50C >120C)
DL-2
interlock: secures dm-2 at 2.5” level in dump tank
DL-6
Scram: Low level reflector tank (4” below overflow)
TS: 4” below overflow
DL-9
Alarm: No overflow reflector tank
Interlock: Withdraw permit circuit operator takes ctrl
DL-10
Alarm: low level dump tank (2” below startup)
GL-1
Alarm: Low level D20 gasholder (8 cu ft)
High Level d20 gasholder (60 cu ft)
DF-1
Scram: Low flow D20 (90 gpm)
TS: Reflector Flow (75 gpm)
DF-2
Alarm: Low Flow Transfer pump (1.5 gpm operator takes manual ctrl)
GPS-1
Alarm: Low Pressure D20 He System (0.4” H20)
GPS-2
Alarm: High Pressure D20 He system (2.5” H20)
GPS-3
Alarm: Low flow recombiner (1.5 cfm)
DC-1
Alarm: High Specific Conductance D20 (1 microS/cm>startup level)
DC-2
Alarm: High Specific Conductance D20 (1 microS/cm>startup level)
DV-4
Interlock: Minor Scram and secures DM-2
TS: dump reactivity worth>reactivity worth of most reactive shim blade + reg rod