Estimated cutting time for 18-inch ductile iron pipe
Approximately 18 minutes; based on a guideline of 1 minute per inch of pipe.
Maximum trench width for an 8-inch concrete pipe
24 inches.
Who may operate valves and hydrants serving a new main
Waterworks employees only.
Backfill compaction in Type 4 laying condition
Approximately 80 percent of standard Proctor.
Flat bottom trench
Undisturbed earth.
Pitometer taps placement on ductile iron pipe
At the 12 o'clock position (top of the pipe).
Weight of a 20 ft length of 12-inch push-on ductile iron pipe at 350 psi
725 pounds.
Torque range for a 5/8-inch bolt in a mechanical joint
45 to 65 foot-pounds.
Action if mud or trench water has stood in a section of new pipe
Scrub the inside with a strong chlorine solution and flush pipe out.
Hydrostatic testing Method A
Method A.
Hydrostatic testing allowance for 1500 feet of 12-inch ductile iron pipe at 350 psi
17,106 pounds.
Hydrostatic testing leakage allowance
2.28 gallons per hour.
Maximum stacking height for ductile iron pipe
12 feet.
Minimum cover for water mains to cushion traffic shocks
2.5 to 3 feet.
Maximum size stone to improve trench bottom
3 inches.
Minimum excavation clearance when excavating rock for pipe size 24 inches or less
6 inches.
Pile location for excavated trench materials
Street side of the main.
Minimum width of wooden walkways with side guard fences when trenching destroys sidewalks
4 feet.
Minimum casing size under railroads/highways where casing is required (larger than bells' outside diameter)
6 to 8 inches.
Pavement cut width wider than trench to permit firm foundation when street is replaced
6 inches.
Casing size larger than pipe when required
6 to 8 inches larger than the pipe.
Gasket material for connecting two mechanical-joint flanged ductile iron pipe pieces
Rubber.
Painted lines around steel pipe for push-on joints represent
Seating of the pipe properly into the bell socket.
Definition of 'rock' in trench backfill
Rock refers to large gravel formations where loose cobbles are more than 8 inches in diameter.
Maximum offset for a 20 ft length of pipe with 5% deflection (MJ pipe)
22 inches.
Best saw for out-of-trench cuts on any size pipe
Abrasive cut-off saw.
Purpose of thrust blocks or kick blocks
To resist resultant forces.
Process of seating plain end into a bell socket
Inserting plain end into the socket.
Maximum direct-tap size for a 4-inch pipe with 0.49 wall thickness
1-1/4 inches.
Maximum direct-tap size for a 12-inch pipe with 0.73 wall thickness
2 inches.
Outside diameter of flange welded on a UB S-12 plate
19 inches.
Required opening in a concrete vault for a valve with a 12-inch inside diameter pipe
18 inches.
Suitable backfill for ductile iron pipe
Good quality materials.
Maximum deflection angle for ductile iron pipe
5 degrees.
Waterproof barrier coating for insulation of ductile iron pipe consists of what?
Asphalt.
Definition of undisturbed earth (alternate entry)
Flat bottom trench