1/110
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced |
---|
No study sessions yet.
addressable device
an FDAS component that can be individually identified of its status or used to individually control other functions
addressable system
A system consisting of an addressable fire alarm control panel and addressable devices that primarily give the exact location of a fire, among other features.
alarm
a notice or warning of danger
false alarm
an alarm caused by a non fire incident or activity such as smoking, cooking
nuisance alarm
an alarm caused by malfunction, equipment defect, improper installation, or poor maintenance
alarm zone
location or part of the protected building or premises
annunciator
An FDAS component containing one or more indicator lamps/LED's or alphanumeric displays in which each indication provides status information about an addressable or conventional device, a group of devices, a zone, a circuit, or an LCD and Graphic condition.
Authority Having Jurisdiction (AHJ)
The office of Bureau of Fire Protection and the Office of Building Official
central station
An entity controlled and operated by a person, firm, or corporation whose business is the monitoring, recording, and maintaining of supervised alarms automatically transmitted to it by the FDAS of a subscriber of this service, and who upon receipt of such signals shall take such actions as required by the AHJ and the subscriber.
conventional system
A system with a conventional fire alarm control panel and conventional devices that is wired in a way that divides the protected building or premises into parts or subdivisions which are called alarm zones.
conventional device
An FDAS component, such as a smoke An FDAS component, such as a smoke detector, heat detector, or manual fire alarm station, that does not have an electromechanical or software address that gives it a discrete identity.
detector
a device or component that is used to sense the products of fire, such as smoke, heat, flame, or carbon monoxide
smoke detector
A detector that detects particles of combustion, whether visible or invisible.
heat detector
A detector that detects abnormally high temperature, abnormally fast rate of temperature rise, or both.
multi-criteria detector
a detector that contains two or more sensors that tracks the corresponding products of fire, such as smoke, heat, flame, or carbon monoxide, and transmits signal to the fire alarm control, which shall be mathematically evaluated with pre-programmed algorithms to determine when an alarm signal is warranted
objective is to reduce false alarms
duct detector
a smoke detector, using sampling tubes, that senses smoke in the air circulating within air-conditioning or ventilating ducts
beam detector
A smoke detector that senses smoke along a continuous path, usually installed in high-ceiling areas
also called a projected beam smoke detector
flame detector
a detector that senses and detects the radiant energy emitted by a flame
air sampling-type detector
a detector that consists of piping layout or network that runs from the detector to the protected areas.
carbon monoxide detector
a detector that senses and detects abnormally high levels of carbon monoxide
Emergency Communication System
a sub-system of an FDAS that broadcasts the existence of a fire or an emergency situation to facilitate appropriate action
Emergency Voice Alarm Communication (EVAC)
It is a sub-system that broadcasts information during an emergency to the occupants of a building or facility and instructs appropriate actions to them, such as evacuating. It is conveyed by audible or visible means, or both.
Two-Way Emergency Communication System
it is a sub-system intended for use by the building fire safety personnel or by fire responders and first responders to both exchange and communicate information.
Fire Alarm Control Panel (FACP)
An FDAS component, provided with primary and secondary power supplies that receives signals from initiating devices, such as detectors and manual fire alarm stations, and processes these signals to determine the required output functions, such as activation of notification appliances, annunciators, and the one-way emergency communications system.
Conventional Fire Alarm Control Panel
an FACP that comes with one or more alarm zones and can only connect conventional devices
Addressable Fire Alarm Control Panel
An FACP that comes with one or more signaling line circuits, called addressable loops, to which addressable devices are connected.
Fire Command Center
The room or principal location wherein the FACP and other life safety system are located to display and monitor all fire alarms and system troubles, and from which all output functions are automatically and manually controlled.
Manual Fire Alarm Station
an FDAS component that is manually operated to initiate a fire alarm signal
Notification Appliance
an FDAS component such as a bell, horn, speaker, strobe, or text display that provides audible or visible outputs, or both
Audible Notification Appliance
a notification appliance that warns by the sense of hearing
Exit Marking Audible Notification Appliance
an audible notification appliance that marks building exits, floor exits, stairwells, or paths to exits for the purpose of evacuation or relocation
Visible Notification Appliance
a notification appliance that warns by the sense of sight
Tactical Notification Appliance
a notification appliance that warns by the sense of touch or vibration
Personnel
people who install, maintain, service, test, and/or inspect fire detection and alarm system
Maintenance and Service Personnel
individuals who perform cleaning, adjustments, replacements of equipment & components, system programming, and other maintenance work according to the manufacturer's recommendations for the system to perform as required
Testing Personnel
individuals who perform physical checks, tests, and procedures to determine whether a system performs as required for acceptance or reacceptance
Inspection Personnel
individuals representing the AHJ who perform physical checks, tests, and procedures to determine whether a system functions and performs as required, as partial compliance for issuance of a Fire Safety Inspection Certificate
Power Supply
source of electricity that provides the power needed to operate the FACP, and consequently all devices connected to it
Primary Power Supply
the 220VAC power voltage from the electrical utility company which is converted to 24 VDC within the FACP
Secondary Power Supply
when there is a failure of the primary power supply, the batteries (serving as the secondary power supply) automatically switch over to provide uninterrupted power to the system
Semi-addressable System
a system consisting of an addressable fire alarm control panel and conventional devices connected to it through input addressable modules
shall
indicates a mandatory requirement
should
indicates a recommendation, but not required
800 sq. m
maximum floor area of an alarm zone
15 dB, 5dB, 30s
audible notification signal shall have a sound level of at least _____ above the average ambient sound level or _____ above the maximum sound level of having a duration of at least ___
red
color of the manual fire station
400 sq m, 2 floors, 10 m
buildings, structures, or facilities not more than ___ in floor area, nor more than ___ floors or levels, and with a height of not more than ___ may choose not to install an FDAS
50 sq m
each battery-operated, stand-alone detector shall cover a floor area of not more than
600 mm
spaces under raised floor more than ___ in height should use conventional detectors and wired as a separate zone
1 m
spaces above drop ceiling more than ___ in height should use conventional detectors and wired as a separate zone
1 m
concealed spaces under the roof more than ___ in height should use conventional detectors and wired as a separate zone
a) 4 sq m
b) 1 sq m, 0.5 sq m
c) 250 mm
detection is not required in areas:
a) toilet and bathrooms with a floor area less than ___
b) walk in type enclosure with a floor area not more than ___ or one with floor area not more than ___ if it contains electrical or comms equipment
c) space sunder raised floor with a height of _____ or less
alarm monitoring services
all installed FDAS should subscribe to the _______ of a central station
detect fire at the earliest stage and give alarm to occupants so appropriate action can be taken
the purpose of of a fire detection and alarm is
1 m
detectors shall be located with a t least ___ radial distance to air blowers or air diffusers
2 or 3 panels
required number of panels networked together if the number of buildings in a multi-building complex exceeds 3 or if total floor area of all buildings in the complex exceeds 40,000 sq m
30 deg C
the FACP, network display and all panels in the network shall be located in a position where temperature shall not exceed
8,000 sq m or more
For buildings or facilities with a total floor area of _ sq. m. , semi-addressable system, or addressable system shall be used.
8,000 sq m or less
For buildings or facilities with a total floor area of __ sq. m. or less, a conventional system, semi-addressable system, or addressable system shall be used.
5°C, 45°C, 93%
Smoke detectors shall not be installed if: Temperature is below __ Temperature is above __ Relative humidity is above __
300 mm
SD shall be located on the ceiling, if installed on a sidewall, it shall be located at a point not more than ___ mm from the ceiling to the top of the detector
9 m, 6.4 m, 300 mm and 4.5 m
For flat ceilings with a height of not more than 4 m
1. SD spacing shall not be more than ___ m
2. All points on the ceiling shall have a detector within a distance of ___ m
3. Spacing of detectors from walls or partitions shall not be less than ___ mm and not more than ___ m
4.5 m, 3.18 m, 300 mm and 2.5 m
For flat ceilings with a height more than 4 m but not more than 6m
1. SD spacing shall not be more than ___ m
2. All points on the ceiling shall have a detector within a distance of ___ m
3. Spacing of detectors from walls or partitions shall not be less than ___ mm and not more than ___ m
beam-type smoke detector
For ceilings with a height of more than 6m, spot-type SD shall not be used, instead ___ SD shall be used.
20
the quantity of smoke detectors connected on a single zone of a conventional system, or to a zone monitor module in a semi-addressable system shall not be more than
Fixed temperature heat detector
this type is designed to operate when a pre-selected temperature is closed
Rate-of-rise heat detector
this type is designed to operate the temperature rises abnormally quickly, around 8.3°C/minute. It is also designed to operate when a pre-selected temperature is reached
11 deg C
temperature rating of the heat detector shall be at least ___ above the maximum expected temperature at the ceiling
7.5 m, 5.3 m
For flat ceilings with a height of not more than 4 m
1. HD spacing shall not be more than ___ m
2. All points on the ceiling shall have a detector within a distance of ___ m
150 mm - 300 mm
HD shall be located on the ceiling, if installed on a sidewall, it shall be located at a point not less than ___ mm and not more than ___ mm from the ceiling to the top of the detector
150 mm, 3.75 m
spacing of heat detectors from walls or partitions shall not be less than ___ mm and more than ___ mm
40
the quantity of heat detectors connected on a single zone of a conventional system, or to a zone monitor module in a semi-addressable system shall not be more than ___
93%
a heat detector shall not be installed in a location wherein the ambient location is such that relative humidity is above
4m
if the ceiling height is more than ____ , heat detectors shall not be used
carbon monoxide (DO)
odorless, tasteless, colorless gas that is a product of incomplete burning of various fuels and of equipment powered by internal combustion engines
20
all indoor and below-ground parking areas that accommodate more than ___ vehicles shall have a carbon monoxide detector
1.4 m
manual fire alarm stations shall be installed at a height of ______ above the finished floor level and shall be located at easily accessible points, free from obstructions
1.2 m
manual fire alarm stations shall be located within ___ of each exit door on each floor
30 m
Additional manual fire alarm stations shall be located that from any point within the building, the travel distance to activate the alarm shall not be more than ___ m, measured horizontally on the same floor
65 dBA, 10dB, 30s, 1.4m
A sufficient number of audible notification appliances shall be used to produce a minimum sound level of ___ dBA or 10 dB above the ambient noise level having a duration of at least ___ s , whichever is greater, measured ___ m above the floor in the area required to be served by the system
115 dBA
The sound level produced by audible notification appliance and the ambient noise combined shall not exceed ___ dBA
10s
The actuation of notification appliances shall occur within ___ s after the activation of an initiating device
150 mm, 80 dBA
The bell shall be the most basic notification appliance. It shall have a diameter of at least ___ mm and an output sound level of at least ___ dBA
10,000 sq m
A one-way emergency communications sub-system networked shall be required for the: Transportation terminals with total floor area of more than ___ sq.m.
15,000 sq m
A one-way emergency communications sub-system networked shall be required for the: Shopping malls, with total area of more than ___ sq.m.
15,000 sq. m, 15 floors
A one-way emergency communications sub-system networked shall be required for the: Hotels, with total area of more than ___ sq.m or with more than ___ floors
20,000 sq. m, 20 floors
A one-way emergency communications sub-system networked shall be required for the: Office buildings, with total area of more than ___ sq.m or with more than ___ floors
25,000 sq. m, 25 floors
A one-way emergency communications sub-system networked shall be required for the: Residential bldg./condo, with total area of more than ___ sq.m or with more than ___ floors
2W RMS
speakers used in one-way emergency communications sub-system shall be connected at ___ W RMS power setting
10 zones
for a conventional system with an FACP of more than ___ zones, a two-way communications sub-system shall be required
200
for addressable and semi-addressable system with more than ___ automatic detectors, a two-way communications sub-system shall be required
common talk or conference call mode
the two-way telephone communications sub-system shall operate on a _____
central processing unit (CPU)
the two-way telephone communications sub-system shall be networked with the panel's _____
FACP or Fire Command Center
the primary display or fire point-zone annunciation shall be at the ___
ground floor, security doors
each elevator will automatically go the ____ and all of ____ will unlock in the event of fire
220 - 240 VAC
the primary power supply to the fire alarm control panel and hence to the entire system shall be from electric utility company, normal direct or derived ___ VAC single phase
50 VDC
the system operating voltage shall be extra low voltage of not more than ___ VDC
75%
the battery charger shall be capable of recharging the batteries, discharged to its minimum voltage, to at least ___% of its rated capacity within 24 hours, and to its rated capacity within another 48 hours.
Building Management System (BMS)
___ shall not control the functions of the FDAS but can only monitor it. The FDAS shall be capable of operating independently at all times
RA 9514
Revised Fire Code of the Philippines 2008