what cools CE isophase?
Turbine cooling water
what happens to stator cooling on a loss of NKN-D41?
no stator cooling trips
how do we do the auto start test?
press a button that simulates a low flow condition, pump must be manually secured
what three signals from the main turbine will not start the standby pump?
generator differential, stator ground, and unit differential
what will happen when you get the stator cooling green trouble alarm?
you have 70 seconds to resolve the issue or the unit will trip
what is the purpose of SLMS
monitors H2 being vented to the roof
how many quadrants are lost for CEDMCS on a loss of PND
¼ anti pac man
what does a CWP prevent?
CWP prevents all outward CEA motion in any mode
where can the RTSG breakers be operated from?
locally at the breaker, the SPLA, and PPS
what is the maximum limit we can withdraw a CEA
maximum withdrawal is the upper electrical limit (UEL)
what do the RSPT input to the PC when a rod drops?
inputs a 0
if the CWP is placed in bypass what is the one mode of operation the CEA CAN NOT be moved in?
they can not be moved in stby with CWP bypassed
what signals will bring in a CWP?
2/4 HI PZR pre trip
2/4 LO DNBR pre trip
2/4 HI LPD pre trip
RPCB (clears after 10 seconds)
CEA misalignment from CPC/CEACS
what rates can we insert CEAS?
CEAS move in at 30 inches per minute or 3 inches per minute
how many inches is reg group overlap?
90 inches
where do we get the UGS (upper group stop) and LGS (lower group stop)?
they are generated from up and down pulse counts from internal logic from ovation
what happens to pulse counters on a CEA slip (not drop)
counters will not see a Slip and will not reset at all
what does CEACs provide on a CEA deviation
provides a penalty based on direction of deviation
what are the safety channels calibrated to?
safety channels are calibrated with JSCALOR
what happens if FW flow is less than actual?
the VOPT will be less conservative
what happens to COLSS if in core instrumentation fails?
COLSS will be out of service
what does the power limit margin compare?
compares licensed power to selected power (smooth)
If COLSS Tcold lowers by 5f what happens to power as read by JCPCAL immediately, and over an hour
If Tcold goes down power will initially go up but over time will be corrected by JSCALOR and brought back down
what happens to tilt on a slipped CEA?
tilt will go up due to ICI seeing flux shifting
how does COLSS see view a dropped CEA
COLSS will view a dropped CEA as if the whole group has dropped
what happens to LPD POL if CEAs lower in the core
LPD POL will lower
what happens of LPD and DNBR POL if PZR pressure lowers
DNBR pol lowers, but LPD pol is unaffected
what happens to JSCALOR if FW temp fails low
JSCALOR will go up and overtime affect the other powers
what happens to DNBR POL if ASI becomes more negative
DNBR POL goes down
what is the purpose of COLSS vs CPC
COLSS is for indications and alarms
CPC is for protection and trips
if BD is secured with constants still in what will happen to JCPCAL?
initially lower and lower an hour later due to a lowering JSCALOR
If RCP DP lowers what is the affect on NKBDELT
RCP DP lowering will cause NKBDELT to go up
if BD is secured but constants are still in, what affect does this have on the JSCALOR VOPT
JSCALOR VOPT is less conservative
how are input failures sensed by PC and CMC
Input failures are sensed by both the PC and CMC
How are alarms reported in the control room?
reported to the CRS without delay using 3 way communication
what is unique about the BDAS and PDIL alarms
these alarms can not be left in fast flash
who is allowed to take command function in mode 5 and 6
an RO is now able to take command of the control room
what are the two handed operations in the control room
ADV, Aux feed, HPSI, SIAS/CIAS
how often does an RO perform board walkdowns
walkdowns performed every two hours
who is responsible for overall appearance of the CR? who is responsible for scheduling painting and MODs
SM is responsible for the overall appearance of the control room
UOM is responsible for scheduling painting and mods
what is required in order for the peer checker and the IV to be the same person
SM approval and a CR must be generated
what defines an “expected alarm”
the alarm must be briefed
who monitors the plant during shift turnover?
OATC
describe the alignment for control oil cleaning
control oil flow control valve diverts flow through filters for clean up
what is the logic and setpoint for EHC turbine trip?
setpoint at 1100 psig
2/3 logic
when does the standby control oil pump auto start?
auto starts at 1300 PSIG