What counts as a HV System?
>60V DC or 25V AC (RMS)
What is Galvanic Separation?
Isolation between circuits that prevents current from flowing between them, even if info is shared between them in other ways (such as through capacitance, inductance, etc).
Is the tractive system motor allowed to be connected directly to the accumulator?
No, must be connected through the motor controller
What is the maximum power draw from the accumulator?
80kW
What is the maximum voltage between any two points in the tractive system?
600V
How is the max power and voltage checked by the event organizers?
Through the Energy Meter provided by the event
What counts as a "violation"?
When the power or voltage values are exceeded either: a) continuously for over 100ms b) at all after a moving average over 500ms is applied
What is the penalty for a violation?
Best run of the team eliminated, or 60s penalty in endurance, plus add'l penalties at discretion of organizer up to DQ
What is the main restriction on drive-by-wire?
The algorithm may only LOWER the drive torque requested by the driver, it cannot increase the torque request
What is the brake pedal plausibility test?
Power to the motors must be shut down if the mechanical brakes are actuated and the accelerator pedal is at 25% pedal travel or more. Power must remain off until the accelerator pedal position drops below 5%, regardless of whether the brakes are still actuated
What is the maximum voltage and energy allowed in each segment of the accumulator?
120V, 6MJ
What voltage must every wire in the accumulator container (regardless of whether or not it is in the high current path) be rated to?
the max voltage of the accumulator
How many accumulator isolation relays are required?
Min. two
What is the maximum accum. cell temperature?
60deg C or max on the datasheet, whichever is lower
Where must the temperature on the cell be measured?
At the negative terminal on the terminal or the bus bar (if on bus bar, less than 10mm from the terminal)
What is the minimum number of cells that must have their temperature monitored by the AMS (BMS)?
20% for Lithium Ion, equally distributed through the pack
If the temp or cell voltages are exceeded, what must happen?
The AMS must open the AIRs (Accumulator Isolation Relays) and Red LED must turn on in the cockpit
All electrically conductive parts of the vehicle (parts made of steel, (anodized) aluminum, any other metal parts, etc.) which are within 100 mm of any Tractive System component must have a resistance below what?
300 mOhms
All parts of the vehicle which may become electrically conductive (completely coated metal parts, carbon fiber parts, etc.) which are within 100 mm of any tractive system, must have a resistance below what?
5 Ohms
Where must tractive system measuring points be placed?
Two on positive/negative inverter supply lines
Two on charger output lines
Physically, what should tractive system measuring points look like? How should they be enclosed?
Red 4mm shrouded banana jacks
Marked HV+ and HV-
Enclosed by nonconductive housing that can be opened WITHOUT tools
What value resistance should the tractive system measuring point have?
Vmax<=200V --> 5kOhm
200 -400V Vmax --> 10kOhm
400-600V Vmax --> 15kOhm
What should the system ground measuring point look like/how should it be enclosed?
Black 4mm shrouded banana jack, marked GND, next to tractive system measuring point
It must not be possible to touch any tractive system connections (wires etc) with a ___ mm long, ___ mm diameter test probe when the tractive system enclosures are in place.
100mm long, 6mm diameter
What IP rating should tractive system components and containers be rates to?
IP65 recommended, but actual rule is that it "must be protected from moisture in the form of rain or puddles"
What is the minimum insulation material temp rating?
90deg Celsius
Wires must be marked with ____
wire gauge, temperature rating, and insulation voltage rating. (serial number is sufficient if provided with a datasheet)
What is the minimum temp rating for tractive system cables?
90deg Celsius
All tractive system wiring that runs outside of electrical enclosures must be enclosed in _____
separate orange nonconductive conduit or use an orange shielded cable