What conditions allow for a system to be opened and repaired without recovering the refrigerant to the required vacuum level?
A system with a large leak and internal pressure of 0 psig
Refrigerant should be recovered from the condenser outlet if the condenser is;
Below the reciever
What can be done with a refrigerant trace gas and nitrogen mixture after a system leak is found?
Release into the atmosphere
Leaks must be repaired on industrial process and refrigeration units with a 50-pound charge or greater when the annualized leak rate reaches _____ or more.
30%
What must the equipment owners/operators include in recovered refrigerant records for equipment with refrigerant charges that range from 5 to 50 pounds?
The quantity of refrigerant (by type) added or recovered from disposed appliances in each calendar month and quantity of refrigerant (by type) sent for reclamation or destruction.
What happens to a refrigerant that is heated above the saturation temperature?
It remains in the vapor state
Unless plans are made to replace a system with a leak rate that exceeds the maximum leak rate, repairs must be made within;
30 Days
Which of the following refrigerants is classified as a very high-pressure refrigerant?
R-744
Proper recovery techniques begin with the use of appropriate recovery equipment that has been certified by;
EPA approved laboratory
A high-pressure appliance containing 210 lbs. of R-407C refrigerant must be evacuated (recovered) to a level of
10 Inches of Vaccum
A crankcase heater is often used to prevent refrigerant from mixing with compressor oil during periods of:
Low ambient temperature
All HVAC/R systems must be protected by a;
Pressure Relief Valve
A comfort cooling system that contains 50 pounds or more of R-410A is leaking. What will be the new maximum allowable annual leak rate starting in 2019?
10%
Refrigerants CFC-12, HCFC-22, and HFC-134a are all classified as Type _______ substances.
A-1
A high-pressure appliance containing less than 200 lbs. of an HCFC or HFC refrigerant must be evacuated (recovered) to a level of
0 inches of vacuum
EPA regulations require that all Industrial Process Refrigeration (IPR) systems containing more than 50 pounds of refrigerant MUST be repaired when the annual leak rate exceeds;
30%
When using a recovery unit on a system containing 100 lbs. of R-410A it must be evacuated to;
0 inches of mercury
A new split system should be checked for leaks by;
pressurizing the system with a few ounces of system refrigerant and an inert gas.
When an appliance containing 50 pounds or more of a regulated refrigerant leaks refrigerant at an annual rate of 125% or more, what must be included on the leak inspections records?
Initial verification, verification tests and records of recovered refrigerant from equipment.
A refrigerant sensor which will sound an alarm and automatically start a ventilation system in occupied equipment rooms falls under ASHRAE Standard;
15
EPA regulations state that removal of which component constitutes a "major repair"?
compressor
Non-condensables will cause;
High Discharge Pressure
When recovering refrigerant from a medium-pressure system with more than 200 lbs. of refrigerant, recover to a level of
15" Hg
If a leaking appliance with a regulated refrigerant is not going to be repaired, it must be;
retrofitted or retired within 12 months.
When dehydrating a system, it should be evacuated to a minimum level of;
500 microns