1/61
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced |
---|
No study sessions yet.
Where there is a requirement to add a second grounding electrode, the two electrodes must be separated at
least 6 feet apart.
the unintentional electrically conducting connection between an ungrounded conductor, of an electrical circuit and the normally noncurrent-carrying conductors, metallic enclosures, metallic equipment, or the Earth.
A ground fault is
When a main bonding jumper is required by the NEC,the jumper
cannot be less than 12.5% of the area of the largest phase conductor.
A grounding test utilizing an earth ground resistance tester known as
the 3-point method.
( or neutral ) is what connects to the neutral terminal bus of a main panel.
Grounding electrode conductor
If single-gang nail-on non-metallic boxes are used with NM cable, which of the following is true ?
No connection to the box is required
Grounding requirements for AC SYSTEM are contained in
NEC section 250.20 and 250.21.
An acceptable grounding electrode is
the Metal frame of a building which is effectively grounded.
Ultimately, the ground fault is cleared
when the overcurrent devices are opened.
Rod, pipe, and plate electrodes must have a resistance to ground of at most
25 ohms or less.
Equipment grounding refers to
connecting the normally non-current-carrying metal parts of equipment to the system grounding conductor and/or the grounding electrode conductor.
Plate electrodes
are made of copper must be at least .06 inches thick.
In a separately derived system, the equipment bonding jumper
connects the system housing to the neutral bus bar.
AC systems over 1000V that supply mobile or portable equipment
are required to be grounded.
The size of the equipment grounding conductor (EGC)
is determined by the size of the overcurrent device.
Grounding Clips are used to
secure Equipment Grounding Conductors (EGCs) to metallic outlet boxes.
A ground ring consisting of 20' of #2 bare copper must be buried no less than ____ feet below grade.
2.5
System less than 50V must be grounded if
the supply voltage to the transformer exceeds 150V.
To be effective, a grounding system must limit
the voltage on the electrical system and protect it from a voltage surge.
A short circuit is a conducting connection between
any of the conductors of an electrical system.
The path to ground from circuits, equipment and metal enclosures shall be ________________________. This is a requirement for grounding and bonding as stated by the NEC.
permanent and continuous
The minimum length allowed for driven ground rods under normal conditions is ___ feet
8
Electrical Continuity is the key to successfully
clearing of ground fault currents.
The requirement for grounding of services are located in
NEC section 250.24(A), (B), (C), and (D).
The maximum value of a short circuit current from line to ground will
vary depending on the distance from the source to the fault.
The bonding jumper for multiple disconnecting means
is located on the supply side of the service disconnect.
The minimum diameter of galvanized pipe allowed for a grounding electrode is
3/4 of 1 inch.
The Neutral in a grounded system provides a
low impedance return path for the flow of fault current to the source.
The continuity between service equipment and enclosure is maintained by
bonding.
A separately derived system for a premises wiring system is
powered from a source other than a service entrance.
If the neutral in a grounded system is not needed for voltage, the system must be run to the service
and connected to the grounding electrode conductor (Neutral) and the electrode grounding conductor (Ground).
Plate electrodes must have at least ___ feet of service area exposed to the surrounding Earth.
2 square
For separately derived systems that are required to be grounded
an equipment grounding conductor must be supplied with the primary circuit.
The equipment grounding conductor would be sized using _____________ based on the overcurrent device supplying the second structure.
NEC table 250.122
The GEC in the second structure is sized using ____________ based on the size of the feeder conductors.
NEC table 250.66
An earth ground resistance tester may be used to
make soil resistivity measurements or measure the resistance of the installed grounding electrode system to earth.
Ground Grid:
System of grounding electrodes interconnected by bare cables buried in the earth to provide lower resistance than a single grounding electrode.
Ground Mat:
System of bare conductors on or below the surface of the earth connected to a ground or ground grid to provide protection from dangerous touch voltage.
Auxiliary Electrodes:
Metallic electrode pushed or driven into the earth to provide electrical contact for the purpose of performing measurements on grounding electrodes or ground grid system.
Bonding:
Connecting to establish electrical continuity and conductivity.
Equipment Bonding Jumper:
The connection between 2 or more portions of the equipment grounding conductor.
Equipment grounding Conductor (EGC):
The conductive path(s) that provides a ground-fault current path and connects normally non-current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both.
Ground:
The earth or a conducting connection to the earth,
Ground Rod:
A metal rod or pipe used as a grounding electrode.
Grounded:
Connected to ground or to a conductive body that extends the ground connection.
Grounded Conductor:
A system or circuit conductor that is intentionally grounded.
Grounding Connections:
Connections used to establish a ground; they consist of a grounding conductor, a grounding electrode, and the earth surrounding the electrode.
Grounding Electrode:
A conduction object through which a direct connection to earth is established.
Grounding Electrode Conductor (GEC):
A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system.
Neutral Conductor:
The conductor connected to the neutral point of a system that is intended to carry current under normal conditions.
Short circuit:
An often unintended low-resistance path through which current flows around, rather than through, a component or circuit.
Supplemental Electrode:
An additional electrode (commonly a driven rod or pipe) required where the primary electrode is an underground metal water pipe in direct contact with the earth.
Grounding Clip:
A listed spring clip used to secure a bonding conductor to an outlet box.
Grounding Conductor:
A conductor used to connect equipment or the grounded circuit of a wiring system to a grounded electrode or electrodes.
Effective ground fault path:
An intentionally constructed, low-impedance, electrically conductive path designed and intended to carry current under ground fault conditions from the point of a ground fault on a wiring system to the electrical supply source.
Main Bonding jumper:
The connection between the grounded circuit conductor and the equipment grounding conductor at the service.
Separately Derived System:
A premises wiring system whose power is derived from a source of electric energy or equipment other than a service. Such systems have no direct electrical connection, including a solidly connected grounded circuit conductor, to supply conductors originating in another system.
Ground Current:
Current in the earth or grounding connections.
Ground Resistance:
The ohmic resistance between a grounding electrode and a remote or reference grounding electrode that are spaced such that their mutual resistance is essentially zero.
Resistivity:
Resistance between opposite faces of a unit cube. Expressed in ohm-centimeters or ohms per cubic centimeter.
Step Voltage:
The potential difference between two points on the earth's surface separated by the distance of one pace or almost 3'.
Touch Voltage:
The potential difference between a grounded metallic structure and a point on the earth's surface equal to the normal maximum horizontal reach- approximately 3'.