1/5
Ancillary DGs included
Name | Mastery | Learn | Test | Matching | Spaced |
---|
No study sessions yet.
Simplified Diagram
Fuel Tanks
Day
Storage
Ancillary
Day: 4hrs, One per Engine
Storage: 7days (55,000gal), One per Engine
Ancillary: 4days(>600gal), One for both
Ancillary Diesels
Loads?
When implemented?
Location?
PAMs, MCR Light, PCS recirc, Ancillary support
P-72 Procedures
Annex Building but from outside near BAST
Fuel Oil Pumps
Low FOST Level Trip?
Temperature Band?
Power?
Day Tank Control Band?
FOST 27.2” (Norm >206”)
33.6-46.4F
EC-123(233)
35.1-61.4” Day Tank
Fuel Recirculation SOVs
(V070A/B)
Opens when Transfer pump running and high Day Tank level
Closes when Pump off or low Day Tank
Fails Closed
Fuel Makeup SOVs
(V071A/B)
Opens when Transfer pump running and low Day Tank level
Closes when Pump off or high Day Tank
Fails Closed