1/42
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced |
---|
No study sessions yet.
Alternate Power
one or more generator sets or battery systems where permitted, intended to provide power during the interruption of the primary electrical service.
American Wire Gauge (AWG)
a standard system for designating wire diameter
Current Carrying Capacity (ampacity)
maximum current an insulated conductor can safely carry without exceeding its insulation and jacket temperature limitations
Disconnecting Means
device of group of devices by which conductors of a circuit can be disconnected for source of power
Emergency Power Supply (EPS)
source of electricity capable of providing power to an Emergency Power Supply System (EPSS)
Emergency Power Supply System (EPSS)
an EPS coupled to a system of conductors, disconnecting means, protective devices, transfer switches, control, supervisory, support devices and load terminals of transfer equipment needed to operate as a safe and reliable source of power
Fault Current
Hazardous, unintended and uncontrolled flow of current in an electric circuit due to a fault condition
Gauge
physical size of a wire
Ground
earth
Grounded
connected to ground
Grounding System
system of conductors that provides a low-impedance return path for leakage and fault currents
Isolated Electrical Distribution Systems (Isolated Power System)
a system compromising of an isolating transformer, a line isolation monitor and ungrounded circuit conductors
“Let-Go” Current
current level where the electricity causes muscles to contract until the current is removed
Primary (normal) Power
power usually produced by a public utility to provide normal operating power to a facility
Category 1
Due to power loss, failure of equipment or system is likely to cause major injury or death of patients, staff, visitors
Ex: Critical Care Units, Special Care Units, Operating Rooms
Category 2
Due to power loss, failure of equipment or systems is likely to cause minor injury of patients, staff or visitors
Ex: General Care Areas, Impatient bedrooms, Dialysis Units
Category 3
Due to power loss, failure of equipment or system is not likely to cause injury, but may cause discomfort to patients, staff or visitors
Ex: Examination Rooms, Treatment Rooms, Dental Rooms
Category 4
Due to power loss, failure of equipment or system is not likely to have a physical impact on patient care
Ex: Sterile Supply, Laboratories, Morgues
Meter
Measures amount of energy used by facility
Service Panels (Breaker Box)
Fuses, Circuit Breakers, Surge Protectors
Non-Essential Loads
Isolated or non-Isolated power
General lighting
General Lab equipment
Non-critical service equipment
Outlets
Standard outlets hospital grade outlets
Ground-Fault Circuit Interrupters (GFCI)
Transfer Switches
Used to transfer between normal power source and emergency power source
Emergency Electrical Distribution System
Isolated or non-isolated power
Essential Loads
Patient Care Space Categories
Category 1
Ex: Operating room, emergency room
Category 2
Ex: Critical Care lighting (Exit signs), Elevators, Automatic Doors
Branch Circuits
circuit conductors between the final overcurrent device protecting thee circuit and the outlets
Life Safety Branch
responsible for supplying power to lighting, receptacles and equipment essential for life safety that is automatically connected to the emergency power system during the interruption or primary power (essential loads)
Critical Branch
responsible for providing power for task illuminations, fixed equipment, select receptacles, select circuits serving patient care areas that is automatically connected to the emergency power system during the interruption of the primary power
Equipment Branch
circuits arranged for delayed, automatic or manual switching to the emergency power system during the interruption of primary power (non-essential loads)
Ground-Fault-Circuit-Interrupter (GFCI)
shuts off power in 1/40th of a second
de-energizes circuit when ground current exceeds 6mA
Surge Protector (type 1)
provides protection to external power surges and lightning strikes
Surge Protector (type 2)
Protects facility from internal power surges
Surge Protector (type 3)
used to protect sensitive equipment
Wire Sizing Factors
Load of circuit
length of circuit
Circuit breaker size
Gauge to Amps
AWG
14 AWG - 18 amps (15 amp breaker)
12 AWG - 24 amps (24 amp breaker)
10 AWG - 33 amps (30 amp breaker)
Kcmil
250 kcmil - 245 amps
600 kcmil - 413 amps
1000 kcmil - 542 amps
kcmil ranges
starts at 250 kcmil and increases to 2000 kcmil
AWG Ranges
#40 Smallest
#4/0 Largest
*Smaller the gauge number, larger the wire, larger current allowed
*Larger the gauge number, smaller the wire, smaller current allowed
Grounded (neutral) Conducotr
white wire
Normal current carrying wire
Needed for equipment to operate
Grounding Conductor
Green Wire
Not used as the normal current carrying wire
NFPA 70
Reference used to determine wire sizing for different applications in specific situations
Line Isolation Monitor (LIM)
Continuously monitors the maximum current that could flow between an isolated power conductor and isolated ground
Green Light Signal
System is adequately isolated from ground
Red Signal Light (Audible Alarm)
Current reaches 5mA under normal conditions
Ungrounded Circuit Conductors
Conductors within an isolated power supply that are not connected to the primary grounding circuit
Testing of EPSS
12 times a year (once a month)
Minimum of 30 minutes
Will be tested under a load