Materials typically used for cable jackets include neoprene, lead, and _____.

PVC

2
New cards

Which of the following termination classes is the only one that provides a seal against external elements?

Class 1

3
New cards

Insulation must protect from flashover damage and _____.

tracking damage

4
New cards

Which of the following is the recommended abrasive cloth used to clean cable during a splice?

120-grit abrasive cloth

5
New cards

Acceptance testing calls for a maximum value of what percentage of the factory test voltage?

80%

6
New cards

A quick test that can be made to determine if an installation is good is known as a(n) _____.

go/no-go test

7
New cards

A knee in a leakage current-versus-voltage plot indicates a _____.

breakdown current

8
New cards

Proof tests are made at what percentage of the original factory voltage?

60%

9
New cards

A suitable connector for medium-voltage cable splices is a compression or _____.

crimp type

10
New cards

When conducted properly, which of the following will indicate faults such as cracks, discontinuity, thin spots, and faulty terminations?

Hi-pot test

11
New cards

To finish a splice and ensure complete protection, it should be covered with how many layers of vinyl electrical tape?

Four

12
New cards

Two methods used to provide stress control for medium-voltage cable terminations are geometric and _____.

capacitive

13
New cards

Insulation shielding performs all of the following functions, except

protecting the insulation from the elements

14
New cards

Which of the following materials is not likely to be used for a cable jacket?

Nylon

15
New cards

The outer shielding in a medium-voltage cable is best described as

a semi-conductive layer under a metallic layer

16
New cards

Which of the following best describes a medium-voltage termination?

An insulator

17
New cards

Compressed stranding is compressed to what percentage of the concentric conductor diameters?

97%

18
New cards

When testing insulation resistance, the ratio of the insulation resistance at the end of 10 minutes to the insulation resistance at the end of one minute is called the

polarization index