25 deg C
@ initial; td=30, tw=24
@mixed; td 22 tw 17
what is dry bulb temp
19.3 deg C
@ initial; td=30, tw=24
@mixed; td 22 tw 17
what is wet bulb temp
56 kj/kg
@ initial; td=30, tw=24
@mixed; td 22 tw 17
what is enthalpy
total heat load
overall heat to be removed from space
sensible heat load
amount of heat required to maintain the temperature difference between the room air and supplied air
latent heat load
in heat load calculation, it is required to to remove the excess moisture in the room
sensible heat ratio/ sensible heat factor
ratio of sensible and total heat
both a and b ( no recirculation and recirculation)
methods to analyze air conditioning space
70Kw
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
what is required sensible heat load
30kw
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
what is required latent heat load
10 kg/s
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
how much air is circulating
8.3 m3/s
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
capacity of fan in terms of volume
13deg C
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
what is apparatus dewpoint
QRL=353
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
what is ref effort
66gv/s
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
what is condensate drain
12 gv/s
@auditorium pt 4
26 C 50% RH. HL =100KW.
sensible heat ratio 70%
@fan blow pt 3 = 19C
@pt1 outdoor air 31C & 24C
what is moisture pickup
cooling tower
heat rejecting device, remove waste heat
recycle water by heating
not purpose of cooling tower
open cooling tower
type of cooling tower rely on direct air and water contact
induced draft
type of cooling tower placing fan from top
evaporative cooling
process of cooling tower
13889 kg/s
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
mass water enter in the condenser
111.1111kg/s
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
make up water
sh2= 10.539 gv/kg
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
moisture air carry in the cooling tower
6622 kga/s
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
air allowed to flow in tower
99.972 kj/kg
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
what is enthalpy of air carry out in cooling tower
34.65 C
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
what temperature is cooling water goes out of tower
13778 kg/s
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
what is exit mass upon leaving cooling tower
25%
tw in 40. td in 26. RH in 50%
t out 30. RH 100%
efficiency of cooling tower
internal combustion engine
since cooling tower are actually use. which if the following does not use cooling tower