1/26
Looks like no tags are added yet.
How to use voltage drop formula?
Vd = (mV/A/m × Ib × L) ÷ 1000
mV/A/m = millivolts per amp per metre
I = current
L = length
÷ 1000 = millivolts to volts
(If asked about ring circuit, length is halved as current splits and flows both directions)
Lighting : Not to exceed 3% of a nominal voltage (6.9)
Power : Not to exceed 5% of the nominal voltage (11.5)
Cable Selection & De-rating Formulas
Current Carrying Capacity – Correction Factors
Iz = It × Ca × Ci × Cg
Where:
Iz = usable/current carrying capacity after de-rating
It = tabulated current carrying capacity (from tables)
Ca = ambient temperature factor
Cg = grouping factor
Ci = thermal insulation factor
To find required tabulated cable capacity - when selecting cable
It = Iz ÷ (Ca × Ci × Cg)
Use this when choosing a cable size.
Definitions
It = tabulated current carrying capacity
Determined from:
Cable size (mm²)
Installation method
Cable type
C = correction factor
Ca = Ambient temperature factor
Cg = Grouping factor
Ci = Thermal insulation factor
Many more cable factors but all tabulated table factors can be found on BS 7671: Appendix 4: Tables 4C1 - 4C5
How can I use ohms law formula?
To find ohms law, its best to use the ohms law triangle
V = I x R
R = V / I
I = V / R

How can I use power formula?
To find the power, use the power triangle
P = I V
I = P / V
V = P / I

How can I combine ohms law and power triangle?
Combine V = IR with P = VI to unlock I²R and V²/R
Replace V:
P = V × I
P = (I × R) × I
👉 P = I²R
Replace I:
I = V ÷ R
P = V × (V ÷ R)
👉 P = V² ÷ R
Earth Fault Loop Impedance (Zs) calculation
Zs = U₀ / Iₐ
U₀ = 230 V (UK nominal voltage to earth)
Iₐ = MCB rated current (In) × type of MCB
Iₐ = In × 5 (Type B)
Iₐ = In × 10 (Type C)
Iₐ = In × 20 (Type D)
If not using the formula:
Take the maximum Zs from tabulated values (BS 7671), then multiply by 0.8 temperature correction factor.
What is the relationship between power and energy?
Energy is the total amount of electrical work done or energy transferred and is measured in joules (J).
E = pt
Power is the rate at which electrical energy is transferred or work is done per unit time and is measured in watts (W).
P = e/t
The key difference between energy and power is time.
T = e/p
Ohm’s Law applies to DC and purely resistive AC circuits: V = I × R.
In AC circuits, the power triangle relates real power, apparent power, and reactive power
What is Charge and what is its formula?
Q = I × t
I = Q / t
t = Q / I
Where:
Q = charge (measured in coulombs, C)
I = current (amps, A)
t = time (seconds, s)
Always in seconds. If current is flowing, charge is building up over time.
1 amp = 1 coulomb per second
How to find the CSA of a cable and how to find the volume of a cylinder?
For CSA:
Divide the diameter by 2 to get the radius, square the radius, then multiply by π (3.142) to get the cross-sectional area. (mm2
For diameter:
Divide the CSA by π (3.142), square root the value, then multiple by 2. (mm)
For volume of a cylinder:
Just multiply the CSA by the height of the cylinder. (mm3)
What is efficiency and what is its formula?
Efficiency in electrical terms is about how much of the input energy or power actually becomes useful output.
Efficiency = (Useful Output / Total Input) × 100
Input Power= Useful Output Power / Efficiency (as a decimal)
Useful Output Power= Input x Efficiency (as a decimal)
What is a RMS value instantaneous value and how do you calculate this?
AC Values
Works for both: Voltage & Current
×1.414 ×2
RMS ⇄ Peak ⇄ Peak-to-Peak
÷1.414 ÷2
Frequency (f) = 1 ÷ Period (T)
Period (T) = 1 ÷ Frequency (f)
What is the basic Volt drop formula?
Vd = I x R
What is Coulomb & Joules?
Coulomb (C)
Coulomb = electric charge
Joule (J)
Joule = energy
key thing to remember:
1 amp = 1 coulomb per second
I = t Q
Charge = current × time
What is the three-phase power formula, and when is it used?
For three-phase AC:
Purely resistive: P = √3 × VL × IL
Non-purely resistive: P = √3 × VL × IL × PF
VL = line voltage (400 V) IL = line current PF = power factor
What is Zs?
Zs= Ze + (R1 +R2)
Zs = entire earth fault loop impedance of a circuit (measured at the furthest point).
Ze = external earth fault loop impedance (Measured at the origin of the source)
R1 + R2 = resistance of live conductor & continuity of CPC
What are the motor speed and frequency formulas
Frequency (f) = Number of revolutions (n) × Number of pole pairs (p)
Period (T) = Time for one revolution (t) ÷ Number of pole pairs (p)
How do you calculate the total resistance of resistors in parallel?
1/Rpg = 1/R1 + 1/R2 + 1/R3
Example: R1 = 5Ω, R2 = 10Ω, R3 = 15Ω
Find the common denominator (30), then convert and add the fractions:
1/Rpg = 6/30 + 3/30 + 2/30 = 11/30
Flip the final fraction to find Rpg:
Rpg = 30/11 = 2.73Ω
If there are only two resistors, use:
Rp=R1×R2R1+R2Rp=R1+R2R1×R2
How do you calculate flux density when flux is in μWb and area is in cm²?
Formula: B = Flux ÷ Area
Convert units:
μWb to Wb: × 10⁻⁶
cm² to m²: × 10⁻⁴
Example: Flux = 90 μWb, Area = 4 cm²
B = (90 × 10⁻⁶) ÷ (4 × 10⁻⁴)
B = 0.225 T
What are the design current formulas for purely resistive single-phase and three-phase circuits?
Single-phase: Ib = P ÷ V
Three-phase: Ib = P ÷ (√3 × VL)
Purely resistive loads have a power factor of 1, meaning voltage and current are in phase.
Examples: heaters, kettles and immersion heaters.
Single-phase voltage = 230 V
Three-phase line voltage = 400 V
What are the design current formulas for non-purely resistive single-phase and three-phase circuits?
Single-phase: Ib = P ÷ (V × PF)
Three-phase: Ib = P ÷ (√3 × VL × PF)
Power factor (PF) accounts for the phase difference between voltage and current.
Examples: motors and transformers
What is diversity, how is it calculated, and why is it used?
Formula: Diversified demand = Original demand × Diversity factor
Diversity accounts for the fact that not all electrical equipment and circuits operate at full load simultaneously.
For an entire installation:
Calculate each circuit's design current first.
Apply the relevant diversity percentages from Table A2, Appendix A of the IET On-Site Guide.
Add the diversified demands to find the total assumed installation demand.
This helps determine the supply cable size and ratings of the main protective devices and switchgear.
Important: Never apply installation diversity percentages to individual circuits when calculating their design current.
Note: There is no single universal diversity factor; the applicable percentage depends on the type of circuit and installation.
What is the formula for calculating cable resistance?
R = ρ × L ÷ A
R = Resistance (Ω)
ρ = Resistivity of conductor
L = Length of cable (m)
A = Cross-sectional area (mm²)
Longer cable = Higher resistance.
What is the formula for calculating power dissipated as heat in a cable?
P = I² × R
P = Power (W)
I = Current (A)
R = Resistance (Ω)
Higher current or resistance = More heat.
How do you calculate R1 + R2 using Tables I1, I2 and I3, and why?
R1 + R2 = (I1 × I2 × I3 × Cable length) ÷ 1000
I1 = Basic conductor resistance.
I2 = Temperature correction.
I3 = Cable insulation/CPC correction.
Why? To calculate the actual resistance of the line and CPC conductors in ohms, accounting for cable length and installation conditions.
Front:
How do you calculate earth fault current, and why?
If = Uo ÷ Zs
If = Earth fault current (A).
Uo = Nominal voltage to earth (230 V).
Zs = Actual earth fault loop impedance (Ω).
Why? To determine how much fault current will flow, so you can check whether the protective device will disconnect the supply within the required time.
What is the adiabatic equation, what is it used for, and why must the CPC be checked?
S = √(I² × t) ÷ k
Used to calculate the minimum permissible cross-sectional area (CSA) of the CPC.
S = Minimum CPC size (mm²).
I = Earth fault current (A).
t = Disconnection time (seconds).
k = Conductor and insulation constant.
Why? To ensure the CPC can withstand the heat produced by an earth fault until the protective device disconnects, without suffering damage.
What is fusing factor (FF), and when must the formula be rearranged?
Fusing factor is the ratio between the current that guarantees operation (I₂) and the nominal rating (In).
FF = I₂ ÷ In
Rearrange depending on what you need to calculate:
To find I₂: I₂ = FF × In
To find In: In = I₂ ÷ FF