25mm
The airgap for drainage shall be not less than ____ between the plumbing fixture, appliance or appurtenance outlet and the rim of the floor sink or receptor.
1.5m to 4.6m
length indirect waste pipes that shall be directly trapped, but not to be vented
4.6 m, 13 mm
Indirect waste pipes less than ____ in length need not be larger in diameter than the drain outlet or tailpiece of the fixture, appliance or equipment served, but in no case less than ____ diameter
0.8m, 0.45m
No standpipe receptor for any clotheswasher shall extend more than ___ meter nor less than ___ above its trap.
0.15m, 0.45m
No trap for any clotheswasher standpipe receptor shall be installed below the floor, but shall be roughed no less than ___ and not more than ___ above the floor.
0.6 meter
Such tailpiece or connections shall be as short as possible and in no case shall exceed ____ for (CW & VS)
4.6 m
branches more than ____ in length shall be separately vented
19mm
The top of the deep seal trap shall have a ___ diameter opening located at the highest point of the trap to serve as a siphon breaker.
102 mm, 13 mm
Concrete sumps, condensers or intercepting tanks shall have walls and bottom not less than ____ thickness, and the inside shall be cement plastered not less than ____ in thickness.
No. 12 U.S. Standard gauge (2.77 mm)
metal condenser shall be not less than _____ thick
152mm
clean water used only for cooling can be drained into the plumbing system through the inlet side of a fixture trap, but only if there's no suitable fixture available to receive it. Such trap connection shall be by means of a pipe connected to the inlet side of an approved fixture trap, the upper end terminating in a funnel shaped receptacle set adjacent, and not less than ___ above the overflow rim.
152 mm
All condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within ____ of the bottom of the tank.
152mm
clearance above overflow rim of the fixture drain of cooling medium
152mm
connection from the island vent to other vents is not less than____ above the flood level rim of the fixture served
51mm
Wet-vented pipe section shall not be less than _____ diameter
51mm
cleanouts may not be required on any wet-vented branch serving a single trap when the fixture tailpiece or connection is not less than ____ in diameter
32mm
minimum pipe size for 1 inlet serving not more than 2.8 m3 of refrigeration space;
3.2 mm
Intended to receive the discharge of any fixture where acid or corrosive chemical is placed and each vent pipe connected thereto, shall be constructed of chemical-resistant lead pipe not less than _____ wall thickness
1/2
Outlets shall be taken off from the side in a manner to allow a water line to be maintained that permanently occupies not less than ____ the capacity of the condenser or sump
½ of drain
minimum area of vent in CW & VS
1 pipe size larger or 51mm
minimum wet-vented section larger than the required waste pipes size
2 pipe sizes larger
each waste pipe and each trap in CW &VS shall be at least _____ than any fixture tailpiece or connection served
1, 45 degree
the return bend used under the drainboard for island fixtures shall be a __ piece fitting or assembly of a ___ elbow
60°C
maximum temperature to discharge under pressure directly into drainage system
2%
slope of vent back toward the drain for island fixtures
1 and 2
wet venting is limited to vertical drainage piping receiving the discharge from the trap arm of ___ and ___ FU
4 FU
limit for fixtures that also serves as a vent
Indirect waste receptor
Shall not be installed in any toilet room, closet, cupboard or storeroom nor in any other portion of a building not for general use by the occupants.
indirect waste pipes
pipes from boilers shall discharge through
Indirect wastes
Drinking fountains may be installed with -
Indirect waste
Where a pump is used to discharge waste pool water to the drainage system, the pump discharge shall be installed as an -
Airgap
Appliances, devices or apparatus such as stills, sterilizers and similar equipment requiring water and waste and used for sterile materials shall be drained through an -
Airgap or Airbreak
Air-conditioning condensate waste pipes shall connect indirectly to the drainage system through an -
dishwasher airgap fitting
necessary for the connection of dishwashing machine to a food waste disposer
Chemical or Industrial liquid wastes
Likely to damage or increase maintenance costs on the excreta sewer system.
Chemical wastes
Shall not be discharged into the ground, local sewer or other disposal means without approval of the local Administrative Authority.
Protect the shell
Wearing plates or baffles shall be installed in the tank to -
Bituminous coating
All such metal condensers shall be protected from external corrosion by an approved -
wet-vented
the vertical piping between any 2 consecutive inlet levels shall be considered a _____ section
Uppermost fixture
the vent connection shall be downstream of the -
Beehive strainer
Every indirect waste interceptor receiving discharge containing particles that clogs the receptor drain shall have a readily removable -
“Sacrarium”
_____ also called as waste of holy water and washwater at church altar services must not be discharged into the sanitary drainage system but disposed off directly into the ground.
sumps
no piping or equipment carrying or producing wastes or other discharge under pressure shall be directly connected to any part of the drainage system, except for _____
cast iron, galvanized iron, plastic
material for undiluted condensate waste discharging from a fuel burning condensing appliance
same
all wet-vented fixtures shall be on the ____ floor level
Combination Waste and Vent Systems
Meaning of CW &VS