Open in a WYE, NO Neutral
IL = (86.6%) of previous current before the break
PT = (50%) of previous power before the break
Open in Line WYE with NEUTRAL
IN = Same as any of the two lines
PT = (66.7%) of previous power before the break
Delta Open Line ( Fuse )
IL = (86.6%) of previous
PT = (50%) of previous
Delta open Load ( Resistors)
IL = (57.7%) of previous
PT = (66.7%) of previous
Delta Connection
Before a Break IL = IP*root 3
After a Break IL Becomes IP for two of the phases because there is no other path for current or power in an open load.