AN APPROVED CENTRAL STATION COMPANY IS ONE THAT HAS BEEN ISSUED A VALID CERTIFICATE FROM ____________.

FDNY

2
New cards

A _________ IS THE OPEN SPACE THAT CARRIES AIR BETWEEN THE CEILINGS AND FLOOR ABOVE.

PLENUM

3
New cards

AN _________ ALARM IS ONE WHICH FUNCTIONED AS DESIGNED, BUT WHICH DEPARTMENT RESPONSE IS UNNECCESSARY.

UNNECESSARY

4
New cards

AN _________ ALARM IS THE RESULT OF IMPROPER INSTALLATION, OR MAINTENANCE.

UNWARRANTED

5
New cards

THE NEW FIRE CODE WAS ADOPTED IN __________ AND VASTLY CHANGED THE REQUIREMENTS FOR SUPERVISION OF ALL FIRE ALARM SYSTEMS.

JULY 2008

6
New cards

DUTIES THAT CAN BE PERFORMED BY AN S-95 COF HOLDER INCLUDE ___________ ONLY.

VISUAL INSPECTIONS ONLY

7
New cards

THE PRIMARY PURPOSE OF A ____________ IS TO WARN OCCUPANTS AND TO TRANSMIT SIGNALS INDICATION FIRE TO THE FDNY.

FIRE ALARM SYSTEM

8
New cards

THE PRIMARY PURPOSE OF A ______________ IS TO PROCESS SIGNALS RECEIVED FROM INITIATING DEVICES AND TO ACTIVATE APPROPRIATE SIGNALS.

FIRE ALARM CONTROL PANEL

9
New cards

A ___________ SIGNAL IS INITIATED WHEN A DEVICE INDICATES THE PRESENCE OF FIRE.

FIRE ALARM

10
New cards

A _________ SIGNAL INDICATES THAT A SYSTEM OR DEVICE BEING MONITORED IS IN AN ABNORMAL STATE.

SUPERVISORY

11
New cards

A __________ SIGNAL INDICATES THAT THE ALARM SYSTEM, TRANSMITTER, OR COMMUNICATIONS PATH IS WHOLLY OR PARTIALLY OUT OF SERVICE.

TROUBLE

12
New cards

ROUTINE HANDLING OF TROUBLE SIGNALS SHOULD TAKE A MAXIMUM OF ___________ MINUTES FROM RECEIPT OF TROUBLE SIGNAL BY CENTRAL STATION UNTIL INITIAL INVESTIGATION BY TELEPHONE.

FOUR

13
New cards

THE FDNY IS NOT DISPATCHED TO RESPOND TO _________ OR ________ SIGNALS.

SUPERVISORY, TROUBLE

14
New cards

DO NOT SILENCE THE BUILDING ___________ AND ________ DEVICE UNTIL THE FIRE ALARM CONDITION IS VERIFIED BY FDNY PERSONNEL.

AUDIBLE, VISUAL

15
New cards

SMOKE DETECTORS MUST BE CLEANED AT LEAST _____________ BY AN S-78, S-97, T-97, OR S-98 COF HOLDER.

ONCE EVERY SIX MONTHS.

16
New cards

ANY ABNORMAL CONDITIONS MUST BE INVESTIGATED AND NOTED IN THE ___________.

LOGBOOK

17
New cards

THE FIRE ALARM PRIMARY POWER SOURCE SHALL BE GENERATED ELECTRIC POWER NOT EXCEEDING ____________ VOLTS.

277/480

18
New cards

________ SHALL NOT BE A SUBSTITUTE FOR CONNECTION TO A SECONDARY POWER SOURCE.

BATTERIES

19
New cards

THE NFPA DEFINES ACCESSIBILITY AS __________________.

"ADMITTING CLOSE APPROACH: NOT GUARDED BY LOCKED DOORS, ELEVATION, AND OTHER EFFECTIVE MEANS."

20
New cards

WHEN SMOKE DETECTORS REPORT THE NEED FOR MAINTENANCE TO THE FACP, IT MUST BE CLEANED WITHIN __________.

1 WEEK

21
New cards

IONIZATION DETECTORS USE AN _______________ AND A SOURCE OF IONIZING

IONIZATION CHAMBER

22
New cards

IONIZATION SMOKE DETECTORS MONITOR ___________, OR ELECTRICALLY CHARGED PARTICLES IN THE AIR.

IONS

23
New cards

_____________ DETECTORS ARE BETTER AT SENSING SMOKY FIRES, SUCH AS THOSE CAUSED BY A SMOLDERING MATTRESS.

PHOTOELECTRIC

24
New cards

PROJECTED BEAM-TYPE DETECTORS SHALL BE KEPT CLEAR OF __________ OBSTACLES.

OPAQUE

25
New cards

PROJECTED BEAMS SHALL BE DESIGNED SO THAT SMALL ANGULAR MOVEMENTS DO NOT CAUSE ______________.

NUISANCE ALARMS

26
New cards

THE TWO TYPES OF PHOTOELECTRIC SMOKE DETECTORS: LIGHT-______________ AND LIGHT- ____________ .

OBSCURATION, SCATTERING

27
New cards

____________ DETECTORS CONTAIN MULTIPLE SENSORS THAT RESPOND SEPERATELY BUT PROVIDE ONLY ONE ALARM SIGNAL.

MULTI-CRITERIA

28
New cards

____________ DETECTORS CONTAIN MULTIPLE SENSORS AND ARE CAPABLE OF GENERATING MULTIPLE ALARMS.

MULTI-SENSOR

29
New cards

____________ DETECTORS EMPLOY MORE THAN ONE OPERATING PRINCIPLE AND OPERATE INDEPENDENT OF EACH OTHER.

COMBINATION

30
New cards

____________ DETECTORS ARE USED TO PROTECT LARGE AREAS. IT IS A LIGHT BEAM BROKEN BY COMBUSTIBLE PARTICLES.

BEAM

31
New cards

___________ DETECTORS SHUT DOWN A BUILDINGS HVAC SYSTEM AND RE-DIRECT AIRFLOW.

DUST SMOKE

32
New cards

FIRE ALARM DEVICES SHALL BE PROTECTED, ESPECIALLY DURING ___________.

INSTALLATION

33
New cards

FOR AIR SAMPLING TYPE DETECTORS, THE MAXIMUM AIR SAMPLING TRANSPORT TIME FROM THE FARTHES POINT SHALL NOT EXCEED ____________.

120 SECONDS

34
New cards

AIR-SAMPLING DETECTORS SHALL GIVE A ____________ SIGNAL IF THE AIRFLOW IS OUTSIDE THE MANUFACURERS SPECIFIED RANGE.

TROUBLE

35
New cards

MAXIMUM ALLOWABLE TIME FOR FIRE ALARM OUTPUT FUNCTIONS TO OPERATE ONCE A SMOKE DETECTOR HAS BEEN ACTIVATED IS __________ SECONDS.

10

36
New cards

__________ HEAT DETECTORS DO NOT HAVE TO BE REPLACED AFTER IT HAS ACTIVATED THE FIRE ALARM.

RATE OF RISE

37
New cards

________ HEAT DETECTORS ACTIVATE THE ALARM WHEN THE DETECTOR COMPONENTS MELT AT A PRESET TEMPERATURE.

FIXED-TEMPERATURE

38
New cards

__________ HEAT DETECTORS ARE THE MOST COMMONLY USED.

FIXED-TEMPERATURE

39
New cards

___________ DETECTORS ARE REQUIRED IN ANY BUILDING THAT HAS FOSSIL FUEL BURNING EQUIPMENT.

CARBON MONOXIDE

40
New cards

THE _________ SHALL ONLY BE RESET AT THE DIRECTION OF A FIRE DEPARTMENT REPRESENTATIVE.

FIRE ALARM CONTROL PANEL

41
New cards

SINGLE ACTION STATIONS ARE USUALLY FOUND __________.

INDOORS

42
New cards

ONCE ACTIVATED, THE FIRE ALARM SYSTEM CANNOT BE RE-SET AT THE _____________.

FIRE ALARM MANUAL PULL STATION

43
New cards

A MASTER PLUMBER WITH AN S-12 COF IS ALLOWED TO PERFORM MAINTENANCE ON SPRINKLER SYSTEMS IN RESIDENTIAL OCCUPANCIES WITH LESS THAN ____________ SPRINKLERS.

30

44
New cards

WHEN A ____________ CONDITION IS INDICATED, THE COF HOLDER SHOULD CHECK THE SYSTEM IN ORDER TO IDENTIFY THE PART OF THE SYSTEM THAT CAUSED THE SIGNAL.

SUPERVISORY

45
New cards

ALL SUBSYSTEMS ARE SUBJECT TO FDNY INSPECTION AND TEST FOR ISSUANCE OF _______________.

LETTER OF APPROVAL

46
New cards

IN LARGE BUILDINGS, THE FIRE ANNUNCIATOR MAY BE ASSOCIATED WITH ____________ CONTROL AND _____________ SYSTEMS.

SMOKE PURGE, COMMUNICATIONS

47
New cards

THE _______________ ALARM METHOD ACTIVATES ALL AUDIO/VISUAL DEVICES THROUGHOUT THE BUILDING WHEN A FIRE IS DETECTED.

GENERAL

48
New cards

THE ______________ ALARM METHOD ACTIVATES AUDIO/VISUAL DEVICES ONLY ON THE FLOOR OF ALARM AS WELL THE FLOORS IMMEDIATELY ABOVE AND BELOW.

SELECTIVE

49
New cards

TWO-WAY COMMUNICATION SYSTEMS MUST BE TESTED AT LEAST ONCE EVERY ______________ MONTHS.

6

50
New cards

UNMONITORED FIRE COMMAND CENTERS MUST BE INPSECTECTED AT LEAST _____________.

WEEKLY

51
New cards

MONITORED FIRE COMMAND CENTERS MUST BE CONDUCTED AT LEAST ___________.

ANNUALLY

52
New cards

_________ VISUAL INSPECTION IS HIGHLY RECOMMENDED BY THE FDNY.

DAILY

53
New cards

THE __________ SHOULD BE MAINTAINED AT THE BUILDINGS FACP.

ALARM LOG BOOK

54
New cards

THE LOG BOOK SHOULD BE A ________ BOOK.

BOUND

55
New cards

THE FOUR SECTIONS IN THE ALARM BOOK SHOULD CONTAIN THE FOLLOWING:

DAILY ENTRIES, SYSTEM OFF-LINE ENTRIES, ACTIVATED ALARM ENTRIES, AND NOTIFICATION ENTRIES.

56
New cards

SMOKE DETECTORS MUST BE CLEANED AT LEAST ONCE EVERY ______________.

6 MONTHS.