Maximum leak rate for comfort cooling
10% of the charge per year.
Maximum leak rate for commercial refrigeration
20% of the charge per year.
Maximum leak rate for industrial process refrigeration
30% of the charge per year.
Threshold leak rate for appliances with 50 or more pounds of refrigerant
Owner has 30 days to repair or 18 months to retrofit or retire if exceeding.
Initial verification test
Must be conducted after the repair to ensure leak rates are below the threshold.
Recovery unit cut-out control setting for low-pressure chiller
Typically set for 10 psig.
Average refrigerant remaining in a 350-ton R-123 chiller at 0 psig
Approximately 100 pounds of refrigerant in the vapor state.
Process for evacuation/dehydration involving moisture
Increase pressure with nitrogen to prevent trapped water from freezing.
Record-keeping requirement for leak inspections
Records must be kept for three (3) years.
System mothballing definition
Does not require removing the appliance and storing it.