P-3 ON
(RTCB open)
Permits manual block of all safeguards signals and reset of latched safeguards signals (signal persistent for > 60 sec)
Input to P-4
P-3 OFF
(RTCB closed)
Prevents manual reset of latched Safeguards signals, and removes block of unlatched Safeguards signals
P-4 ON
(Reactor Trip signal or P-3)
Causes Turbine Trip
w/ Tavg Low (550 F), causes Feedwater Isolation A
w/ Tavg Low 2 (525 F), causes Feedwater Isolation B
w/ SG NR Level High (66.8%), causes Feedwater Isolation C and CVS Makeup Isolation
Causes Boron Dilution Protection
Blocks Steam Dump load rejection control
Transfer Steam Dump to Press Control Mode
Actuates RTVO to SFW Control Valves and opens FWS-V097
P-4 OFF
(No Reactor Trip signal and No P-3)
Enables Steam Dump load rejection control
P-6 ON
(IR ≥ 1E-5%)
Manual block of SR Flux High (1 E5 CPS SR) → Reactor Trip
P-6 OFF
(IR < 1E-5%)
Auto unblock SR Flux High (1 E5 CPS SR) → Reactor Trip
Auto unblock SR Flux doubling (2.2x in 10 sec) → Boron Dilution Protection
Auto unblock SR Flux doubling (2.2x in 10 sec)→ CVS Makeup Isolation
P-8 ON
(Tavg ≥ 551 F)
Manual block SR Flux doubling (2.2x in 10 sec) → Boron Dilution Protection
Manual block SR Flux doubling (2.2x in 10 sec) → CVS Makeup Isolation
P-8 OFF
(Tavg < 551 F)
Auto unblock SR Flux doubling (2.2x in 10 sec) → Boron Dilution Protection
Auto unblock SR Flux doubling (2.2x in 10 sec) → CVS Makeup Isolation
P-9 ON
(Tavg ≥ 200 F)
Auto unblock SG NR Level High 3 (76%) → Turbine Trip
Auto unblock SG NR Level High 3 (76%) → Feedwater Isolation ABC
Auto unblock SG NR Level High 3 (76%) → CVS Makeup Isolation
Auto unblock SG NR Level High (66.8%) w/ P-4 → CVS Makeup Isolation
Auto unblock SG NR Level High (66.8%) w/ P-4 → Feedwater Isolation C
Auto unblock SG NR Level Low 2 (21%) → Reactor Trip
Auto unblock SG NR Level Low 2 (21%) → SG Blowdown Isolation
Auto unblock SG NR Level Low 2 (21%) w/ SFW Flow Low 2 (200 gpm) → PRHR Actuation
Auto unblock SG WR Level Low 2 (35%) → PRHR Actuation
Auto unblock SG WR Level Low 2 (35%) w/ HL Temp High (636 F) → CMT Actuation
Auto unblock IRWST WR Level Low (96%) → Refueling Cavity Isolation
P-9 OFF
(Tavg < 200 F)
Manual block SG NR Level High 3 (76%) → Turbine Trip
Manual block SG NR Level High 3 (76%) → Feedwater Isolation ABC
Manual block SG NR Level High 3 (76%) → CVS Makeup Isolation
Manual block SG NR Level High (66.8%) w/ P-4 → Feedwater Isolation C
Manual block SG NR Level High (66.8%) w/ P-4 → CVS Makeup Isolation
Manual block SG NR Level Low 2 (21%) → Reactor Trip
Manual block SG NR Level Low 2 (21%) → SG Blowdown Isolation
Manual block SG NR Level Low 2 (21%) w/ SFW Flow Low 2 (200 gpm) → PRHR Actuation
Manual block SG WR Level Low 2 (35%) → PRHR Actuation
Manual block SG WR Level Low 2 (35%) w/ HL Temp High (636 F) → CMT Actuation
Manual block IRWST WR Level Low (96%) → Refueling Cavity Isolation
P-10 ON
(PR ≥ 10%)
Auto block SR Flux High (1 E5 CPS SR) → Reactor Trip
Manual block IR Flux High (25% IR) → Reactor Trip
Manual block PR Flux High (low setpoint) (25% PR) → Reactor Trip
Auto unblock PZR Level High 3 (66%) → Reactor Trip
Auto unblock PZR Press Low 2 (1955 psig) → Reactor Trip
Auto unblock Reactor Coolant Flow Rate (90%) → Reactor Trip
Auto unblock RCP Speed Low 2 (91%) → Reactor Trip
P-10 OFF
(PR < 10%)
Manual reset SR Flux High (1 E5 CPS SR) → Reactor Trip
Auto unblock IR Flux High (25% IR) → Reactor Trip
Auto unblock PR Flux High (low setpoint) (25% PR) → Reactor Trip
Auto block PZR Level High 3 (66%) → Reactor Trip
Auto block PZR Press Low 2 (1955 psig) → Reactor Trip
Auto block Reactor Coolant Flow Rate (90%) → Reactor Trip
Auto block RCP Speed Low 2 (91%) → Reactor Trip
P-11 ON
(PZR NR Press < 1970 psig)
Manual block SG NR Level High 3 (76%) → Reactor Trip
Manual block PZR Press Low 3 (1855 psig) → Safeguards Actuation
Manual block Steamline Press Low 2 (560.3 psig) → Safeguards Actuation
Manual block Low 3 (1855 psig) → Safeguards Actuation
P-11 OFF
(PZR NR Press ≥ 1970 psig)
Placeholder
P-12 ON
(PZR Level < 16%)
Manual block PZR Level Low (20%) → Aux Spray and Purification Isolation
Manual block PZR Level Low 2 (10%) → CMT Actuation
Auto unblock HL Level Low 2 (58.1%) → CVS Letdown Isolation
Manual unblock HL Level Low 4 (9.7%) → ADS 4 Actuation
P-12 OFF
(PZR Level ≥ 16%)
Auto unblock PZR Level Low (20%) → Aux Spray and Purification Isolation
Auto unblock PZR Level Low 2 (10%) → CMT Actuation
Manual block HL Level Low 2 (58.1%) → CVS Letdown Isolation
Auto block HL Level Low 4 (9.7%) → ADS 4 Actuation
P-17 ON
(PR Rate more negative than or equal to -15% RTP)
Auto block
Auto and Manual rod withdrawal for both M and AO banks
Auto AO rod insertion
P-17 OFF
(PR Rate less negative than -15% RTP)
Manual reset of P-17
P-19 ON
(RCS WR Press < 700 psig)
Manual block PZR Level High 3 (66%) → PRHR Actuation
Manual block PZR Level High 3 (66%) → PZR Heater Trip
Manual block PZR Level High 2 (55%) → CVS Makeup Isolation
P-19 OFF
(RCS WR Press ≥ 700 psig)
Auto unblock PZR Level High 3 (66%) → PRHR Actuation
Auto unblock PZR Level High 3 (66%) → PZR Heater Trip
Auto unblock PZR Level High 2 (55%) → CVS Makeup Isolation