IAD51 Qualcards - Full Electrical

0.0(0)
studied byStudied by 5 people
GameKnowt Live
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
Card Sorting

1/159

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

160 Terms

1
New cards

Voltage at Utility

230 kV

2
New cards

Voltage at Substation

34.5 kV

3
New cards

Voltage at Step-down transformer

480 V

4
New cards

What does a VISTA do?

VISTA is a manual transfer switch that is fed from two separate substations and can be switched between the two.

5
New cards

Generator Function

Provide backup power if the utility source is unavailable

6
New cards

480/277 Volts

high voltage range, 480 V is between 2 phases, and 277 V is between any phase and neutral.

7
New cards

Normal Status of Generator Breaker

Open

8
New cards

Normal Status of Utility Breaker

Closed

9
New cards

Major components in Electrical Flow path

Utility, Substation, VISTA, Transformer, Switchgear, UPS, PDU, RPP, racks.

10
New cards

IAD51 Electrical Redundancy

Distributive Redundancy - upon loss of 1 line, the other 4 UPS should pick up the remaining.

11
New cards

At what level does load shedding occur?

At the rack level.

12
New cards

Type of Batteries used in our UPS Electrical Rooms?

Lithium-ion Batteries

13
New cards

How many batteries per string in UPS Electrical Rooms

17 Batteries per String

14
New cards

How many strings of batteries?

5 Strings of batteries

15
New cards

How long can we keep load on batteries if loaded to full design?

5-7 minutes

16
New cards

What is the float voltage of the batteries?

570 V

17
New cards

Why do we keep a float voltage of 570 V?

The float voltage is maintained to prevent overcharging.

18
New cards

Voltage

Pressure that pushes electrons through the circuit; measured in Volts

19
New cards

Current

Flow of electrons through the circuit; measured in Amps

20
New cards

Resistance

Opposition to current flow; measured in Ohms

21
New cards

Power

Work done in a circuit; measured in Watts

22
New cards

Frequency

The number of times AC completes a full cycle in a given time period, usually 1 second; Measured in Hertz.

23
New cards

Phase

Distribution of AC power, a single-phase being one hot and one neutral. Position of a wave form at a fraction of a time period

24
New cards

What is AC Power?

Alternating Current, looks like a sine wave. Very good for doing work, present in pretty much every system in the data center.

25
New cards

What is DC power?

Direct current, no change in polarity. Used in batteries and some control circuits.

26
New cards

Single Phase

One Sine wave created by one hot wire and one neutral; Typically used residentially.

27
New cards

3 Phase

3 Sine waves each set 120 degrees apart each one with two hot wires. Most critical loads use this as it’s the most power efficient source.

28
New cards

Power Usage Effectiveness (PUE)

Measures the energy efficiency of a data center, ratio of the total amount of energy used by the building to the energy delivered to computing equipment. Goal is to be as close to 1.0 as possible.

29
New cards

PUE Formula

Total Facility Load / Total IT Load.

30
New cards

Primary Function of a Circuit Breaker

Control the flow of electricity in a circuit

31
New cards

Secondary Function of a Circuit Breaker

Provides Overload Protection by tripping

32
New cards

Major External Components of a Circuit Breaker

LOTO, Status, Position, Manual Push Buttons, Charging Handle, Trip Unit

33
New cards

LOTO Function

Safety measure to ensure equipment is safely shutdown and isolated

34
New cards

Breaker Status

Open, Closed, Tripped, Charged, Not Charged

35
New cards

Breaker Position

Racked-in, test, disconnected, racked-out (withdrawn)

36
New cards

Breaker Manual Push Buttons

Used to manually close/open the circuit

37
New cards

Breaker Charging Handle

When in open status, this charges the spring so the breaker may close

38
New cards

Breaker Trip Unit

Part that opens the contacts of a breaker in the event of a fault

39
New cards

Breaker Status - Open

Circuit is open and there is no power through the circuit

40
New cards

Breaker Status - Closed

Circuit is closed and there is power through the circuit

41
New cards

Breaker Status - Tripped

Fault in the circuit and the circuit has tripped open

42
New cards

Breaker Status - Charged

Ready to close the breaker

43
New cards

Breaker Status - Not Charged

Not ready to close the breaker

44
New cards

What does it mean when a breaker is tripped?

There is an excess of electrical current in the circuit

45
New cards

LSIG

Type of circuit protection and the available adjustments based on certain trip units

46
New cards

L in LSIG

Long time setting; Overload Protection

47
New cards

S in LSIG

Short time setting; Low level fault short circuit protection

48
New cards

I in LSIG

Instantaneous Setting; High level fault short circuit protection

49
New cards

G in LSIG

Ground Fault setting; equipment ground fault protection

50
New cards

Which breaker trips are safe to reset without a thorough breaker inspection?

Engineering team can reset long term setting if they know what caused the trip

51
New cards

Who resets other types of breaker trips?

Any trips besides a long term trip (in some cases) require a technician

52
New cards

Arc Flash

Light and heat created from an arc fault explosion

53
New cards

Why are arc flashes dangerous?

Temperatures can reach 5,000 to 35,000 degrees Fahrenheit.

54
New cards

When are arc flashes most likely to occur?

When preforming energized electrical maintenance and when closing a live circuit breaker

55
New cards

What are the boundaries called for arc flashes? (In order from closest to electrical equipment to farthest)

Restricted Approach Boundary, Limited Approach Boundary, Arc Flash Boundary

56
New cards

What are the spaces called when in comes to arc flashes and the limits? (Closest to farthest)

Restricted Space, Limited Space, then unnamed space

57
New cards

How are trip settings and arc flash labels related?

Arc flash ratings are determined by the trip settings. If settings have changed then the arc flash labels must be updated.

58
New cards

What is Selective Tripping?

It is the process for when a fault occurs anywhere in the electrical distribution system, one and only one breaker will trip. The breaker is usually the one closest to the fault

59
New cards

Why does selective tripping trip the closest breaker upstream?

It trips the closest breaker upstream from the fault as to prevent cascading failure.

60
New cards

How is selective tripping accomplished?

The opening times are adjusted so the breakers closest to the faults open first

61
New cards

Open Transition

Break before make, Open contact with the primary source before closing the secondary source

62
New cards

Closed Transition

Make before break, Closed contact with the secondary source before opening the primary source.

63
New cards

Type of Transition during maintenance bypass

Closed Transition

64
New cards

Type of Transition during a transfer from utility to generator

Open Transition

65
New cards

UPS

Uninterruptible Power Supply - device that allows an electrical system to keep running for at least a short time when incoming power is interrupted until utility or generator provides the power.

66
New cards

Primary Function of the UPS

Uninterruptible Continuous power to the load

67
New cards

Secondary Function of the UPS

Protected power, filters and conditions power preventing damage to the output

68
New cards

UPS Model in Electrical rooms

Schneider Galaxy VX

69
New cards

UPS Model in PPOP and SPOP rooms

Schneider Galaxy VS

70
New cards

Type of UPS

Double Conversion

71
New cards

Output of Electrical Room UPS

1 MW

72
New cards

Output of PPOP and SPOP UPS

50 kW (?)

73
New cards

Major Internal Components of the UPS

Rectifier, Inverter, Batteries, Static Switch, Back Feed Breaker

74
New cards

Rectifier basic function

Converts AC to DC power then filters it through capacitors and trickle charges the batteries.

75
New cards

Inverter Basic Function

Converts DC to AC power via Pulse Width Modulation (PWM) and then filters again through capacitors

76
New cards

Batteries Basic Function

Provides DC power to the inverter should the utility fail

77
New cards

Static Switch Basic Function

Diverts power from the rectifier, inverter, and batteries to the load when there is a fault/failure within the UPS system

78
New cards

Back Feed Breaker Basic Function

Prevents the flow of electricity from going backwards

79
New cards

UPS Modes of Operation

Normal, Static Bypass, Maintenance Bypass, On Battery

80
New cards

UPS MOO - Normal

Power is going through rectifier, trickle charging batteries, then going through inverter to the load.

81
New cards

UPS MOO - Static Bypass

Failure within the internal components of the UPS, power is diverted from those parts

82
New cards

UPS MOO - Maintenance Bypass

Power is diverted from the UPS altogether, UPS system may safely be worked on for maintenance.

83
New cards

UPS MOO - On Battery

Batteries are supplying DC power to the inverter

84
New cards

UPS Sequence of Operation

Under normal conditions, power goes through the rectifier, trickle charges the batteries, through the inverter and to the load.

85
New cards

UPS Alarming Set Points

Over Temperature, Inverter/rectifier failure, fan failure, communication failure, power module failure.

86
New cards

When would maintenance bypass be required?

When performing maintenance on the internal components, diverting power away from the UPS altogether (externally)

87
New cards

When would static bypass be required?

When there is an internal fault or UPS failure, divers power away from the rectifier, battery, and inverter.

88
New cards

Transformer Function

Step-up or Step-down voltages in circuits (AC). DC cannot change voltages.

89
New cards

Delta Transformer Configuration

Three loads connected in a triangle shape

90
New cards

WYE Transformer Configuration

Three loads connected in a Y shape, has a neutral wire which allows for singe-phase AC power.

91
New cards

Step-up Transformers

Voltage is higher on the secondary side, lower current

92
New cards

Step-down Transformer

Voltage is lower on the secondary side, current is higher

93
New cards

Transformer Turn Ratio

The ratio between the number of turns on the primary to secondary sides of the generator. A higher turn ratio means a higher voltage.

94
New cards

PDU

Power Distribution Unit, Converts power via transformer and distributes it to multiple devices.

95
New cards

Output Power Capacities of a PDU

415/240V

96
New cards

PDU Internal Components

Input Breaker, Voltage Transformer, Current Transformer, Sub-feed Output Breakers

97
New cards

PDU Sequence of operations

480 V enter and is converted to dual tap 415/240 V and 208/120V. This is then distributed to the output through the sub-feed output breakers

98
New cards

ATS

Automatic Transfer Switch, device that automatically transfers power from primary source to secondary source if there’s a failure or power outage.

99
New cards

Normal Seeking

Has a preferred power source and will automatically transfer back to this preferred source.

100
New cards

Power Seeking

Does not have a preferred source, staying on the current source unless manually switched back to the primary source.