1/159
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced |
---|
No study sessions yet.
Voltage at Utility
230 kV
Voltage at Substation
34.5 kV
Voltage at Step-down transformer
480 V
What does a VISTA do?
VISTA is a manual transfer switch that is fed from two separate substations and can be switched between the two.
Generator Function
Provide backup power if the utility source is unavailable
480/277 Volts
high voltage range, 480 V is between 2 phases, and 277 V is between any phase and neutral.
Normal Status of Generator Breaker
Open
Normal Status of Utility Breaker
Closed
Major components in Electrical Flow path
Utility, Substation, VISTA, Transformer, Switchgear, UPS, PDU, RPP, racks.
IAD51 Electrical Redundancy
Distributive Redundancy - upon loss of 1 line, the other 4 UPS should pick up the remaining.
At what level does load shedding occur?
At the rack level.
Type of Batteries used in our UPS Electrical Rooms?
Lithium-ion Batteries
How many batteries per string in UPS Electrical Rooms
17 Batteries per String
How many strings of batteries?
5 Strings of batteries
How long can we keep load on batteries if loaded to full design?
5-7 minutes
What is the float voltage of the batteries?
570 V
Why do we keep a float voltage of 570 V?
The float voltage is maintained to prevent overcharging.
Voltage
Pressure that pushes electrons through the circuit; measured in Volts
Current
Flow of electrons through the circuit; measured in Amps
Resistance
Opposition to current flow; measured in Ohms
Power
Work done in a circuit; measured in Watts
Frequency
The number of times AC completes a full cycle in a given time period, usually 1 second; Measured in Hertz.
Phase
Distribution of AC power, a single-phase being one hot and one neutral. Position of a wave form at a fraction of a time period
What is AC Power?
Alternating Current, looks like a sine wave. Very good for doing work, present in pretty much every system in the data center.
What is DC power?
Direct current, no change in polarity. Used in batteries and some control circuits.
Single Phase
One Sine wave created by one hot wire and one neutral; Typically used residentially.
3 Phase
3 Sine waves each set 120 degrees apart each one with two hot wires. Most critical loads use this as it’s the most power efficient source.
Power Usage Effectiveness (PUE)
Measures the energy efficiency of a data center, ratio of the total amount of energy used by the building to the energy delivered to computing equipment. Goal is to be as close to 1.0 as possible.
PUE Formula
Total Facility Load / Total IT Load.
Primary Function of a Circuit Breaker
Control the flow of electricity in a circuit
Secondary Function of a Circuit Breaker
Provides Overload Protection by tripping
Major External Components of a Circuit Breaker
LOTO, Status, Position, Manual Push Buttons, Charging Handle, Trip Unit
LOTO Function
Safety measure to ensure equipment is safely shutdown and isolated
Breaker Status
Open, Closed, Tripped, Charged, Not Charged
Breaker Position
Racked-in, test, disconnected, racked-out (withdrawn)
Breaker Manual Push Buttons
Used to manually close/open the circuit
Breaker Charging Handle
When in open status, this charges the spring so the breaker may close
Breaker Trip Unit
Part that opens the contacts of a breaker in the event of a fault
Breaker Status - Open
Circuit is open and there is no power through the circuit
Breaker Status - Closed
Circuit is closed and there is power through the circuit
Breaker Status - Tripped
Fault in the circuit and the circuit has tripped open
Breaker Status - Charged
Ready to close the breaker
Breaker Status - Not Charged
Not ready to close the breaker
What does it mean when a breaker is tripped?
There is an excess of electrical current in the circuit
LSIG
Type of circuit protection and the available adjustments based on certain trip units
L in LSIG
Long time setting; Overload Protection
S in LSIG
Short time setting; Low level fault short circuit protection
I in LSIG
Instantaneous Setting; High level fault short circuit protection
G in LSIG
Ground Fault setting; equipment ground fault protection
Which breaker trips are safe to reset without a thorough breaker inspection?
Engineering team can reset long term setting if they know what caused the trip
Who resets other types of breaker trips?
Any trips besides a long term trip (in some cases) require a technician
Arc Flash
Light and heat created from an arc fault explosion
Why are arc flashes dangerous?
Temperatures can reach 5,000 to 35,000 degrees Fahrenheit.
When are arc flashes most likely to occur?
When preforming energized electrical maintenance and when closing a live circuit breaker
What are the boundaries called for arc flashes? (In order from closest to electrical equipment to farthest)
Restricted Approach Boundary, Limited Approach Boundary, Arc Flash Boundary
What are the spaces called when in comes to arc flashes and the limits? (Closest to farthest)
Restricted Space, Limited Space, then unnamed space
How are trip settings and arc flash labels related?
Arc flash ratings are determined by the trip settings. If settings have changed then the arc flash labels must be updated.
What is Selective Tripping?
It is the process for when a fault occurs anywhere in the electrical distribution system, one and only one breaker will trip. The breaker is usually the one closest to the fault
Why does selective tripping trip the closest breaker upstream?
It trips the closest breaker upstream from the fault as to prevent cascading failure.
How is selective tripping accomplished?
The opening times are adjusted so the breakers closest to the faults open first
Open Transition
Break before make, Open contact with the primary source before closing the secondary source
Closed Transition
Make before break, Closed contact with the secondary source before opening the primary source.
Type of Transition during maintenance bypass
Closed Transition
Type of Transition during a transfer from utility to generator
Open Transition
UPS
Uninterruptible Power Supply - device that allows an electrical system to keep running for at least a short time when incoming power is interrupted until utility or generator provides the power.
Primary Function of the UPS
Uninterruptible Continuous power to the load
Secondary Function of the UPS
Protected power, filters and conditions power preventing damage to the output
UPS Model in Electrical rooms
Schneider Galaxy VX
UPS Model in PPOP and SPOP rooms
Schneider Galaxy VS
Type of UPS
Double Conversion
Output of Electrical Room UPS
1 MW
Output of PPOP and SPOP UPS
50 kW (?)
Major Internal Components of the UPS
Rectifier, Inverter, Batteries, Static Switch, Back Feed Breaker
Rectifier basic function
Converts AC to DC power then filters it through capacitors and trickle charges the batteries.
Inverter Basic Function
Converts DC to AC power via Pulse Width Modulation (PWM) and then filters again through capacitors
Batteries Basic Function
Provides DC power to the inverter should the utility fail
Static Switch Basic Function
Diverts power from the rectifier, inverter, and batteries to the load when there is a fault/failure within the UPS system
Back Feed Breaker Basic Function
Prevents the flow of electricity from going backwards
UPS Modes of Operation
Normal, Static Bypass, Maintenance Bypass, On Battery
UPS MOO - Normal
Power is going through rectifier, trickle charging batteries, then going through inverter to the load.
UPS MOO - Static Bypass
Failure within the internal components of the UPS, power is diverted from those parts
UPS MOO - Maintenance Bypass
Power is diverted from the UPS altogether, UPS system may safely be worked on for maintenance.
UPS MOO - On Battery
Batteries are supplying DC power to the inverter
UPS Sequence of Operation
Under normal conditions, power goes through the rectifier, trickle charges the batteries, through the inverter and to the load.
UPS Alarming Set Points
Over Temperature, Inverter/rectifier failure, fan failure, communication failure, power module failure.
When would maintenance bypass be required?
When performing maintenance on the internal components, diverting power away from the UPS altogether (externally)
When would static bypass be required?
When there is an internal fault or UPS failure, divers power away from the rectifier, battery, and inverter.
Transformer Function
Step-up or Step-down voltages in circuits (AC). DC cannot change voltages.
Delta Transformer Configuration
Three loads connected in a triangle shape
WYE Transformer Configuration
Three loads connected in a Y shape, has a neutral wire which allows for singe-phase AC power.
Step-up Transformers
Voltage is higher on the secondary side, lower current
Step-down Transformer
Voltage is lower on the secondary side, current is higher
Transformer Turn Ratio
The ratio between the number of turns on the primary to secondary sides of the generator. A higher turn ratio means a higher voltage.
PDU
Power Distribution Unit, Converts power via transformer and distributes it to multiple devices.
Output Power Capacities of a PDU
415/240V
PDU Internal Components
Input Breaker, Voltage Transformer, Current Transformer, Sub-feed Output Breakers
PDU Sequence of operations
480 V enter and is converted to dual tap 415/240 V and 208/120V. This is then distributed to the output through the sub-feed output breakers
ATS
Automatic Transfer Switch, device that automatically transfers power from primary source to secondary source if there’s a failure or power outage.
Normal Seeking
Has a preferred power source and will automatically transfer back to this preferred source.
Power Seeking
Does not have a preferred source, staying on the current source unless manually switched back to the primary source.