Level 4 module 5 fire alarm systems

0.0(0)
studied byStudied by 0 people
0.0(0)
full-widthCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/25

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

26 Terms

1
New cards

The national institute for certification In engineering technologies (NICET) -

Establishes standardized testing of fire alarm designers and installers.

2
New cards

national fire alarm code (NFPA 72) -

The recommended requirements for installation of fire alarm systems and equipment in residential and commercial facilities are covered in this code.

3
New cards

Life safety code (NFPA 101) -

This document is focused on the preservation and protection of human life, as opposed to property.

4
New cards

NFPA 90A -

Standard for the installation of air conditioning and ventilating systems.

5
New cards

The simplest of all fire alarm systems is a hardwired system using a

Conventional initiation device.

6
New cards

Most analog addressable systems operate on a

Two conductor circuit.

7
New cards

Rate of rise heat detector is in the

HEAT STAGE.

8
New cards

Secondary power for a fire alarm system can be provided by a battery or a

Battery with an approved backup generator.

9
New cards

As defined by NFPA 72, standby time for operation of the system on secondary power must be no less than 24 hours for

Central, local, proprietary, voice communications, and household systems. No less than 60 hours for auxiliary and remote systems.

10
New cards

UL requires that any system controls that affect system operation be

Protected behind a locked door or locked out by a key.

11
New cards

The NFPA does not permit remote resetting of

Fire alarm systems that have signaled an alarm.

12
New cards

Verification is commonly used in hotels, motels, hospitals, and

Other institutions with large numbers of detectors.

13
New cards

When more than two strobes are visible from any location, the strobes must be synchronized to avoid random flashing,

Which can be disorienting and may actually cause seizures in certain individuals.

14
New cards

General signals operate throughout the

Entire building.

15
New cards

All residential alarm sounding devices must have a minimum dB rating of

85dBA at 10 feet

16
New cards

Mechanical rooms sound level is the highest and is

85dBA.

17
New cards

Urban thoroughfares sound level is

55dBA.

18
New cards

Educational occupancies sound level is

45dBA.

19
New cards

Certified central station - monitoring facilities that are constructed and operated according to a standard and are

Inspected by a listing agency to verify compliance.

20
New cards

Cables must be supported by the building structure in such a manner that the

Cables will not be damaged by normal building use.

21
New cards

Fire alarm circuits extending beyond one building are

Governed by the NEC.

22
New cards

The force required to operate manual pull stations must be no more than

5 foot pounds.

23
New cards

Temperatures below 32 Hebrews can cause false alarms and

Temperature above 120 degrees can prevent proper smoke detector operation.

24
New cards

Phase 1 recall is the method of recalling the elevator to the floor that provides the highest probability of

Safe evacuation determined by the AHJ in the event if a dire emergency.

25
New cards

Upon activation of the fire alarm, stair enclosure doors must

Unlock to permit egress.

26
New cards

If no sensors are present, cover or seal the sensor to confirm that the alarm

Originated with the sensor.