Boiler Piping, Valves, and Fittings Code Review

0.0(0)
Studied by 0 people
call kaiCall Kai
Locked
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/9

flashcard set

Earn XP

Description and Tags

Flashcards covering requirements for blowoff piping, safety valves, pressure-reducing valves, valve designs, threaded joint limitations, and material standards from the lecture notes.

Last updated 9:37 PM on 9/22/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

10 Terms

1
New cards

When are outside screw and yoke valve designs required for piping systems?

NPS 3” & larger for pressures over600 psi600\,\text{psi}

2
New cards

What is the code definition of a Slow-opening valve?

A valve that requires at least five full 360∘360^\circ turns

3
New cards

What are the sizing and material requirements for valve bypasses?

bypasses shall be at least 3/4” & Schedule 80 seamless pipe.

4
New cards

What radius is required for sweep bends in boiler blowoff piping between the boiler and blowoff tank?

Pipe connections must use sweep bends having a radius of three times the diameter of the pipe.

5
New cards

What pressure and temperature conditions must boiler blowoff discharge meet prior to entering a sanitary sewer system?

Blowoff must pass through a blowoff tank or apparatus that reduces the pressure to not more than 5 PSIG and the temperature to not more than 140∘F140^\circ\text{F}.

6
New cards

What piping material requirements apply to blowoff systems when pressure exceeds 100 psig100\,\text{psig}?

Pipe and fittings shall be steel with a thickness not less than Schedule 80 pipe. Galvanized pipe or fittings shall not be used.

7
New cards

What valve arrangements are mandated for boiler blowoff when pressure exceeds 100 PSIG?

Two blowoff valves shall be used, with at least one valve being of the slow-opening type. If a quick-opening valve is used, it must be located nearest the boiler.

8
New cards

What are the required installation clearance distances for blowoff tanks?

Blowoff tanks must be installed with a space of not less than 18 inches18\,\text{inches} between the tank and wall, and not less than 12 inches12\,\text{inches} between the tank and the floor.

9
New cards

What is mandatory regarding pressure gage installation on pressure-reducing valves?

It is mandatory that a pressure gage be installed on the low-pressure side of a reducing valve, and on the low-pressure side of each reducing valve when two or more are installed in series.

10
New cards

At what temperature limit are threaded pipe joints completely prohibited?

Threaded joints are prohibited above 925∘F925^\circ\text{F}.