Philippine Green Building Code

0.0(0)
Studied by 0 people
call kaiCall Kai
Locked
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/109

encourage image

There's no tags or description

Looks like no tags are added yet.

Last updated 9:11 AM on 7/6/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

110 Terms

1
New cards

June 22, 2015

Philippine Green Building Code, Date approved by Rogelio L. Singson (DPWH Secretary)

2
New cards

10,000 sqm - Hotel/resort, school, hospital, office, mixed occupancy

15,000 sqm - mall

20,000 sqm - condominium

The GB code is applicable to buildings types with the following minimum TGFA:

3
New cards

Visible light Transmittance (VLT)

used to determine the amount of light transmitted through the glass.

4
New cards

10% of floor area (operable window sizes)

Operable windows or balcony door shall be provided in regularly occupied spaces. The size of the opening shall be equal to at least _________ of the floor area of regularly occupied spaces.

5
New cards

86-92

Reflective white SRI

6
New cards

80-88

Basic white SRI

7
New cards

74-80

Beige/tan SRI

8
New cards

38-40

Terracotta red SRI

9
New cards

25-32

Green SRI

10
New cards

0-33

Dark brown SRI

11
New cards

0-41

Dark grey SRI

12
New cards

28-36

Red SRI

13
New cards

23-30

Blue SRI

14
New cards

70

Building metal roof surfaces shall either be colored white or have a minimum SRI of _________

15
New cards

R-8 (min. R-value of the roof)

Buildings shall be provided with roof insulation so that the average thermal resistance value (R-Value) of the roof is at least __________

16
New cards

Variable Speed Drive (VSD)

describes the equipment used to control the speed of machinery by changing the frequency of the motor that is being operated.

17
New cards

5 kW

All motors for mechanical equipment over ______ kW shall be provided with variable speed drive and high efficiency motors in accordance with Table 10.

18
New cards

heat exchangers

When buildings have outside air or fresh air supply and extract system through mechanical means, using ______________ can use the air extracted from the building areas to pre-condition the incoming outdoor air. This process exploits the fact that the extract air is usually already conditioned and therefore colder and drier.

19
New cards

sixty percent (60%) of ninety percent (90%) exhaust air.

All buildings with centralized air supply system shall use enthalpy recovery wheels with efficiency of at least ___________ of ninety percent (90%) exhaust air.

20
New cards

55 lumens/watt (elevator light lamp efficiency)

Use of energy efficient lighting and display lighting in the elevator car shall have an average lamp efficacy, across all fittings in the car, of more than ______________

21
New cards

one and a half (1-1/2) minutes

Escalators / Moving Ramps / Walkways shall be fitted with automated controls to reduce to a slower speed when no activity has been detected for a maximum period of ______________ and duration may be adjusted depending on the demand.

22
New cards

16.1 W/sqm

Maximum allowed LPD for malls (excluding accent lighting)

23
New cards

12.9 W/sqm

Maximum allowed LPD for hospitals/schools

24
New cards

10.8 W/sqm

Maximum allowed LPD for condo/hotel/resort

25
New cards

10.8 W/sqm

Maximum allowed LPD for offices

26
New cards

BUILDING AVERAGE LPD

Condo/hotel/resort - 10.8 W/sqm

Office - 10.8 W/sqm

Schools and hospital - 12.9 W/sqm

Mall - 16.1 W/sqm

BUILDING AVERAGE LPD

Condo/hotel/resort - 10.8 W/sqm

Office - 10.8 W/sqm

Schools and hospital - 12.9 W/sqm

Mall - 16.1 W/sqm

27
New cards

1.6 W/sqm - open and outdoor parking

3.2 W/sqm - covered parking

2.15 W/sqm - exterior facade

98.4 W/sqm - active entrance

65.6 W/sqm - inactive entrace

MAXIMUM ALLOWED LPD:

1.6 W/sqm - open and outdoor parking

3.2 W/sqm - covered parking

2.15 Q/sqm - exterior facade

28
New cards

sixty per cent (60%)

For covered car parks: minimum of ___________ of the lighting must be controlled by the occupancy sensors.

29
New cards

2.15 W/sqm

Maximum allowed LPD for exterior facade

30
New cards

1.6 W/sqm

Maximum allowed LPD for open and outdoor parking

31
New cards

98.4 W/sqm

Maximum allowed LPD for active entrance (pedestrian conveyance)

32
New cards

65.6 W/sqm

Maximum allowed LPD for inactive entrance (normally locked)

33
New cards

3.2 W/sqm

Maximum allowed LPD for covered parking

34
New cards

five (5) minutes

The escalator / moving ramp / walkway shall automatically be put on a standby mode when no activity has been detected for a maximum period of ___________ and duration may be adjusted depending on the demand

35
New cards

98%

Transformers that are part of the building electrical system shall have efficiencies not lower than _________ as prescribed in the DOE Guidelines on Energy Conserving Design of Buildings

36
New cards

five (5) minutes

Lighting shall switch off after the elevator has been inactive for a maximum period of ___________

37
New cards

20% fire reserve + ADD

To reduce dependence on motorized systems to supply and distribute potable or non-potable water within the building, thus help reduce energy consumption, overhead or elevated water storage systems are used, provided there's a ___________ fire reserve over and above the average daily demand supply.

38
New cards

≤ 4.8 lpm (60 psi)

Maximum flow rate for lavatory taps, kitchen faucets, and handheld bidet sprays

39
New cards

≤ 9 lpm (80 psi)

Maximum flow rate for shower

40
New cards

≤ 1 lpm

Maximum flow rate for urinals

41
New cards

≤ 6 (full), 3 (low) lpf

Maximum flow rate for dual flush water closet

42
New cards

4.9 lpf

Maximum flow rate for single flush water closet

43
New cards

building footprint area by 75

Rainwater storage tank minimum size requirement (in cu. m)

44
New cards

1.0 sqm/2,500 sqm TGFA + 50% circulation space

MRF minimum daily storage space requirements for residential dwelling: condominium and hotels/resort

45
New cards

5.6 to 8.0

R-value/inch of polyisocyanurate

46
New cards

5.6 to 6.5

R-value/inch of polyurethane

47
New cards

5.5 to 6.0

R-value/inch of closed-cell spray foam

48
New cards

3.6

R-value/inch of open-cell spray foam

49
New cards

1 to 1.1

R-value/inch of reflective bubble foil

50
New cards

2.4

R-value/inch of vermiculite/perlite

51
New cards

3.7

R-value/inch of rockwool and fiberglass

52
New cards

4.8

R-value/inch of phenolic foam

53
New cards

4.6

R-value/inch of urea formaldehyde foam

54
New cards

3.8 to 5.0

R-value/inch of polystyrene

55
New cards

See image

See image

<p>See image</p>
56
New cards

150 g/L

Maximum VOC limit for non-flat paint

57
New cards

50 g/L

Maximum VOC limit for flat paint

58
New cards

350 g/L

Maximum VOC limit for varnish (clear wood finish)

59
New cards

1.0 sqm/2,500 sqm TGFA + 50% circulation space

MRF minimum daily storage space requirements for offices

60
New cards

1.0 sqm/1,400 sqm TGFA + 50% circulation space

MRF minimum daily storage space requirements for hospital

61
New cards

1.0 sqm/400 sqm TGFA + 50% circulation space

MRF minimum daily storage space requirements for mall

62
New cards

1.0 sqm/2,500 sqm TGFA + 50% circulation space

MRF minimum daily storage space requirements for school

63
New cards

Condo/hotel/resort - 1.0 sqm/2,500 sqm TGFA + 50% circulation space

Office - 1.0 sqm/2,500 sqm TGFA + 50% circulation space

Hospital - 1.0 sqm/1,400 sqm TGFA + 50% circulation space

Mall - 1.0 sqm/400 sqm TGFA + 50% circulation space

School - 1.0 sqm/2,500 sqm TGFA + 50% circulation space

MRF SIZES

Condo/hotel/resort - 1.0 sqm/2,500 sqm TGFA + 50% circulation space

Office - 1.0 sqm/2,500 sqm TGFA + 50% circulation space

Hospital - 1.0 sqm/1,400 sqm TGFA + 50% circulation space

Mall - 1.0 sqm/400 sqm TGFA + 50% circulation space

School - 1.0 sqm/2,500 sqm TGFA + 50% circulation space

64
New cards

fifty percent (50%)

A minimum of ____________ of the required Unpaved Surface Area (USA), as required in Rule VII and VIII of the NBC, shall be vegetated with indigenous and adaptable species.

65
New cards

12.75 cmh/person or 7.5 cfm/person

minimum ventilation people outdoor Air Rate rate for malls, restaurant, supermarket

66
New cards

17 cmh/person or 10 cfm/person

minimum ventilation people outdoor Air Rate rate for Classrooms

67
New cards

8.5 cmh/person or 5 cfm/person

minimum ventilation People Outdoor Air Rate rate for Office Spaces, bedrooms, living rooms

68
New cards

8.5 cmh/person or 5 cfm/person (Office Spaces, bedrooms, living rooms)

17 cmh/person or 10 cfm/person (Classrooms)

12.75 cmh/person or 7.5 cfm/person (malls, restaurant, supermarket)

minimum ventilation People Outdoor Air Rate rate

69
New cards

at half (½) the depth of daylight zone.

The photoelectric sensor shall be located approximately at ___________ the depth of daylight zone.

70
New cards

Air Conditioning

the process of treating air so as to control simultaneously its temperature, humidity, cleanliness, and distribution to meet the requirements of conditioned space

71
New cards

Air-Conditioning, Heating, and Refrigeration Institute (AHRI)

trade association representing manufacturers of HVACR and water heating equipment within the global industry

72
New cards

American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)

global society founded in 1894, advancing human well-being through sustainable technology for the built environment with focus on building systems, energy efficiency, indoor air quality, refrigeration and sustainability within the industry

73
New cards

British thermal unit (Btu)

amount of heat energy needed to raise the temperature of one pound of water by one degree Fahrenheit

74
New cards

Building Related Illness (BRI)

diagnosable illness whose cause and symptoms can be directly attributed to a specific pollutant source within a building

75
New cards

Coefficient of Performance (COP)

ratio of heating or cooling provided to electrical energy consumed where higher COPs equate to lower operating costs

76
New cards

Daylight Zone

area substantially illuminated by daylight consistently receiving significant quantities of daylight during the day

77
New cards

Door assembly

unit composed of a group of parts or components which make up a closure for an opening to control passageway through a wall which consists of the following parts: door; hinges; locking device or devices; operation contacts (such as handles, knobs, push plates); miscellaneous hardware and closures; the frame, including the head, threshold and jambs plus the anchorage devices

78
New cards

Energy Efficiency Ratio (EER)

energy efficiency rating for room air conditioners that lists how many Btu per hour are used for each watt of power it draws

79
New cards

Enthalpy Recovery Wheel

an energy recovery device that transfers outgoing temperature and humidity to the incoming outdoor air

80
New cards

Environmental Tobacco Smoke (ETS)

secondhand smoke consisting of airborne particles emitted from the burning end of cigarettes, pipes, and cigars, exhaled by smokers containing about 4,000 compounds, up to 50 of which are known to cause cance

81
New cards

Environmental Management Bureau (EMB)

national authority in the Philippines that sets air and water quality standards and monitors ambient and point source pollutants

82
New cards

Harmonics

increased heating in equipment and conductors, the reduction of which is desirable

83
New cards

Heat Island Effect (HIE)

describes built up areas that are hotter than nearby rural areas

84
New cards

Illuminating Engineering Society of North America (IESNA)

a non-profit learned society whose mission is to improve the lighted environment by bringing together those with lighting knowledge and translating that knowledge into actions that would benefit the public

85
New cards

Light Monitor

raised structure running along the ridge of a double-pitched roof, with its own roof running parallel with the main roof

<p>raised structure running along the ridge of a double-pitched roof, with its own roof running parallel with the main roof</p>
86
New cards

Light Scoop

south-facing skylight, that uses tilted panels of transparent glass to strategically bring daylight into an interior space.

<p>south-facing skylight, that uses tilted panels of transparent glass to strategically bring daylight into an interior space.</p>
87
New cards

Office of the Building Official (OBO) -

the office authorized to enforce the provisions of NBC and its IRR in the field as well as the enforcement of orders and decisions made pursuant thereto

88
New cards

Lighting Power Density (LPD)

amount of electric lighting, usually measured in watts per square foot, being used to illuminate a given space

89
New cards

National Building Code Development Office (NBCDO)

created through DPWH Department Order, assist the Secretary in the administration and enforcement of the provisions of the GB Code and its IRR

90
New cards

Overall Thermal Transfer Value - (OTTV)

measure of the energy consumption of a building envelope

91
New cards

Outside Supply Air (OSA)

air containing at least the minimum volume of outside air filtered and conditioned to the required temperature and humidity

92
New cards

Parking, Open

parking structure with wall openings open to the atmosphere, distributed over 40 percent of the building perimeter or uniformly over two opposing sides to provide ventilation

93
New cards

Photoelectric Sensor

a device used to detect the distance, absence, or presence of an object by using a light transmitter, often infrared and a photoelectric receive

94
New cards

Professional Regulatory Commission (PRC)

the instrument of the Filipino people in securing for the nation a reliable, trustworthy and progressive system of determining the competence of professionals by credible and valid licensure examinations and standards of professional practice that are globally recognized

95
New cards

R-Value

resistance value or the capacity to resist heat loss or its thermal resistance

96
New cards

Sick Building Syndrome (SBS)

Building whose occupants experience acute health and/or comfort effects that appear to be linked to time spent therein, but where no specific illness or cause can be identified

97
New cards

Seasonal Energy Efficiency Ratio (SEER)

energy efficiency rating for central air conditioners

98
New cards

Solar Heat Gain Coefficient (SHGC)

fraction of solar gain admitted through a window, expressed as a number between 0 and 1

99
New cards

Special Waste

a class of waste that has unique regulatory requirements with potential environmental impacts that needs to be managed to minimize the risk of harm to the environment and human health

100
New cards

Unity Power Factor

power factor of 1.0 obtained when current and voltage are in phase, as in a circuit containing only resistance or in a reactive circuit at resonance.