Grounding and Bonding, Level I - 2017 Lesson 7

0.0(0)
studied byStudied by 0 people
0.0(0)
full-widthCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/39

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

40 Terms

1
New cards

A ? is a conductor installed on the supply side of a service or separately derived system to ensure the required electrical conductivity between metal parts required to be electrically connected.

supply-side bonding jumper

2
New cards

A(n) ? is the connection between two or more portions of the equipment grounding conductor.

equipment bonding jumper

3
New cards

When two conductive parts are connected together to establish electrical continuity and conductivity between them, they are ? .

bonded

4
New cards

A system bonding jumper is the connection between the grounded conductor and the equipment grounding conductor or ? , or both, at a separately derived system.

supply-side bonding jumper

5
New cards

Bonding of electrical equipment is important for a grounded system because it accomplishes all but which of the following?

It eliminates voltage gradients in the Earth.;

It always provides grounding connection to the Earth.

6
New cards

List the three elements that an effective ground-fault return path is required to perform in order to maintain and provide adequate safety.

Be electrically continuous.

Have sufficiently low impedance to limit the voltage to ground and to facilitate the operation of the circuit protective devices.

Have the capacity to conduct safely any fault current likely to be imposed on it.

7
New cards

Which of the following is not recognized in the Code as an acceptable method of attaching bonding jumpers to circuits and equipment?

Sheet metal screws

Solder connections

8
New cards

According to the NEC Style Manual, the phrase "likely to become energized" is best described by which of the following?

Failure of insulation on

9
New cards

Which part of Article 250 provides specific electrical bonding requirements?

Part V

10
New cards

Fittings for wiring methods such as electrical metallic tubing and rigid metal conduit are required to be ? .

listed

11
New cards

Effective bonding of metal parts is required to maintain effective continuity from the service to the ? .

all of the above

12
New cards

Where loosely jointed metal raceways are used and, especially where there are expansion joints or telescoping sections of raceways, the National Electrical Code requires that they be made electrically continuous by the use of a(n) ? unless the fitting is listed for use without a field inspected equipment bonding jumper.

equipment bonding jumper

13
New cards

Reducing washers are not suitable for non-service bonding in circuits over and under 250 volts to ground.

False

14
New cards

Where concentric, eccentric, or oversized knockouts are encountered in circuits over 250 volts phase to ground, one of the bonding methods in Section 250.92(B)( ? ) through ( ? ) must be applied to ensure the required continuity and conductivity.

2 / 4

250.97

15
New cards

Which of the following methods is not suitable for establishing bonding connections for circuits over 250 volts phase to ground?

A locknut on the outside and a bushing on the inside of metal enclosure

16
New cards

Standard boxes with concentric and eccentric knockouts that are listed as suitable for bonding can be used in circuits over and under 250 volts phase-to-ground.

True

17
New cards

Nonconductive coatings on equipment to be grounded shall be removed from threads and other contact surfaces to ensure good electrical continuity or be connected by means of fittings designed so as to make such removal unnecessary.

True

250.12

18
New cards

An aluminum equipment bonding jumper installed on the load side of a 400-ampere overcurrent device must not be smaller than ? .

1 AWG

19
New cards

What is the minimum-size copper supply-side bonding jumper for a 600-ampere service supplied with two 400 kcmil conductors (800 kcmil is the largest ungrounded service-entrance conductor per phase) if all the conductors are in a single six-inch raceway?

2/0 AWG

20
New cards

Where more than one raceway enters or leaves a switchboard, pull or junction box, or other equipment, it is permissible to use a single conductor to bond these raceways to the equipment where sized appropriately.

True

21
New cards

A(n) ? is generally required to connect the grounding terminal of a grounding-type receptacle to a grounded box.

equipment bonding jumper

22
New cards

Which NEC table is used to size equipment bonding jumpers on the load side of a fuse or circuit breaker?

Table 250.122

23
New cards

What is the minimum-size aluminum equipment bonding jumper required for a range receptacle installed in a metal box where the branch circuit is protected by a 60-ampere circuit breaker?

8 AWG

24
New cards

An equipment bonding jumper from a metal box to a grounding-type receptacle is not necessary for a self-grounding type receptacle.

True

25
New cards

? requires that metal water piping systems and other metal piping systems installed within or attached to buildings or structures be bonded.

Section 250.104

26
New cards

The metal water piping system is permitted to be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where large enough, or to one or more grounding ? .

electrodes

27
New cards

What is the minimum-size copper bonding jumper required for interconnected exposed structural metal if the service is rated 1,000 amperes and supplied by two parallel 600 kcmil copper conductors for each ungrounded service phase conductor?

3/0 AWG

28
New cards

The bonding connection for a metal water piping system is required to be readily accessible unless it is a buried connection or a connection made using the exothermic welding process.

False

29
New cards

Where a building or structure is supplied by a feeder or branch circuit, the bonding jumper to the metal water piping system(s) is required to be sized according to ? , based on the size of the feeder or branch circuit that supplies the building or structure.

Table 250.102(C)(1)

30
New cards

The grounded conductor of each separately derived system shall be bonded to the nearest available point of the metal water piping system(s) in the area served by the separately derived system.

True

31
New cards

An equipment bonding jumper is permitted to be installed either inside or outside of a raceway or enclosure.

True

32
New cards

When an equipment bonding jumper is installed on the outside of flexible metal conduit or liquidtight flexible metal conduit, the length of the jumper is generally limited to not exceeding ? in length.

6'

33
New cards

Where a feeder supplies a separate building or structure, and a metal frame of that structure must be bonded, what NEC table is used to size the bonding jumper?

Table 250.102(C)(1)

34
New cards

When a gas furnace is supplied by a 30-ampere branch circuit, what is the minimum size bonding conductor or jumper required for bonding the metal gas piping system?

10 AWG copper

35
New cards

Referring to the drawing, what is the minimum size required for the copper supply-side bonding jumper in this service?

2 AWG

36
New cards

Referring to the drawing, what is the minimum size required for the copper supply-side bonding jumper in this service, and what is the minimum size required for a copper load-side bonding jumper?

2 AWG / 4 AWG

37
New cards

Which of the following tables is used to size bonding conductors or jumpers for interior metal water piping systems?

Table 250.102(C)(1)

38
New cards

What is the minimum size copper bonding conductor for an interior metal water piping system if the building is supplied by a service that has a large ungrounded service entrance conductor size of 2,500 kcmil?

350 kcmil

39
New cards

The largest size bonding jumper or conductor for interconnected exposed structural metal building frames is 3/0 copper or 250 aluminum.

False

40
New cards

Bonding wedges are suitable for use to accomplish the bonding required by 250.92(B)(2) through (4).

True