What colours are used for 415V 3-phase AC?
L1 = Red, L2 = Black, L3 = Grey, Neutral = Blue, Earth = Green/Yellow.
What colours are used for 240V 1-phase AC?
Live (L1 or Phase) = Brown, Neutral = Blue, Earth = Green/Yellow.
What is the wire colour for 110V DC?
Black.
What is the wire colour for 110V AC?
Grey.
What wires are used in panel wiring?
1.5mm² and 2.5mm² tri-rated white wire.
What is used for earthing panels?
1 x 75mm² tri-rated wire, 50x4mm or 50x6mm earth tape.
What is a Cleveland multi-core cables?
XLPE insulation, LSZH sheath, armoured, black outer. Sizes: 1.5mm² to 16mm², Voltage: 600/1000V.
What are telephone cables made of?
Tinned copper, LSZH insulation, Standard: ESI 09-6 Section 4.5.
What are multi-core and panel cables used for?
Control panels, switchgear, CTs and VTs (protection and metering), AC/DC supplies, alarm circuits, tap changers, remote indication.
What are the crimp colours and sizes?
Red = 1mm² – 1.5mm², Yellow = 1.5mm² – 2.5mm², Blue = 4mm² – 6mm².
What colours are used for CT and VT ferrules?
CT = Red ferrule (IDs A, B, C, D), VT = Yellow ferrule (IDs E, F, G).
What are the 4 base wire colour pairs in a Cleveland 20-pair cable?
What gland size fits 2c–4c 2.5mm² or 5-pair cable?
20s.
What gland size fits 7c 2.5mm² or 10-pair?
20L.
What gland size fits 12c or 20-pair?
25mm.
What gland size fits 19c–27c?
32mm.
What gland size fits 37c 2.5mm²?
40mm.
What drill size do I need for a 6mm tap?
5.5mm drill.
What drill size is used for 10mm tap?
8.5mm drill.
What drill size is used for a 4mm tap?
3.5mm drill.
What drill size is used for a 5mm tap?
4.5mm drill.
What drill size is used for an 8mm tap?
6.8mm drill.
What drill size is used for a 12mm tap?
10.2mm drill.