1
New cards

When there is a conflict between the requirements of the code and the manufacturer's installation instructions, which requirements apply?

The manufacturer's installation instructions apply.

2
New cards

What is the minimum thickness required for sheathing or wrapping used for corrosion protection of pipes?

Not less than 0.008 inch (0.203 mm) thick.

3
New cards

When steel shield plates are required to protect concealed piping against physical damage, what is their minimum required thickness?

Not less than 0.0575 inch (1.46 mm) thick.

4
New cards

When rock is encountered while excavating a trench for underground piping, to what depth must the rock be removed below the bottom of the pipe?

At least 6 inches below the bottom of the pipe.

5
New cards

What is the maximum interval for supporting 1/2-inch CPVC water pipe installed horizontally?

3 feet.

6
New cards

When performing an air test on cast iron DWV piping at a pressure of 5 psi, what is the maximum increment permitted on the test gauge?

0.10 psi increments.

7
New cards

What minimum head of water is required when conducting a water test on a building drain?

A 10-foot head of water.

8
New cards

What minimum slope must condensate piping maintain?

Not less than 1 percent.

9
New cards

For an employee toilet room, where must the required lavatory be located relative to the required water closet?

In the same room as the water closet.

10
New cards

What maximum water discharge temperature is allowed for bidets equipped with ASSE 1070 or CSA B125.3 devices?

110 degrees Fahrenheit.

11
New cards

What is the maximum allowable water temperature setting supplied by an individual shower valve?

120°F.

12
New cards

What temperature range of water must be delivered from public hand-washing lavatories?

Between 85°F and 110°F.

13
New cards

What device is required on a bottom-fed water heater to prevent siphonage of the tank?

A vacuum relief valve.

14
New cards

Unless the tank's working pressure is lower, what is the maximum pressure setting permitted for a temperature and pressure relief valve?

150 psi.

15
New cards

What minimum insulation value is required for an unfired hot water storage tank?

Not less than R-12.5 (h·ft²·°F)/Btu.

16
New cards

What is the maximum distance a water heater installed in an attic can be located from the access opening?

20 feet (6.096 m).

17
New cards

What is the maximum allowable water pressure permitted on a water distribution system before a pressure reducing valve is required?

80 psi.

18
New cards

What maximum lead content is permitted for water supply pipe and fittings supplying water for drinking or cooking?

0.25 percent.

19
New cards

What horizontal distance must separate a water service pipe from a building sewer in undisturbed or compacted earth?

A minimum of 5 feet.

20
New cards

What color is required to identify nonpotable water distribution piping?

Purple.

21
New cards

How high must a barometric loop extend vertically to prevent backflow?

35 feet.

22
New cards

What is the minimum required distance between a private water well and a septic tank?

50 feet.

23
New cards

What minimum concentration of chlorine is required for 24 hours to disinfect a potable water supply system?

50 parts per million.

24
New cards

What is the minimum required slope for a 4-inch horizontal drainage pipe?

1/8 inch per foot.

25
New cards

What are the minimum required dimensions for a sewage sump pit?

18 inches in diameter and 24 inches deep.

26
New cards

What is the maximum spacing allowed between cleanouts on horizontal drainage piping?

100 feet.

27
New cards

How is a food-preparation sink required to discharge to the sanitary drainage system?

Indirectly through an air gap.

28
New cards

What minimum air gap is required between an indirect waste pipe and the flood level rim of a waste receptor?

A minimum of 2 times the effective opening of the indirect waste pipe.

29
New cards

What is the main purpose of venting in a plumbing system?

Trap seal protection.

30
New cards

What is the minimum required height above roof level for a vent terminal on a roof that serves as a sun deck?

7 feet.

31
New cards

How many fixtures does a common vent provide venting for?

Two fixtures.

32
New cards

What minimum distance above insulation materials must an air admittance valve be installed?

6 inches.

33
New cards

What is the maximum allowable retention time for untreated gray water in a collection reservoir?

24 hours.

34
New cards

What minimum water seal depth is required for an oil separator below the invert of the discharging drain?

24 inches.

35
New cards

In nonpotable rainwater collection systems, how far above the bottom of the tank must storage tank outlets be located?

At least 4 inches.