A set of vocabulary-style flashcards defining the technical classifications, standards, and spacing rules for heat-sensing fire detectors as outlined in Section 17.6.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai | Chat |
|---|
No analytics yet
Send a link to your students to track their progress
Partial or Selective Coverage
Protection provided for selected areas only, as required by governing laws, codes, or standards, which must be protected in accordance with the Code.
Nonrequired Coverage
Detection installed for fire safety objectives but not mandated by law, which must meet Code requirements except for the prescriptive spacing criteria of Chapter 17.
UL 521
The applicable standard for Heat Detectors for Fire Protective Signaling Systems that heat-sensing fire detectors shall be listed in accordance with.
Response Time Index (RTI)
A sensitivity metric that spot-type heat detectors must include in their installation instructions, technical data, and listing documentation.
Low Temperature Classification
Heat detectors with a temperature rating range of 100−134∘F (38−56∘C) and a maximum ceiling temperature of 80∘F (28∘C).
Ordinary Temperature Classification
Heat detectors with a temperature rating range of 135−174∘F (57−79∘C) and a maximum ceiling temperature of 115∘F (47∘C).
Intermediate Temperature Classification
Heat detectors with a temperature rating range of 175−249∘F (80−121∘C) and a White color code.
High Temperature Classification
Heat detectors with a temperature rating range of 250−324∘F (122−162∘C) and a Blue color code.
Extra High Temperature Classification
Heat detectors with a temperature rating range of 325−399∘F (163−204∘C) and a Red color code.
Very Extra High Temperature Classification
Heat detectors with a temperature rating range of 400−499∘F (205−259∘C) and a Green color code.
Ultra High Temperature Classification
Heat detectors with a temperature rating range of 500−575∘F (260−302∘C) and an Orange color code.
Ambient Ceiling Temperature Buffer
The requirement that the temperature rating of a detector be at least 20∘F (11∘C) above the maximum expected temperature at the ceiling.
Smooth Ceiling 0.7 Rule
The design requirement that all points on a ceiling shall have a detector within a distance equal to or less than 0.7×S, where S is the listed spacing.
Irregular Area Spacing
A provision allowing spacing between detectors to exceed the listed spacing as long as the maximum distance to the farthest point of a sidewall or corner is not greater than 0.7 times the listed spacing.