Facility Chilled Water (FCW) System

A variable primary flow system consisting of 95 air-cooled chiller skids, 11 chiller managers, 36 CDU groups, 124 CRAH units, and other components designed for continuous 24/7 operation.

2
New cards

Chiller Manager

One of 11 units that monitors between 6 and 9 chillers, staging them up or down by commanding the chillers and their respective primary pumps.

3
New cards

Staging Up Criteria

Conditions including average chiller load > 60%60\% for more than 2minutes2\,minutes, differential pressure 3PSI3\,PSI less than setpoint, or discharge temperature 2F2^{\circ}F greater than setpoint.

4
New cards

Staging Down Criteria

Conditions including average chiller load < 40%40\% for more than 10minutes10\,minutes, differential pressure within 2PSI2\,PSI of setpoint, and discharge temperature within 1F1^{\circ}F of setpoint.

5
New cards

Plant Primary Chiller Manager

The component that averages all plant differential pressure sensors to send a common pump speed command to all operating chiller managers.

6
New cards

Chiller Skid Components

Includes an air-cooled chiller, a facility chilled water pump on a VFD, an air separator, manual isolation valves, and an adiabatic cooling skid.

7
New cards

FCWS-T-SPT

The adjustable Facility Chilled Water Supply Temperature Set Point, which has a default value of 60F60^{\circ}F.

8
New cards

FCWS-DP-SP

The Facility Chilled Water System Differential Pressure Set Point, used to ramp all primary pumps together, with a default value of 20PSI20\,PSI.

9
New cards

Loss of Communication Preset Speed

The default speed of 75%75\% that a pump will maintain if it or the chiller loses communication with the chiller manager.

10
New cards

FCW Minimum Flow Setpoint

The greater of the speed required to meet the chiller minimum flow setpoint and 20Hz20\,Hz.

11
New cards

Adiabatic System

A system sized to provide 3.75GPM3.75\,GPM of water to each of the two refrigeration circuits to lower the incoming air to the condenser coils.

12
New cards

Adiabatic Enablement Temperature

The adjustable threshold where the entering air temperature for the condenser coil must be greater than 117F117^{\circ}F.

13
New cards

Adiabatic Enablement Humidity

The adjustable threshold where the ambient relative humidity must be less than 80%RH80\%\,RH.

14
New cards

Adiabatic Purge Sequence

A sequence triggered if the system hasn't run in twelve hours, running high pressure pumps for 5seconds5\,seconds to prevent water stagnation.

15
New cards

Adiabatic Winter Maintenance

The requirement that each adiabatic skid must be drained during winter months to prevent freezing.