In apartments or residential condominium of five (5) storey or more how any elevator (s) shall be kept on twenty-four (24) hour constant service?
At least 1
Exactly 1
2 or more
more than 3 elevators
At least 1
Permanent gravity ventilation openings of _ net free area opening directly to the outside of the building or extending to the outside of the building by continuous duct
not less than 5 ft^2
not less than 2 ft^2
not less than 4 ft^2
not less than 3 ft^2
not less than 2 ft^2
The effective air movement within the living zone of air used for comfortable cooling shall be:
4.6 m/min to 5.6 m/min
4.6 m/min to 7.6 m/min
5.6 m/min to 6.6 m/min
1.4 m/min to 4.6 m/min
4.6 m/min to 7.6 m/min
Spaces provided with natural ventilation shall have a minimum permanent wall opening of how many percent of the net occupied area?
7%
4%
10%
8%
4%
Strainer plates on drain inlets shall be designed and installed to that no opening is:
Greater than 1/2 inch in the least dimension
Greater than 1/4 inch in the least dimension
Greater than 1 inch in the least dimension
Greater than 2/3 inch in the least dimension
Greater than 1/2 inch in the least dimension
Wet standpipe (Class I or III) shall be limited to:
8 - storey building
More than 8 - storey
Less than 8 storey building
4 storey building
More than 8 - storey
2
Miniature Boiler
Steam heating boiler
At least 1000 mm
42 inches
2 means of feeding water
not less than 3 inches
Power Hot water Boiler (High Temperature Water Boiler)
Foam extinguishing system
8%
Annually
Package Boiler
Automatic sprinkler system
For boilers having more than 46 sq m of water surface heating or a generating capacity exceeding 910 kg/hr how many safety valves shall be required?
1
2
4
3
2
Standpipe system providing 2 1/2 inch (64 mm) hose connections to supply water for use by fire departments and those trained in handling heavy fire streams
Class I System
Class II System
Class III System
Class IV System
Class I System
What is the minimum number of hoisting rope for traction elevators?
1
4
2
3
3
For wet-pipe foam-water sprinkler systems, at what temperature is the sprinkler head quick response?
50 deg F
37 deg F
75 deg F
100 deg F
75 deg F
3 feet
Biannually
exceeds 46 m distance
Foam extinguishing system
25 mm
12
Twice
2
intermittent pilot
Power Boiler
Pressure vessel (unfired)
30 mm
6 months
Impairment coordinator
10 to 20 times
15 m high
Crude oils
41. Pipings less than 100 mm are:
Screwed
Flanged
Welded
Seamed
Screwed
Window type air conditioners shall be provided with exhaust ducts if the exhaust duct is discharged into corridors/hallways/arcades/sidewalks, etc, and shall be installed at not less than how many meter(s) above the floor level?
3.20 m
2.10 m
1.70 m
2.80 m
2.10 m
Kerosene
20 minutes
2
Halogenated extinguishing system
A pilot that burns without turndown throughout the entire period that the boiler is in service, whether or not the main burner is firing
Continuous pilot
Intermittent pilot
Interrupted pilot
Infinite pilot
continuous pilot
An approved system of devices and equipment which automatically detects a fire and discharges an approved fire
Automatic re extinguishing system
Automatic sprinkler system
Carbon dioxide extinguishing system
Deluge system
Automatic re extinguishing system
Guards or Rails at least how many ft between any part of the equipment and the edge of a roof or similar hazard, or rigidly fixed rail, guards and parapets
8 ft
12 ft
6 ft
24 ft
6 ft
Each boiler shall have a steam gauge, with dial range of not less than one and one-half time and not more than how many times the maximum allowable working pressure?
Twice
Thrice
4 times
1.5 times
Twice
A boiler having a volume exceeding 120 gallons (454 L), a heat input exceeding 200,000 Btu/hr (58.6 kW) or an operating temperature exceeding 210 F (99C) that provides hot water to be used externally or itself
Hot water heating boiler
Low pressure hot water heating boiler
Miniature Boiler
Package Boiler
Hot water heating boiler
Each boiler have at least how many safety valve?
1
2
3
4
1
How many elevators are allowed in one hoistway?
Maximum 4
Maximum of 2
Only one
4 elevators or more
Maximum 4
An alarm caused by mechanical failure, malfunction, improper installation or lack of proper maintenance, or an alarm activated by caused that cannot be determined
Mechanical Alarm
Unintended fire alarm
Smoke Alarm
Nuisance Alarm
Nuisance Alarm
Class III System
Class I
interrupted pilot
Not less than 2 hoist ways
915 mm
Manual Dry
1.66 gal/min/sq. ft
5 storey and above
6 months
121 deg C
Clean agent
175 km/hr
Wireless protection system
Wet-chemical extinguishing agent
20 feet
Coke
Maintenance aircraft hangars
175 psi
3 storey in height
Fire extinguishers should be installed in plain view, in an accessible spot room exits, which provides an escape route. It should be located away from fire hazards and installed at what height above the floor?
1,500 mm
2,000 mm
1,200 mm
3,000 mm
1,500 mm
The angle of inclination of an escalator shall not exceed how many degrees from the horizontal?
45 degrees
60 degrees
30 degrees
20 degrees
30 degrees
A burner smaller than the main burner that is ignited by a spark or other independent and stable ignition source, and that provides ignition energy required to immediately light off the main burner
Torch
Small burner
Pilot
Miniature burner
Pilot
The age limit of a horizontal return tubular, flue or cylinder boiler having a longitudinal lap joint and operating a pressure in excess of 0.345 MPa or 3.45 Bar gage shall be how many years?
30 years
50 years
40 years
25 years
30 years
LPG (liquified Petroleum Gases) are mixture of hydrocarbons liquefied under pressure for efficient transportation, storage and use. LPG are generally composed of Ethylene, Propane, Propylene, Butane, Isobutene and Butylenes. However, commercially they (LPG) are classified as mixtures of:
Propane and Butane
Propylene and isobutene
Ethylene and Propane
Propane and Propylene
Propane and Butane
Carbon Dioxide extinguishing system shall be inspected and tested for proper operation at how many months interval?
3 months
4 months
6 months
12 months
12 months
A system supplying carbon dioxide (CO2) from pressurized vessel through fixed pipes and nozzles. This system includes manual or automatic actuating mechanism
Automatic re extinguishing system
Automatic sprinkler system
Carbon dioxide extinguishing system
Deluge system
Carbon dioxide extinguishing system
Passage ways around all sides of the boiler shall have an unobstructed width of not less than:
24 inches
18 inches
12 inches
36 inches
18 inches
In case the building is not made of fire resistive material, boilers shall be located outside the building at a distance of not less than how many meter(s) from the outside wall of the main building?
3 m
2 m
5 m
7 m
3 m
The weight of the machine plus the weight of the foundation should be distributed over a sufficient soil area which is large enough to cause a bearing stress with safe bearing capacity of the soil with factor of safety equivalent to:
4
5
6
10
5
Helmets and Refrigerant mask shall be used for refrigerating plants more than how many kg rating?
35 kg
40 kg
45 kg
50 kg
45 kg
A refrigeration machinery rooms shall be of such dimensions that all system parts are readily accessible with adequate space for maintenance and operations. An unobstructed walking space at least what height?
6 ft and 8 inches
7 ft and 10 inches
10 ft and 2 inches
5 ft and 10 inches
6 ft and 8 inches
Foundation mass should be how many times the weight of the machinery it is supposed to support?
3 to 5 times
2 to 5 times
5 to 7 times
10 to 20 times
3 to 5 times
The effective temperature of the air to be used for comfortable cooling shall be maintained at:
20 deg C to 24 deg C
18 deg C to 22 deg C
15 deg C to 17 deg C
12 deg C to 15 deg C
20 deg C to 24 deg C
Work rooms (referring to maintenance shop and machine room) shall be at what height from the floor to ceiling?
At least 3000 mm
At least 4000 mm
At least 4500 mm
At least 1500 mm
At least 3000 mm
Foundation bolts of specified size should be used and surrounded by a pipe sleeve with an inside diameter of at least how many times the diameter of anchor bolt
3 times
Twice
4 times
1.5 times
3 times
The standard of Water based Fire protection system
NFPA 13A
NFPA 17A
NFPA 10A
NFPA 12
NFPA 13A
Carbon dioxide extinguishing system shall not be installed in areas normally occupied by:
Machineries
Flammable gases
Persons (People)
Heavy equipment
Persons (People)
A sprinkler system employing open sprinklers attached to a piping system connected to a water supply through the valve that is opened by the operation of detection system installed in the same area as the sprinklers. When this valve opens, water flows into the piping system and discharges from all sprinklers attached thereto
Automatic re extinguishing system
Automatic sprinkler system
Carbon dioxide extinguishing system
Deluge system
Automatic sprinkler system
A solution of water and potassium-carbonated-based chemical, potassium-acetate-based chemical or combination thereof, fanning and extinguishing agent
Foam extinguishing system
Halogenated extinguishing system
Wet - Chemical extinguishing Agent
Dry - Chemical extinguishing Agent
Wet - Chemical extinguishing Agent
No part of the boiler shall be closer than how many meter(s) from any wall?
1 m
2 m
3 m
4 m
1 m
Up to how many kilograms of refrigerant in approved containers shall be stored in a machine room at any given time?
140 kilograms
170 kilograms
150 kilograms
200 kilograms
140 kilograms
A wet stand pipe connected to a water supply for the purpose of maintaining water within the system but to which does not have a water supply capable of delivering the system demand attached to the system. It requires water from a fire department pumper (or that like) to be pumped into the system through the fire department connection in order to supply the system demand
Manual Dry
Manual Wet
Bulk Storage
Deluge
Manual Wet
A fire-extinguishing system using one or more atoms of an element from the halogen chemical series: fluorine, chlorine, bromine and iodine
Foam extinguishing system
Halogenated extinguishing system
Wet - Chemical extinguishing Agent
Dry - Chemical extinguishing Agent
Halogenated extinguishing system
When boilers are replaced or new boilers are installed in either existing or new buildings, a minimum height of at least how many mm shall be provided between the top of the boiler proper and the ceiling?
2,130 mm
4,500 mm
1,230 mm
3,120 mm
2,130 mm
A flanged is applied to piping system of how many mm in diameter?
100 mm and above
100 mm below
150 mm and above
More than 200 mm
100 mm and above
A boiler in which water is heated for the purpose of supplying heat at pressure not exceeding 160 psia (1,102 kPa) and temperatures not exceeding 250 F (121C)
Hot water heating boiler
Low pressure hot water heating boiler
Miniature Boiler
Package Boiler
Low pressure hot water heating boiler