pg 15-20 Electrical Inspection, Testing & Documentation – Module 6

0.0(0)
studied byStudied by 0 people
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
Card Sorting

1/19

flashcard set

Earn XP

Description and Tags

20 question-and-answer flashcards covering insulation resistance testing, polarity verification, earth fault loop impedance and related BS 7671 requirements from Module 6.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

20 Terms

1
New cards

Why must all electrical loads be removed or disconnected before an insulation resistance test?

To prevent damage to sensitive equipment and to avoid their influence on the insulation-resistance measurement.

2
New cards

When loads cannot be removed, how should live conductors be arranged for insulation resistance testing?

Connect line and neutral conductors together and test between the joined conductors and the earthing arrangement.

3
New cards

What must be done to the incoming neutral conductor prior to insulation resistance testing?

It must be disconnected so there is no connection with earth from the incoming supply.

4
New cards

What capability must an insulation resistance tester have according to BS 7671?

It must supply the appropriate DC test voltage at a short-circuit current of 1 mA.

5
New cards

List the two main actions in "Test 1" before insulation resistance testing.

(1) Securely isolate the circuit, including the neutral. (2) Disconnect or remove all current-using equipment and ensure switches controlling any non-removable equipment are open.

6
New cards

Name three checks included in "Test 2" before taking insulation resistance readings.

Disconnect vulnerable equipment, verify instrument/leads condition and battery state, select the correct test voltage/range.

7
New cards

For circuits NOT vulnerable to the test voltage, which additional insulation resistance readings must be taken?

Line-to-earth and neutral-to-earth.

8
New cards

What minimum insulation resistance value is generally acceptable for a 230 V system?

Greater than 1 MΩ.

9
New cards

Below what insulation resistance value (at 230 V) should further investigation normally be considered?

Less than 2 MΩ.

10
New cards

Why are insulation resistance tests important?

They reveal the condition of insulation, helping protect against electric shock, short-circuits, earth faults, leakage currents and potential fire hazards.

11
New cards

Give three examples of specialist tests mentioned that may be required for certain installations.

Protection by SELV/PELV or electrical separation, earth electrode resistance, prospective fault current (others include phase sequence, voltage drop, etc.).

12
New cards

What does BS 7671 Regulation 643.6 require regarding fuses and single-pole devices in polarity testing?

Every fuse and single-pole control or protective device must be connected in the line (live) conductor only.

13
New cards

How must bayonet and Edison screw lamp holders be connected in circuits with an earthed neutral conductor?

Their outer or screwed contacts must be connected to the neutral conductor.

14
New cards

Which combined continuity test often removes the need for a separate polarity test?

The R1 + R2 test method.

15
New cards

What is the difference between dead and live polarity testing?

Dead testing checks wiring with the installation isolated; live testing at the origin confirms that the distributor’s service cables have correct polarity before energising the installation.

16
New cards

What does Ze represent in an electrical installation?

The external earth fault loop impedance of the supply.

17
New cards

Where is Ze measured and why must the earthing conductor be disconnected during this test?

At the origin of the installation; the earthing conductor is separated to remove parallel earth paths and prove the intended means of earthing.

18
New cards

How can earth fault loop impedance be established if direct measurement is impractical?

By calculation or enquiry from the supply provider.

19
New cards

Write the formula that relates Ze, R1, R2 and Zs.

Ze + R1 + R2 = Zs (the total earth fault loop impedance of a circuit).

20
New cards

In a TN-C-S system, what does PEN stand for and what does it signify?

Protective Earth and Neutral—a single combined conductor in the supply that is later separated into PE and N within the installation.