30 Terms

1
New cards

High Voltage (HV) Switchgear

Under the GE Vernova OFW ESP, this is identified as any switchgear operating at voltages above 1000VAC1000\,V\,AC and 1500VDC1500\,V\,DC.

2
New cards

AT2 (Authorised Technician 2)

The individual responsible for checking RAMS, ensuring safety documents are robust, delivering turbine pre-task briefings, and maintaining safety precautions during work.

3
New cards

Safety Document Issuing Authority

Responsible for establishing HV isolations/earthing, issuing AE2 pre-written safety documents, and verifying equipment is safe to return to service.

4
New cards

AE2 (Authorised Engineer 2)

Responsible for risk assessments justifying live testing, approving HV safety documents, and maintaining a list of safety documents for each site.

5
New cards

ROC 1 (Remote Operation Center Role 1)

Responsible for safely operating HV equipment from the ROC for functional switching or to achieve safety from the system as instructed by an AT2.

6
New cards

ROC 2 (Remote Operation Center Role 2)

Includes all ROC 1 responsibilities plus interrogating HV systems for fault finding and operating equipment of an unoccupied turbine.

7
New cards

Circuit Breaker (CB)

Equipment used to make or break a circuit under fault or load conditions; categorized by insulating mediums like Air (ACBACB) or SF6SF_6 (GISGIS).

8
New cards

Disconnector

Used to provide physical and securable separation between conductors for isolation; generally cannot be operated under load.

9
New cards

Three-Position Disconnector

A device on the Haliade-X that can be in three states: Closed/Earth Open, Open/Earth Open, or Open/Earth Closed (Q11Q11 or Q51Q51).

10
New cards

Disconnecting Circuit Breaker (DCB)

A circuit breaker that also provides enough physical separation between contacts to be rated as a Point of Isolation (PoIPoI).

11
New cards

Q01Q01

The primary HV disconnecting circuit breaker found in the GISGIS used for main circuit protection and isolating the 66kV66\,kV supply.

12
New cards

Earth Switch

A device used to create a short circuit to earth to bring equipment to ground potential for safe access.

13
New cards

Primary Earth

An earth of suitable cross-sectional area to withstand inadvertent energisation for 2seconds2\,seconds until fault protection operates.

14
New cards

Drain Earth

A fixed or portable device applied to protect against induced voltages, impressed voltages, or inadvertent back-feed.

15
New cards

F650F650

The primary High Voltage protection relay on the Haliade-X providing protection against over/under voltage, frequency, earth faults, and over currents.

16
New cards

Instantaneous Overcurrent Protection

Protection where the relay operates as soon as current exceeds a preset value with no intentional time delay.

17
New cards

Inverse Time Protection

Protection where the operating time is inversely related to current; higher currents result in faster relay operation.

18
New cards

Main Transformer

A transformer on the Haliade-X rated at 66kV/3.1kV/3.1kV66\,kV / 3.1\,kV / 3.1\,kV using Oil as an insulating medium.

19
New cards

Service Voltage Transformer (T6T6)

A transformer used to step down voltage from 66kV66\,kV to 400V400\,V, insulated with SF6SF_6.

20
New cards

Functional Switching

Switching actions specifically aimed at returning a turbine to service or preventing a nuisance trip.

21
New cards

Safety Switching

Switching actions aimed at isolating and earthing equipment to make it safe for access, testing, or work.

22
New cards

Nuisance Tripping

The potential to inadvertently trigger an HV circuit breaker while working on specific LV systems.

23
New cards

DIESR

The HV Safety Rules acronym for: Dead, Isolate, Earth, Screen, and Release.

24
New cards

Permit to Work (PtW)

A formal, written safety document authorizing work on equipment that has been isolated, de-energized, and earthed.

25
New cards

Sanction for Test (SfT)

A document authorizing HV testing activities on equipment that may be live or not fully earthed; required for test voltages above 5000V5000\,V.

26
New cards

Limitation of Access (LoA)

A document issued for limited access to HV areas for non-electrical work under conditions not involving live conductors.

27
New cards

Interlock

A mechanical, electrical, or software feature that makes the state of two mechanisms mutually dependent to prevent unsafe operations.

28
New cards

Gas Densimeter

A device used to permanently monitor SF6SF_6 gas density in the switchgear and trigger alarms for pressure decline.

29
New cards

GDMGDM (Generator Disconnector Module)

A motorized 3-phase disconnector used to connect, disconnect, or ground the generator.

30
New cards

Turbine Island Mode (TIM)

A feature that allows the turbine to generate power in island mode to supply its own auxiliary systems during prolonged grid loss.