1/37
Flashcards covering vocabulary and technical specifications from Part 1 of the Philippine Electrical Code (PEC) for REE Board Exam preparation.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai | Chat |
|---|
No analytics yet
Send a link to your students to track their progress
Intermediate Conduit Trade Size
The maximum electrical trade size for intermediate conduit is 100mm.
Electrical Permit
The type of permit required before starting any installation work, alteration, repair, or extension on any electrical system.
PEC Application
The Philippine Electrical Code (PEC) is intended for mandatory applications by government bodies exercising legal jurisdiction over electrical installation.
Hazardous Location Classifications
Equipment for installation in hazardous locations is divided into 3 groups according to the classification of the hazards involved.
Type FCC (Flat Conductor Cable)
Individual branch circuits using this cable shall have ratings not exceeding 30A.
Type USE
An electrical conductor type applicable specifically for underground service entrance conductors.
Bending Space Requirement
If three wires of 150mm2 are connected to one terminal entering a cabinet or switchboard, the bending space at each terminal shall NOT be less than 250mm.
Auxiliary Gutter Clearance
A clearance of not less than 26mm shall be secured between bare current carrying metal parts and any metal surface of an auxiliary gutter.
Minimum Box Depth
No electrical box shall have an internal depth of less than 12mm.
Pendant
A device or equipment suspended from overhead either by means of a flexible cord carrying the current, or otherwise.
THW Copper Conductor Ampacity (8.0mm2)
The allowable ampacity of THW insulated copper conductor with an area of 8.0mm2 exposed to an ambient temperature of 30∘C is 45A.
Expansion Bolt
The hardware best suited for mounting electrical equipment on a concrete wall.
Range Neutral Load
The neutral load of a range with a demand load of 10.4kW is 7.28kW.
Permit Issuance Delay
If a project is expensive and requires complex checking, the delay for the issuance of an electrical permit shall not be longer than 5 working days.
Ground Conductor Pull Test
Splices in ground conductors shall be attached so as to withstand a pull test of 890Newton.
Class II Hazardous Location
Locations which are hazardous because of the presence of combustible dust.
THW Copper Conductor (Buried)
For an ambient temperature of 30∘C, a THW insulated copper conductor with a cross sectional area of 3.5mm2 buried underground has an ampacity of 30A.
Lightning Protection Bonding
All extended parts located within 1,800mm of the lighting protection system shall be bonded to it.
Continuous Duty
Operation at substantially constant load for an indefinitely long time.
Transformer Clearance
Transformers exceeding 112.5kVA shall not be located within 300mm from combustible materials of the building.
Steel Electrode Thickness
Electrodes of iron or steel shall be at least 6.4mm in thickness.
Neutral Insulation Level
The minimum insulation level for the neutral conductors of a solidly grounded system shall be 600V.
Advisory Rules
Rules in the PEC that are characterized by the use of the word 'should'.
Air Terminal
A device capable of drawing lightning discharge to it in preference to vulnerable parts of the protected area.
Fixed Appliance
An appliance which is fastened or otherwise secured at a specific location.
Inverse Time CB Rating
A standard rating of an inverse time Circuit Breaker (CB) is 110A.
Aerial Cable Clearance
Aerial cable under non-metallic extensions shall have a clearance of not less than 50mm from steel structure members.
Republic Act No. 184
Under this act, a licensed Master Electrician may operate and tend generators rated up to 750V.
Heavy Duty Lamp Holder
A lamp holder that must have a rating no less than 660W.
Rigid Metal Conduit Support
In rigid metal conduit wiring, conduits shall be supported at least every 3,000mm.
Open Wiring Damage Protection
Conductors within 2,000mm from the floor in open wiring method are considered exposed to physical damage.
Auxiliary Gutter Conductor Limit
Auxiliary gutters shall not contain more than 30 current carrying conductors at any cross section.
Insulation Resistance (201 to 400A)
Circuits rated from 201 to 400A require a minimum insulation resistance of 25,000ohms.
High Rise Building
For the purpose of lightning protection, a building with a height over 23m.
Branch Circuit Classification
Branch circuits are classified according to the maximum setting of the over-current device.
Type TW
An electrical conductor with the trade name 'moisture resistant thermoplastic'.
Reactor
A device used for the purpose of minimizing irregularities in the flow of welding currents.
Local Building Office
The location where an electrical permit must be filed for land-based electrical installations under the PEC.