1
New cards

What are the set point levels for both lift pumps & Jockey pump at the Castaic Pumping Plant wet-well?

*two lift pumps (4.5’)

*Jockey Pump (3.7’)

2
New cards

What is the overflow alarm level at the castaic pumping plant wet-well?

(6.8’)


3
New cards

What is the level Setpoint for the wet-well at Mission Village Pumping Plant?

  • (6.25’)


4
New cards
5
New cards

The digester pressure relief valve is set to open at how many inches of H20 & Vacuum?

  • (18” of H20)

  • (2” of vacuum)


6
New cards

How many aeration tanks & units does valencia WRP have?

  • (12 Tanks, (6 North, 6 South))

  • (5 units (2 north, 3 south))


7
New cards

What are the four tributary sewers that serve Valencia WRP?

  • Rye Canyon

  • Castaic

  • District 32

  • District 32 Relief


8
New cards

What is the Low level for the Castaic Pumping Plant Wetwell?

  • 1.5’


9
New cards

Which aeration tanks receive primary influent (non stepped & under current normal operations)

  • Tanks 1,4 North

  • Tanks 8, 10, 12 South

  • 65%


10
New cards

What is the name of the two electrical substations that can supply power to valencia WRP?

  • Val-Verde (normal)

  • Crabtree (Secondary)


11
New cards

What manhole is the lowest point between castaic Pumping Station and Valencia WRP?

  • Manhole 41


12
New cards

What is the High level point for Mission Village pumping plant wetwell?

  • 19’


13
New cards

What is the Low level for the wetwell at mission village pumping plant?

  • 3’


14
New cards

Which aeration tanks receive stepfeeding?

  • Tanks 2,5 North

  • Tanks 7,9,11 South

  • 35%


15
New cards

What are the three pumps at castaic pumping plant? (type/ flow capacity)

  • Two submerged lift pumps

  • One secondary Jockey Pump

  • Lift pump(s) capacity (4,431 gallons per pump)

  • Jockey Pump capacity (1,250 gallons)


16
New cards