Heat pump exam

0.0(0)
studied byStudied by 0 people
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
Card Sorting

1/99

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

100 Terms

1
New cards

1. An air-to-air heat pump has many of the same components as an air conditioning system. The major difference is that a heat pump also has a (an);

C: reversing valve.

2
New cards

2. What is the difference between "demand defrost" and "timed defrost?"

D: Demand defrost happens only when needed and timed defrost is based on time whether it is needed or not.

3
New cards

3. The thermostat that controls the auxiliary electric heat according to the outdoor temperature is called the;

C: outdoor ambient thermostat.

4
New cards

4. The outdoor temperature at which the heat pump provides the same amount of heat as the heat loss of the conditioned space without auxiliary heat is known as the;

A: initial balance point.

5
New cards

5. At what temperature is an outdoor ambient thermostat normally set?

B: At or slightly above the initial balance point.

6
New cards

6. The outdoor coil is frozen solid on a "no heat" service call. The most likely reason is:

D: The outdoor fan is inoperative

7
New cards

7. In order to determine a heat pumps' balance point, you must first calculate;

A: the building's heat load.

8
New cards

8. Heat pumps are sized to handle the;

A: cooling load.

9
New cards

A high effciency heat pump system desinged to function form high to low ambient conidtions below 10 F, may have

B: two outddor coils with parallel metering devices

10
New cards

10. Room thermostats for heat pumps should be installed;

B: as near to the main return air grill as possible.

11
New cards

11. When the heat pump compressor has malfunetioned, the cus tomer has the option to switch the system into;

B: emergency heat mode.

12
New cards

12. Start-up with a night set back digital thermostat requires the technician to always;

B: teach the customer to program the thermostat.

13
New cards

13. The heat pump defrost board can be manipulated by the technician to;

C: simulate the defrost cycle.

14
New cards

The air-to-air heat pump outdoor unit is most efficient if located;

C: in a moderate climate zone.

15
New cards

15. Which of the following are are innovations that may be found on new high efficiency units?

D: ECM fan motors

16
New cards

16. How may a lockout (impedance) relay be reset?

C: Simply disconnect power to the unit momentarily.

17
New cards

17. The temperature difference between the 1st and 2nd bulbs for heating on a heat pump thermostat is;

C: approximately 2°F

18
New cards

18. What does the SEER rating determine?

B. Dividing the BTUs removed by the watts consumed during the cooling season

19
New cards

19. What might happen if the indoor fan is operated at an excessive speed in the coolin mode?

A: The system will not properly remove the humidity from the condtioned space

20
New cards

20. The most preferred method of charging any system in the field is;

C: by weight.

21
New cards

21. What is the industry standard for deep vacuum?

B: triple evacuate with nitrogen

22
New cards

22. Good service practice for installation of a reversing valve includes;

D: use heat paste and wet rags while brazing in the new valve.

23
New cards

off cycle crankcase heat is provided by

A: One leg of supply voltage is directed through the start winding.

24
New cards

You are checking for proper airflow in CFM on a three ton heat pump system, The systen has one return grill measuring 24×24, which has a net free area of 3.4 square feet. You measure air velcoity and calculate an average of 400 FPM. From this infomration you can conclude that

B : airflow in CFM is within normal

25
New cards

25. What control operates the 1't stage of secondary heat?

C: The second heating stage of the indoor thermostat.

26
New cards

26. What is the industry standard for maximum duration for defrost?

D: A maximum of 30 minutes.

27
New cards

27. What is the recommended CFM across the evaporator coil of a heat pump?

B: 400 to 450 CFM.

28
New cards

28. If manufacturers specifications are not available, a good way to determine cubic feet per minute through a coil is to:

A: Use temp rise of emergency heat mode

29
New cards

29. What type of defrost is employed on this heat pump?

B: Time and temperature initiation, time or temperature termination.

30
New cards

30. Which component is responsible for energizing auxiliary heat during the defrost cycle?

D: The defrost relay.

31
New cards

31. When this unit switches to the heat mode, describe the sequence of events that take place.

A: The RVR coil is energized through TH-1. The CR coil is energized through the RVR contacts.

32
New cards

32. The DTC motor and cam will close the DTC N.O. Contacts momentarily (approx 5 seconds). How is the DFR kept energized when the DTC N.O contacts open?

C : The DFR No. contacts close , which forms a holding circuit .

33
New cards

33. How is defrost terminated in this system?

D:Either the time or temperature termination requirements has been satisfied

34
New cards

34. Where is the LLP physically tapped into the system on this heat pump?

C: On the liauid line before the reversing valve

35
New cards

35. You are starting-up a split system heat pump for the first time. The outdoor ambien temperature is 60 ° F . You check the temperature split across the indoor coil in the heat mode and find it is 38°F. You switch to cooling mode and determine a temperature split of 29°F. The most likely corrective action (relative to airflow) is;

D: increase the outdoor fan speed.

36
New cards
  1. Heat pump heating mode efficiency is rated in

B. HSPF

37
New cards

37. On a water source heat pump, the heat mode water regulating valve must be

C: reverse acting

38
New cards
  1. An R410a heat pump operating in the heating mode has a suction pressure 50 psig and head pressure of 285 psig has a compression ratio of

C: 5.7:1

39
New cards

39. Which type of heat pump does not require a defrost cycle

D. Water source

40
New cards

40. An r-410a heat pump operating in the cooling mode has a suction pressureof 129 psig . Adding 2 psig for pressure drop in the coil, the true outlet pressure is 131 psig. The temperature of the suction line at the outlet of the evaporator is 57 F. What is the superheat

D: 12 degrees.

41
New cards

41. On a time initiation / temperature termination defrost, the defrost time clock has one N.O. and one N.C: switch. When do the positions of these switches change?

B. Every 30 or 90 mineutes, depesniding on the cam insalled in the timer

42
New cards

42. What would be the result of closing registers is rooms that are uninhabited while operating in the heating mode

D: The discharge pressure and temperature will rise decreasing the life span of the unit

43
New cards

43. What is the most common complaint from a customer changing from gas heat to a heat pump?

A: Cold air at high velocities coming out of the registers.

44
New cards

44. When a heat pump is operating in the heat mode, the suction line at the compressor will feel;

D: cold and sweaty

45
New cards

45. The use of a scroll type compressor on a heat pump can eliminate the need for a;

D: suction line accumulator.

46
New cards

46. A heat pump operates satisfactorily in the cooling mode, but not in the heat mode. This could be caused by;

D: a stuck check valve or clogged TXV screen.

47
New cards

47. It is not always a good idea to immediately connect a standard gauge manifold set and hoses to a heat pump when a problem is suspected because;

C: the charge is critical, sometimes to + 1/2 oz. refrigerant.

48
New cards

48. Which component is responsible for changing the direction of the flow of refrigerant?

C: Reversing valve.

49
New cards

49. A heat pump system uses a___________as a metering device.

D. Fixed orifice

50
New cards

50. The slide valve and piston in the reversing valve is actuated by pressure directed through the;

A: solenoid and pilot valve.

51
New cards

51. During the heating cycle, the outdoor coil becomes;

B: The evaporator.

52
New cards

52. During the cooling eyele, the indoor coil becomes;

B: an evaporator

53
New cards

53. During the defrost eycle, the outdoor fan is usually;

C: turned off

54
New cards

54. Larger heat pumps that use a thermostatic expansion valve at each coil will also have;

A: by-pass lines with check valves.

55
New cards

55. Refrigerant flow through the compressor;

C: is always the same regardless of operating mode.

56
New cards

56. Because of the possibility of liquid flood-back, a heat pump that uses a reciprocating compressor should be equipped with;

D: a suction accumulator

57
New cards

57. A scroll type compressor;

B: is less susceptible to damage from liquid flood-back.

58
New cards

58. On a "no heat / no cooling" service call, you turn the thermostat to the fan on /cont position and the indoor fan operates. This action verifies;

D:The transformer is functioning

59
New cards

59. On most air-to-air heat pumps;

B. the indoor and outdoor coid are of idfferent physical size and capacity

60
New cards

60. A heat pump system, operating at 45°F ambient, may be ____________efficient than electric resistance heat.

B: 3 to 4 times more.

61
New cards

61. Since electric resistance heat provides 1 watt of usable heat for each watt of energy purchased, electric resistance heat has a COP of;

A: 1 : 1

62
New cards

62. As outside ambient air temperature decreases, a heat pump's COP;

B: decreases.

63
New cards

63. During the defrost cycle, the system switches to the__________________ mode.

D. Cooling

64
New cards

64. During the heating mode, the refrigerant in the indoor coil is under;

B: high pressure

65
New cards

65. What three things happen on most air-to-air heat pumps during defrost?

C: The reversing valve must switch to cooling mode, the outdoor fan shuts off and auxiliary heat is energized.

66
New cards

66. High suction pressure and low discharge pressure on a heat pump system can be an indication of;

B. a step closed check valve

67
New cards

67. The PREFERRED method to perform adjustments to the refrigerant charge in a heat pump system is in the________mode.

B: cooling

68
New cards

68. You answer a service call for insufficient heat. You find the suction pressure is higher and discharge pressure is lower than normal. Using a digital thermometer, you measure the line entering the reversing valve from the compressor discharge and find 215F You then measure the line leaving the reversing valve that connects to the indoor coil and find 185F. These readings are an indication of;

B: a faulty reversing valve.

69
New cards

69. The customer complaint is not enough heat. You install service gauges and find low side pressure is higher than normal and the high side pressure is lower than the normal. You switch the system to the cooling mode and find the pressures a re normal. The most likely cause of the problem is;

A: a stuck open check valve at the outdoor coil.

70
New cards

70. A customer complains that their heat pump system blows cool air periodically during the heat mode. This could be caused by;

A: a faulty defrost relay (does not energize the aux, heat during the defrost mode).

71
New cards

71. When a heat pump is in the heat mode, frost ca n accumulate on the outdoor coil even when the ambient temperature is 45°F because;

A: the outdoor coil must be colder than the ambient air

72
New cards

72. The indoor fan on a heat pump system operates;

B. at the same speed for heating or cooling

73
New cards

73. The defrost cycle can be initiated by;

C. Time and temperature

74
New cards

74. The defrost eycle can be terminated by;

C. time/temp

75
New cards

75. Movement of the piston in the reversing valve is accomplished by;

C: bleeding pressure from one side of the piston to the suction side of the compressor

76
New cards

76. Some close coupled (package unit) heat pumps use an electronic expansion valve to meter refrigerant. One advantage to using an electronic expansion valve is;

B. electronic expansion valves can maeter refirgerant in either direction

77
New cards

77. Liquid line filter/driers that are used on heat pump systems;

C: must be a special bi-flow design if used without check valves.

78
New cards

78. When installing the heat pump outdoor unit, care should be taken to provide for drainage during the____cycle .

C: defrost

79
New cards

79. The indoor coil is usually mounted in the air stream__________the auxiliary electric heat strips.

A: before

80
New cards

80. When the auxiliary heat is gas or oil, the indoor coil must be located;

B: after the heat exchanger.

81
New cards

81. Air-to-air heat pumps are most practical to operate in areas where the lowest winter temperature does not go below____________*

A:+10

82
New cards

82. The air-to-air heat pump, operating without auxiliary heat, provides air to the registers that is approximately___________°F or less.

A: 100

83
New cards

83. The most common method of defrosting the outdoor coil on an air source heat pump is;

D: reverse cycle defrost

84
New cards

84. COP is the abbreviation for;

A: Coefficient of performance

85
New cards

85. At temperatures above 45 degrees *F, the heat pump refrigeration cycle permits the

A: Condenser to release 3 to 4 times more heat than it takes in electrical energy to drive the compressor.

86
New cards

86. In addition to heat from the outdoor coil, a heat pump in the heating mode will get heat from;

D. compression

87
New cards

87. When operating in the heat mode, hot gas leaves the compressor and first flows to;

D: the reversing valve.

88
New cards

88. When operating in the cooling mode, hot gas leaves the compressor and first flows to;

D: the reversing valve.

89
New cards

89. To make the reversing valve slide move, the system must have a pressure difference of;

C: 75 to 100 psig.

90
New cards

90. Before connecting your manifold gauge set to a heat pump system, you should first;

D. Verify the operating mode of the system

91
New cards

91. In the heat mode, the suction line entering the compressor contains;

C: low pressure/ low temperature vapor.

92
New cards

92. The reversing valve is often referred to as a;

C: three-way valve

93
New cards

93. A heat pump has a thermostatic expansion valve (TEV) and a check valve at each coil. When the modes are reversed;

C: refrigerant will bypass the TEV on the coil serving as the condenser.

94
New cards

94. Mechanically troubleshooting a reversing valve can be done by;

B. By checking the temperature differential between the connection serving the low side.

95
New cards

95. A reciprocating heat pump compressor differs from a light duty A/C compressor in that;

D. It is designed to operate at high compression ratios

96
New cards

96. One of the most important devices to insure the longevity of a heat pump's reciprocating compressor is the;

C: crankcase heater

97
New cards

97. A heat pump can be difficult to charge properly because;

D.

98
New cards

98. High efficient heat pump systems charged with R-410A refrigerant normally use a

C. fixed orifice metering device for the heating cycle and a TXV for the cooling cycle

99
New cards

99. When a heat pump is operating in the cooling mode, the;

C: indoor metering device is metering refrigerant and the outdoor check valve is open.

100
New cards

100. When in the cooling mode, the low pressure refrigerant vapor leaves the reversing valve and travels to the;

B: accumulator and then to the compressor