1/24
This flashcard set covers the components, voltage thresholds, operational procedures, and troubleshooting steps for DC systems and Station Light & Power (SL&P) within a substation environment.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai | Chat |
|---|
No analytics yet
Send a link to your students to track their progress
DC System Components
The four parts consisting of batteries, battery charger, DC ground detector, and DC distribution panel.
Ground Detector
The specific component of a DC system that may or may not exist at certain substations.
Battery Usage Rationale
Batteries are used instead of the charger to ensure the station can sustain itself for at least 12hours because the battery charger is not considered reliable.
Float Voltage (60cell battery)
The state when cells are at 2.25V each, totaling 135V.
Nominal Voltage (60cell battery)
Occurs at 2V per cell (120V total), indicating the charger has been lost and should be reported.
Solid Station
A condition where battery voltage has depleted below a level where the station will operate, occurring at 1.75V per cell (105V for a 60cell station).
Solid Sub (24cell battery)
A station that would show 42V as its depleted operating limit.
Battery Longevity Methods
Actions to extend life include unscrewing control lights, de-energizing non-critical DC buses, and not turning on emergency lights.
Charger Return to Service
The sequence of turning on AC, waiting 30sec, then turning on DC.
Charger Removal from Service
The sequence of switching from AC to DC without a required 30sec wait.
COLA Circuit C1
The circuit used to close.
COLA Circuit C2
The circuit used to operate.
COLA Circuit C3
The circuit used for light indications.
COLA Circuit C4
The circuit used for alarms.
DC Alarm Conditions
The five conditions are loss of DC, abnormally high voltage, abnormally low voltage, loss of battery charger (loss of AC), and ground detector activity.
Battery Issue Contacts
The TSO (Transmission System Operator) should be contacted first, followed by the battery shop.
Critical DC Buses
Includes DC operating, DC relay, LBFB, EMS, CB control circuit, back up relay, electronic relay, and control bus.
Loss of Control Bus
Means the breaker (CB) cannot be operated remotely and must be operated from the relay itself.
DC Ground Troubleshooting Order
The TSO will direct the de-energization of non-critical buses first; backup protection must never be removed.
HMI (Human Machine Interface)
The screen (often top right corner) where battery voltage can be checked if the physical charger screen is damaged at a SAS station.
SL&P Fuse Disc De-energization
The procedure of opening the center phase first, followed by the outside phases.
SL&P Fuse Disc Re-energization
The procedure of closing the outside phases first, then closing the center phase last.
Battery Duration Calculation
Based on Bulletin 7 in SSI: divide amp hours by load amps (current/normal amps).
AC Critical Loads
Four critical loads for station light and power: battery charger, bank fans, air conditioning for electronic relays, and heaters/fans/compressors in CBs.
SL&P Testing Group Setting
Settings at a SAS station should be left on 'primary' to prevent increasing the minimum trip and losing the ground relay.