1/32
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced |
|---|
No study sessions yet.
To qualify as an electrode, a water pipe must be in contact with the earth for at least — feet. 250.52 (A)(1)
10
When using a water pipe as an electrode you must connect to it within — feet of where the water pipe enters the building. 250.68(C)(1)
5
Structural steel may be used as an electrode if it is in contact with the earth for at least — feet. 250.52(A)(2)
10
A ground ring must consist of at least — feet of # — bare copper and must be buried at least — inches deep. 250.52(A)(4) and 250.53(F)
20, 2, 30
A concrete encased electrode must consist of at least — feet of — inch rebar, or # — bare copper. 250.52(A)(3)
20, 1/2, 4
A rod or pipe electrode must consist of — feet of at least — pipe or — inch rod unless listed or other diameters. 250.52 (A)(5)
8, 3/4, 5/8
Plate electrodes must have at least — square feet of surface area and must be buried at least — inches deep. 250.52(A)(7) 250.53(H)
2, 30
Rod or pipe electrodes must be supplemented by another electrode UNLESS the resistance to ground is not over — ohms. 250.53(A) (2) exception.
25
If a ground rod is supplemented by another ground rod you must space them at least — feet apart.
6
The only electrode that must always be supplemented is the — electrode. 250.53(D)(2)
water pipe
IF solid rock is encountered, you may lay a ground rod down in a trench that is at least — inches deep. 250.53(G)
30
Underground — piping, — ground rods, and the metal parts of an underground — structure may not be used as electrodes. 250.52(B)
gas, aluminium, swimming pool
If using aluminum for the GROUNDING ELECTRODE CONDUCTOR it must not be terminated to the electrode within — inches of the earth when outside. 250.64(A)
18
No matter what the service size, the largest copper Grounding Electrode Conductor ever required to a driven ground rod, pipe, or plate electrode is # — . 250.66(A)
6
No matter what the service size, the largest copper Grounding Electrode Conductor ever required to a concrete encased electrode is # — 250.66(B)
4
Generally, the grounding electrode conductor must be installed continuous without any splice or joint. But "if necessary" it may be spliced using either — connectors or — 250.64(C)(1)
irreversible compression, exothermic welding
Main Bonding Jumper found in — Grounding electrode conductors found in —
T250.102, T250.66
Table 250.102(C)(1) is used for sizing the grounded conductor, the — bonding jumper, the — bonding jumper, and — bonding jumpers. Table 250.102(C)(1)
main, system, supply side
Exposed non-current carrying metal parts of equipment must be grounded if located within — ft vertically or — horizontally of grounded surfaces. 250.110(1)
8, 5
Equipment grounding conductor sized # — and smaller must be green or bare their entire length. 250.119
6
Flexible metal raceway may not serve as an equipment grounding path if the total length is over — feet. 250.118(7)
6
Equipment grounding conductor is found in —
T250.122
When running conductors in parallel, the equipment grounding conductor must be installed in — parallel raceway 250.122(F)
each
When installing a service raceway, an underground metal elbow installed in a run of PVC need not be grounded as long as it is buried at least — inches deep. 250.80 ex
18
The equipment grounding conductor ran to a pump motor must also be connected to the — 250.112(M)
metal well casing
Frames of household ranges and dryers may only use the grounded neutral conductor for equipment grounding purposes for — circuits. 250.140ex
existing
The grounded conductor may be used to ground exposed metal parts only on the — side of the service disconnect. 250.142
line
If a ferrous metal raceway is used to protect the GEC, it must be bonded to the GEC at — end(s). 250.(E)(1)
both
Standard locknuts may not be used for bonding purposes at the — 250.92(B)
service
A locknut on an EMT connector is not considered to be adequate bonding if you encounter concentric knockouts AND the voltage is over — volts to ground. 250.96
250
The building or structure grounding electrode system is to be used as the grounding electrode for a — 250.30(A)(4) and (5)
separately derived system
For the bonding of communication systems, an IBT can be used or you could use a metal bar that is — inch thick and — inches wide. 250.94(B)
1/4, 2
Rooftop equipment supplied with metal raceways that use non-threaded fittings must have an equipment grounding conductor of the — type. 440.9
wire