Section 608 Type I Certification Review

0.0(0)
Studied by 0 people
call kaiCall Kai
Locked
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/107

flashcard set

Earn XP

Description and Tags

108 vocabulary flashcards covering EPA Section 608 Type I Certification topics including refrigerant recovery procedures, equipment standards, and legal requirements for small appliances.

Last updated 1:50 AM on 7/22/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

108 Terms

1
New cards

Type I Appliance Maximum Charge

A maximum allowable factory charge of 5pounds5\,pounds of refrigerant.

2
New cards

Small Appliance (EPA Definition)

Products manufactured, fully charged, and hermetically sealed in a factory containing 5lbs5\,lbs or less of refrigerant.

3
New cards

Self-Contained Recovery (Operating Compressor)

Requirement to recover at least 90%90\% of the nameplate charge or achieve 4inches4\,inches of mercury vacuum.

4
New cards

Refrigerant Mixing Policy

Refrigerants cannot be mixed in any appliance or recovery cylinder.

5
New cards

Passive System-Dependent Recovery

A process for small appliances that captures refrigerant in a non-pressurized container.

6
New cards

Defrost Heater

Used to speed recovery from a frost-free refrigerator by vaporizing liquid refrigerant.

7
New cards

Mixed Refrigerant Handling

Reclamation facilities may refuse to accept a tank or charge extra for processing it.

8
New cards

Refrigerator Access Valves

Installed on both high and low sides to improve the speed of recovery.

9
New cards

Process Stub

A straight piece of tubing on small appliances typically used for piercing access valves.

10
New cards

HCFC or HFC System-Dependent Limit

The maximum normal charge allowed to use system dependent recovery equipment is 15pounds15\,pounds.

11
New cards

Restricted Capillary Tube Recovery

Requires only one access valve on the high side of the system if the compressor is operating.

12
New cards

Passive Recovery Permissibility

Permissible for recovery from domestic refrigerators.

13
New cards

R-600a

An approved hydrocarbon refrigerant for new household refrigerators, freezers, and combination refrigeration/freezers.

14
New cards

Hydrocarbon Retrofitting

Hydrocarbons are not approved for retrofit applications into existing household refrigerators.

15
New cards

Releasing Trapped Refrigerant from Oil

Essential when using passive recovery devices on small appliances with non-operating compressors.

16
New cards

Access Fitting Testing

Fittings should be leak tested after installation and before proceeding with recovery.

17
New cards

Zero psig System Pressure

Indicates that refrigerant recovery is not required.

18
New cards

System-Dependent Recovery Limit

Applicable only to appliances containing 15pounds15\,pounds of refrigerant or less.

19
New cards

Charging Cylinder Venting

Vapor vented off the top of the cylinder must be recovered.

20
New cards

Non-condensable Example

Air is a primary example found in refrigeration systems.

21
New cards

Small Appliance Leak Repair

EPA does not require repair, but recommends doing so whenever possible.

22
New cards

Recovery (Non-Operating Compressor)

Equipment must recover 80%80\% of the refrigerant or achieve 4inches4\,inches of vacuum.

23
New cards

System Flushing Agent

Nitrogen can be used to flush the system after refrigerant has been recovered.

24
New cards

Type I Certification

Required for persons handling refrigerant during maintenance, service, or repair of small appliances.

25
New cards

New Domestic Small Appliance HC

R600aR-600a is an approved hydrocarbon for use in these NEW systems.

26
New cards

Passive Recovery (Non-Operating Compressor)

Technicians should place access fittings on both the low and high sides of the system.

27
New cards

Passive Recovery (Operating Compressor)

Technicians should run the compressor and recover from the high side only.

28
New cards

RV Refrigerants

Ammonia, Hydrogen, and water; these should not be recovered.

29
New cards

Recovery Equipment Certification

Must be certified by an EPA-approved testing laboratory.

30
New cards

Compressor Heat Gun Application

Used to help vaporize trapped liquid refrigerant during the recovery process.

31
New cards

Active Recovery Equipment

Equipment that has its own independent means to recover refrigerant.

32
New cards

Small Appliance Service Certification

Personnel must hold Type I or Universal certification.

33
New cards

Technician Regulation Responsibility

The technician is responsible for complying with any future changes to EPA regulations.

34
New cards

Reclaiming Mixed Refrigerants

Mixing multiple refrigerants in the same cylinder makes them unreclaimable.

35
New cards

Recovery Odor (Strong)

A strong odor detected during recovery usually indicates a compressor burnout.

36
New cards

Deep Vacuum Precaution

The compressor should never be energized while the system is in this state.

37
New cards

R-12/R-22 Thermal Decomposition

Exposure to open flames or hot surfaces can form phosgene gas.

38
New cards

R-134a

The most common replacement for R12R-12 in new household refrigerators.

39
New cards

Certification Manufacturing Date

Recovery equipment manufactured after November 15, 1993 must be certified by an EPA laboratory.

40
New cards

Type I Charge Threshold

5pounds5\,pounds is the maximum factory charge for appliances classified as Type I.

41
New cards

Solderless Piercing Valves

Should not remain on systems after repairs because they tend to leak over time.

42
New cards

Nitrogen Usage Rule

Only nitrogen vapor should be used for pressurizing or clearing debris.

43
New cards

Cylinder Pressure Reading Accuracy

Important to ensure the refrigerant is stable at room temperature for an accurate reading.

44
New cards

ARI 740-1993

The standard that recovery devices manufactured after November 15, 1993 must meet.

45
New cards

Shipping Standards

Refillable tanks for recovered refrigerants must meet Department of Transportation standards.

46
New cards

R-22 Pressure at 75F75\,^\circ F

Pressurized to 130psig130\,psig in the absence of non-condensables.

47
New cards

Refrigerant Type Determination

The necessary first step before beginning any refrigerant recovery procedure.

48
New cards

Section 608 Regulated Refrigerants

Refrigerants such as R12R-12 must be recovered using certified equipment.

49
New cards

Large Refrigerant Release Action

Requires leaving the area or using self-contained breathing apparatus (SCUBA).

50
New cards

Maintenance (Recovery Device)

Regularly checking for refrigerant leaks.

51
New cards

Pungent Odor

Detectable during recovery when a compressor burnout has occurred.

52
New cards

Recovery Aid (Inoperative Compressor)

It is necessary to heat and strike the compressor with a rubber mallet.

53
New cards

Refrigerant Suffocation Hazard

Refrigerants are heavier than air and displace oxygen in contained areas.

54
New cards

Non-Type I MVAC systems

An MVAC-like system holding 3pounds3\,pounds of R12R-12 is not a Type I appliance.

55
New cards

R-500 Recovery

Must be recovered into its own dedicated vessel or one already containing R500R-500.

56
New cards

Service Manifold Practices

Use hand valves or self-sealing hoses to minimize refrigerant release.

57
New cards

Certification Renewal

EPA Section 608 certification has no expiration date.

58
New cards

R-12 Drop-In Substitute

There is no direct service drop-in substitute available for small appliances.

59
New cards

Piercing Valve Material Limit

Should only be used on copper or aluminum tubing.

60
New cards

PTAC

Packaged terminal air conditioners with 5pounds5\,pounds or less of refrigerant, certified under Type I.

61
New cards

R-500 Pressure at 75F75\,^\circ F

Pressurized to 95psig95\,psig in the absence of non-condensables.

62
New cards

Very-High-Pressure Appliance

Liquid phase saturation pressure above 355psia355\,psia at 104F104\,^\circ F.

63
New cards

R-22 Drop-In Substitute

There is no direct service drop-in substitute for R22R-22 in small appliances.

64
New cards

Enclosed Spill Procedure

Technicians should vacate and ventilate the spill area.

65
New cards

R-12 Pressure at 75F75\,^\circ F

Pressurized to 75psig75\,psig in the absence of non-condensables.

66
New cards

Nitrogen Tank Accessory

Must always be equipped with a regulator.

67
New cards

Active Recovery Vapor Draw

Draw from the high side to avoid accidental liquid removal from a vapor-only device.

68
New cards

Nitrogen Venting

Venting is allowed when nitrogen is used for pressurizing or blowing debris.

69
New cards

Low Loss Fittings

Used to prevent refrigerant loss from hoses when they are disconnected.

70
New cards

Sale of Refrigerants

Restricted to technicians who are EPA certified in refrigerant recovery.

71
New cards

R-410A Pressure at 90F90\,^\circ F

Pressurized to 300psig300\,psig in the absence of non-condensables.

72
New cards

DOT Regulation 49 CFR

Requires number of cylinders of each gas recorded for hazard class 2.2 shipping papers.

73
New cards

Process Tube

A service aperture consisting of a straight piece of tubing on small appliances.

74
New cards

Appliance Service Port

Required on all appliances for adding or removing refrigerant.

75
New cards

Phosgene Gas Formation

Gas formed when R12R-12 and R22R-22 decompose at high temperatures.

76
New cards

Hydrochloric Acid

One of the acids formed from thermal decomposition of R12R-12 or R22R-22.

77
New cards

Hydrofluoric Acid

An acid product resulting from the decomposition of refrigerants at high temperatures.

78
New cards

Active Recovery High Side Pressure

Caused by non-condensables in the recovery cylinder or an un-opened inlet valve.

79
New cards

Small Appliance Exception (Self-Contained)

Persons working only on small appliances are exempt from keeping a self-contained machine at the shop.

80
New cards

System Flushing

Using nitrogen after recovery to clean the refrigeration cycle.

81
New cards

Type I Recovery Personal Scope

Applicable for maintenance, service, or repair of small appliances.

82
New cards

CFC Recovery Standard

Requires certification by an EPA-approved testing laboratory for equipment.

83
New cards

Vaporization (Frost-free Fridge)

Turning on the defrost heater to vaporize any trapped liquid refrigerant.

84
New cards

Cylinder Stabilization

The procedure of allowing cylinder temperature to reach room temperature before pressure checks.

85
New cards

Vacuum Pump Limit

Can only be used as a recovery device with a non-pressurized container.

86
New cards

Reclamation Mix Management

Options include refusing the mix or charging extra for special processing.

87
New cards

Self-Sealing Hoses

Equipment used to minimize refrigerant release during manifold connection.

88
New cards

Safe Work Practices (EPA)

Standard safety measures like wearing gloves and safety glasses during service.

89
New cards

Copper and Aluminum Tubing

The only materials on which piercing-type valves should be used.

90
New cards

Passive Recovery Side Access

Required on both the high and low side if the system compressor does not run.

91
New cards

Vented Vapor Recovery

Compulsory recovery of vapor from charging cylinders.

92
New cards

EPA Disposal Rule (Post-93)

Disposal recovery for small appliances requires using ARI 740-1993 certified equipment.

93
New cards

Hazard Class 2.2

Category for Non Flammable Compressed Gases on DOT shipping papers.

94
New cards

Mercury Vacuum (Standard)

4inches4\,inches is the target for both operating and non-operating compressor recovery.

95
New cards

Nameplate Charge (Target)

90%90\% is the recovery objective when the compressor is operating.

96
New cards

Liquid Pressure Saturation (VHP)

Pressure above 355psia355\,psia at 104F104\,^\circ F defines a Very-High-Pressure appliance.

97
New cards

Refrigerant Displacement

The process by which leaking refrigerant displaces oxygen, leading to suffocation.

98
New cards

Burnout detection method

Detection of a pungent or strong odor during a system recovery.

99
New cards

Process Stub Access

The location where a piercing-type access valve is installed.

100
New cards

80 percent capture

The minimum recovery standard for small appliances with an inoperative compressor.