According to 1999 NPCP Sec. 609.7, no building water service pipe shall be less than __________ in diameter.
19mm (2/3")
A pipe fitting that is threaded on the outside at both ends and used to join couplings or other fittings is called a __________.
nipple
A Galvanized Iron nipple that is below 3inches (75mm) in length is known as a __________ nipple.
short (or shoulder)
A pipe fitting having a bend with an inside thread on one end and an outside thread on the other is called a __________ elbow.
street
A valve in which the flow of fluid is cut off by means of a circular disc fitted against machine-smoothed faces at right angles to the flow direction is a __________ valve.
gate
A control valve screwed into the street water main to supply the house service connection is called a __________ cock.
corporation
An unwanted sound created by pipe vibration due to the sudden stoppage of water flow is known as __________.
water hammer
An escutcheon is a circular disc or flange on a pipe used to cover a __________ in a wall or floor through which the pipe passes.
hole
According to the pipe color coding standards, pipes conveying Fresh Water are colored __________.
Green
Galvanized steel supply pipes are typically 1/2inch in diameter with a standard length of __________ feet.
20
PPR PN 10 pipe is designed for cold water piping, having a nominal pressure rating of 10Bars or __________ kPa.
1,000
PPR PN 20 pipe is suitable for hot & cold water piping, having a nominal pressure rating of 20Bars or __________ psi.
290
Unplasticized polyvinylchloride (uPVC) pipes do not contain phthalates and __________.
BPA (Bisphenol A)
A coupling designed to re-connect PVC pipes or connect two pipes into a pipeline is called a __________ Joint.
Gibault
Among copper tubings, Type __________ has the thickest wall section, is color-coded Green, and is used for deep underground burial.
K
Copper tubing color-coded in Blue with a wall section most popular for water supply systems is Type __________.
L
Copper tubing color-coded in Red used in residential and commercial water supply where pressure is not too high is Type __________.
M
Leakages and pilferages in a water supply system should ideally account for no more than __________% of water consumption.
15
In a per capita daily consumption breakdown of 120liters, toilet flushing accounts for __________% of total water demand.
40
The average daily livestock water demand for each milk cow is __________ liters/day.
133
The formula for projected design population (Pd) based on a 3% annual increase over 5 years is Pd=__________ \times P$$.
1.15
When calculating design population without explicit data, non-residential projects use an occupant load assumption of __________ square meters per person.
11
The recommended design period for pumps, wells, pipelines, and storage tanks is __________ years.
5
The formula for Maximum Hour Demand (MHD) in liters per second is MHD=3×[ADD÷__________\,\text{seconds}]$$.
10,800
In a direct water supply system, the pressure at the water main must be at a minimum of __________ kPa.
103
Water Supply Fixture Unit (WSFU) is an index number that uses a lavatory for private use as __________ WSFU.
1
A private-use water closet equipped with a flush tank carries a fixture load of __________ WSFU.
3
A public-use water closet equipped with a flushometer valve requires a minimum pressure requirement of __________ psi.
25
According to PPR PN 20 sizing data, a pipe with a 32mm specified outside diameter serves a fixture load of __________ WSFU.
11-25
The usual operating pressure range in a hydro-pneumatic pressure system is 138kPa (20psi) minimum to __________ kPa (40psi) maximum.
276
An above-grade storage tank positioned directly adjacent to the suction end of a booster pump generates a __________ suction head.
positive
An underground water storage container positioned below grade and below the suction end of a booster pump is called a __________ cistern.
break
The capacity of a suction tank (Cst) in liters is calculated using the formula Cst=ADD×__________$$.
1.03
A conventional air-over-water pressure tank is prone to becoming __________ logged when air dissolves directly into the water.
water
Diaphragm and bladder pressure tanks can withstand operational pressures up to __________ kPa (125psi).
862
An air space provided between the maximum water level and soffit of the top slab of a tank is called free board and must be at least __________ mm.
200
The space provided at the bottom of a storage tank to accommodate accumulated silt is called __________ storage.
dead
To determine the elevation head of a gravity tank (H) in meters, divide the Design Fixture Requirement in kPa by __________ kPa/meter.
9.81