RA 9514 Fire Code

0.0(0)
Studied by 5 people
call kaiCall Kai
Locked
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/99

encourage image

There's no tags or description

Looks like no tags are added yet.

Last updated 6:02 AM on 6/29/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

100 Terms

1
New cards

Minimum exit door width.

0.71 mtr.

2
New cards

Minimum floor to ceiling height.

2.30 mts.

3
New cards

Maximum stair rise height for a class A stair.

0.19 mtr.

4
New cards

Maximum height between landings for class A stair.

2.75 mts.

5
New cards

Minimum headroom for class A & B stairs.

2.00 mts.

6
New cards

Unit area per person for waiting areas or standing rooms.

0.28 sqm.

7
New cards

Number of exits for place of assembly for 1000 occupants

4 exits

8
New cards

Travel distance to an exit without fire sprinkler system.

46.00 mts.

9
New cards

Travel distance to an exit with fire sprinkler system.

61.00 mts.

10
New cards

Minimum spacing of rows of seats from back to back for a public assembly building.

0.83 mtr.

11
New cards

Maximum number of seats in a row in between aisles.

14

12
New cards

Maximum number of seats in a row opening on to an aisle at one side.

7

13
New cards

Standard width of a seat without dividing arms for places of assembly.

60 cms.

14
New cards

Minimum width of an aisle serving an occupant of 60.

91 cms.

15
New cards

Minimum headroom created by any projection from the ceiling.

2.00 mts.

16
New cards

Minimum clear width of turnstiles.

56cms.

17
New cards

Minimum dimension of landings in direction of travel for class A & B stairs.

112 cms.

18
New cards

Minimum number of risers in any one (1) flight of stairs.

3

19
New cards

Minimum height of a handrail above the upper surface of the tread.

76cms.

20
New cards

Minimum clearance of a handrail from any wall.

38cms.

21
New cards

Minimum height of a guard rail.

91cms.

22
New cards

Maximum height of a guard rail.

106cms.

23
New cards

Minimum inner radius of a monumental stair.

7.50mts

24
New cards

Minimum width of any balcony or bridge.

112 cms.

25
New cards

Minimum width of a class A ramp.

112 cms.

26
New cards

Maximum rise of any floor from the balcony floor to which an access door leads.

20.3cms.

27
New cards

Maximum vertical height in floors for an escalator.

1 floor

28
New cards

Minimum width of a fire escape stair for existing stairs.

55.9 cms.

29
New cards

Minimum width of landing for a fire escape stair for existing stairs.

55.9 cms.

30
New cards

Minimum tread for a fire escape stair for small buildings.

15.25 cms.

31
New cards

Maximum rise of fire escape stair for a small building.

30.5 cms.

32
New cards

Maximum rise of fire escape stair for existing stairs.

22.9 cms.

33
New cards

Maximum height between landings for a fire escape stair for existing stairs.

3.66 mts.

34
New cards

Minimum headroom clearance for a fire escape stair for existing stairs.

2.13 mts.

35
New cards

Minimum headroom clearance for a fire escape stair for small buildings.

1.98 mts.

36
New cards

Number of exits for place of assembly for 600-1000 occupants.

3 exits

37
New cards

Maximum occupant load for a class C public assembly.

50-300

38
New cards

Minimum number of exit for an Institutional type of structure.

2 exits

39
New cards

Maximum travel distance between room door intended as exit access and exit with

sprinkler system for institutional use.

30 mts.

40
New cards

Maximum travel distance from the door of any room to exit for hotels with sprinkler.

30 mts.

41
New cards

Maximum travel distance from the main entrance door to exit for apartments with sprinkler.

31 mts.

42
New cards

Minimum increase in width for an aisle per linear meter.

2.5 cms

43
New cards

Minimum width of an aisle serving an occupant of 60 or more serving one side for a

public assembly building.

91 cms.

44
New cards

Minimum width of an aisle serving an occupant of 60 or more serving two sides for a public assembly building.

1.00 mts

45
New cards

Minimum width of an aisle serving an occupant of below 60 for a public assembly building.

76 cms.

46
New cards

Minimum width of an aisle for an educational use building.

1.80 mts

47
New cards

Minimum width of an aisle for hospitals or nursing homes.

2.44 mts.

48
New cards

Minimum width of an aisle for custodial care institutions.

1.83 mts

49
New cards

Minimum width of an aisle for business use structure.

112 cms.

50
New cards

Minimum width of an aisle for an industrial building.

112 cms.

51
New cards

Occupant load per person for laboratories.

4.60 sq.m.

52
New cards

Jails are classified under what classification of occupancy.

Institutional

53
New cards

Courtrooms with an occupant load of more than 100 are classified under what

classification of occupancy.

Assembly

54
New cards

Armories with an occupant load of more than 100 are classified under what classification

of occupancy

Assembly

55
New cards

Libraries are classified under what classification of occupancy.

Business

56
New cards

Rooms where baled, bundled or piled materials segregated into desired sizes or groups.

Picking rooms.

57
New cards

Buildings or structures 15 meters or more in height.

High rise building

58
New cards

Buildings or structures used for the storage of explosives, shells, projectile, etc.

Explosive magazine

59
New cards

An air compartment or chamber to which 1 or more ducts are connected and which form

part of an air distribution system.

Plenum

60
New cards

A kind of stable explosive compound which explodes by percussion.

Fulminate

61
New cards

Descriptive of any substance that ignites spontaneously when exposed to air.

Phyrophoric

62
New cards

A material that readily yields oxygen in quantities sufficient to stimulate or support

Oxidizing material

63
New cards

A process where a piece of metal is heated prior to changing its shape and dimension.

Forging

64
New cards

The process of first raising the temperature to separate the more volatile from the less volatile parts and then cooling and condensing the result vapor so as to produce a nearly purified substance.

Distillation

65
New cards

A finely powdered substance which, when mixed with air in the proper proportion and

ignited will cause an explosion.

Dust

66
New cards

Temperature rating at flash point.

37.8 oC (100 oF)

67
New cards

A class of fire with flammable liquid and gasses.

Class B

68
New cards

The temperature at which a liquid is transformed or converted into vapor.

Boiling Point

69
New cards

Minimum fire resistance rating for a firewall.

4 hrs.

70
New cards

A continuous passageway for the transmission of air.

Duct System

71
New cards

The minimum temperature at which any material gives off vapor in sufficient

concentration to form an ignitable mixture with air.

Flush point

72
New cards

A gas, fume or vapor used for the destruction or control of insects, fungi, vermin, germs,

rodents or other pests.

Fumigant

73
New cards

Minimum width of any driveway in and around a lumber yard / piles.

4.50 mts.

74
New cards

Minimum height of fence for a lumber yard for exterior storage of lumbers.

4.50 mts.

75
New cards

Maximum width of sumps for the retention of oil and petroleum products.

3.70 mts.

76
New cards

Minimum distance of an incinerator from any structure used other than a single family

dwelling.

3.00 mts.

77
New cards

Minimum door width of a single door in a door way.

71 cms.

78
New cards

Maximum force in kilograms required for a panic hardware

7 kgs.

79
New cards

Maximum height required for a panic hardware installation.

112 cms.

80
New cards

Minimum height required for a panic hardware installation.

76 cms.

81
New cards

Maximum number of occupant for a subdivided room or space by a folding partition.

20

82
New cards

Minimum width of a door for family day care homes.

61 cms.

83
New cards

Any material which by its nature or as a result of its reaction with other elements

produces a rapid drop in temperature of the immediate surrounding.

Cryogenic

84
New cards

Classified as mercantile occupancies, the travel distance from exits shall be.

30.50 mts.

85
New cards

Under what classification of occupancy does pool rooms fall.

Assembly

86
New cards

Under what classification of occupancy does home for the aged fall.

Institutional

87
New cards

Under what classification of occupancy does court houses fall.

Business

88
New cards

Under what classification of occupancy does refineries fall.

Industrial

89
New cards

Under what classification of occupancy does drugstores fall.

Mercantile

90
New cards

Class of fire involving combustible metals, such as magnesium, sodium, potassium, and

other similar materials.

Class D

91
New cards

Class of fire involving ordinary combustible materials, such as wood, papers, cloth, rubber, and plastics.

Class A

92
New cards

A tank, vat or container of flammable or combustible liquid in which articles or materials

are immersed for the purpose of coating, finishing, treating or similar processes.

Dip Tank

93
New cards

An integrated system of under ground or overhead piping or both connected to a source

of extinguishing agents or medium and designed in accordance with fire protection

engineering standards which when actuated by its automatic detecting device,

suppresses fire within the area protected.

Automatic Fire Suppression System

94
New cards

A continuous and unobstructed route of exit from any point in a building to a public way.

Means of Egress

95
New cards

Under what classification of occupancy does museums fall?

Assembly

96
New cards

Under what classification of occupancy does town halls fall?

Business

97
New cards

Class III combustible liquids shall mean any liquid having a flash point at how many

degrees Celsius?

60 oC

98
New cards

Includes buildings or groups of building under the same management in which there are

more than 15 sleeping accommodations for hire.

Hotel

99
New cards

Includes buildings containing three or more living units independent cooking and bathroom

facilities, whether designed as rowhouse, apartment house, tenement, garden apartment,

or by any other name.

Apartment Buildings

100
New cards

Occupant load per person for classrooms.

1.80 sqm.