AOP-101 Rapid Power Reduction

0.0(0)
studied byStudied by 1 person
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
Card Sorting

1/27

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced

No study sessions yet.

28 Terms

1
New cards

Entry Condtions

Power Reduction Greater than 12MWe/min

*This AOP is NOT required to be entered to initiate a power reduction during overpower conditions

<p>Power Reduction Greater than 12MWe/min</p><p>*This AOP is NOT required to be entered to initiate a power reduction during overpower conditions</p>
2
New cards

Foldout Page Criteria

(4)

E-0 Transition
If Reactor Trip: Go To E-0

AOP-207 Transition
If Turbine Trip OR Runback: Go To AOP-207

Manual Rod Control
IF auto-movement blocked by C-5: Operate in MANUAL

Step 1 Return
IF TCPS target load changes AND still >150MWe: Return Step 1

<p>E-0 Transition<br>If Reactor Trip: <strong>Go To</strong> E-0</p><p>AOP-207 Transition<br>If Turbine Trip <u>OR</u> Runback: <strong>Go To</strong> AOP-207</p><p>Manual Rod Control<br>IF auto-movement blocked by C-5: Operate in MANUAL</p><p>Step 1 Return<br>IF TCPS target load changes <u>AND</u> still &gt;150MWe: Return Step 1</p>
3
New cards

Rods in Manual Temperature band

(Step 1)

Deviation between 0 - 5°F

<p>Deviation between 0 - 5°F</p>
4
New cards

Reduce Generator Load Method and Alternate

(Step 2 and RNO)

Ensure Megawatt IN, then go

Toggle Manual Runback to 250MW/min (normally 2500)
*Manual Fails = Trip Turbine, Go To AOP-207

<p>Ensure Megawatt IN, then go</p><p>Toggle Manual Runback to 250MW/min (normally 2500)<br>*Manual Fails = Trip Turbine, <strong>Go To </strong>AOP-207</p>
5
New cards

Options if Tavg NOT maintained >551°F

(Step 4 and RNO)

  1. Restore to >551°F within 30min

  2. Go To E-0

<ol><li><p>Restore to &gt;551°F within 30min</p></li><li><p><strong>Go To </strong>E-0</p></li></ol><p></p>
6
New cards

E-0 Requirement based on SG NR Level

(Step 10)

Step 10 RNO
IF cannot maintain greater than 21% NR

<p>Step 10 RNO<br>IF cannot maintain greater than 21% NR</p>
7
New cards

What Target Megawatt aligns Auxiliary Steam

(Step 12)

360 MWe (Approximately 30% Plant)

<p>360 MWe (Approximately 30% Plant)</p>
8
New cards

Securing a MFW Pump (First)
What Megawatt Target?
Sequence of steps to secure pump?

Less than 720MWe

  1. Manual and Start of Aux LO pump

  2. Stop MFW Pump

  3. Ensure Discharge Valve closes

9
New cards

Securing a Condensate Pump
What Megawatt Target?
Sequence of steps to secure pump?

(Step 16 & 17)

Less than 480MWe

Per SOP

10
New cards

Securing a MFW Pump (Second)
What Megawatt Target?
Sequence of steps to secure pump?

(Step 19 & 20)

Less than 360MWe

Manual and Start of Aux LO pump
Stop MFW Pump
Ensure Discharge Valve closes

11
New cards

What Target Megawatt are Rods placed in Manual and Steam Dumps moved to Pressure Mode

(Step 21 & 22)

Less than 240 MWe

12
New cards

Basis Step 1

What GFES factor causes positive reactivity addition during Turbine Load reduction?

Power Defect

13
New cards

Basis Step 2

At what ramp rate could Bypass Valves open?

Is this desirable?

>60MWe/min (5%/min)

Operation of bypass valves will NOT assist REACTOR power lowering, however if the objective is to lower TURBINE power steam dumps will NOT impede reduction therefore a faster manual runback may be desirable

14
New cards

Basis Step 2 Note 2

What should your INITIAL MWe target be during reduction?

>150MWe

“target of 150MWe can complicate Tavg controller later”

15
New cards

Step 2 Basis

Why do we use Megawatt IN during load reduction?

“Provides a rate and fine tuning component to coarser load controller setting” (Finer control)

16
New cards

Step 16 Basis

When do we realign MSR reheater scavenging steam vents?

What is high/low power destination of vent paths?

When the down power reaches 480MWe (40%RTP) Just before stopping a Condensate Pump

*Seems to be some confliction with Step 18 basis based on 40% vs. 32% not sure if it’s important enough

High: Feedwater Heaters for plant efficiency
Low: Condenser

17
New cards

Step 25 Basis

If the Main Generator is the only source of power to the UATs, when will the RATs be aligned to ES buses?

PRIOR to opening the Main Generator Output Breaker (Turbine Trip)

*Manually transfer ES buses instead of foolishly relying on a residual bus transfer to complicate the transient

18
New cards

Step 26 Basis

What is status of Real and Reactive Power when tripping the turbine?

Why is Reactive power changed to this load?

Real: <15% Turbine Load (150MWe)
Reactive: ±10MVAR

Minimize effects to Grid on trip

19
New cards

Turbine Auxiliaries Refresher during coast down

Jacking Oil Pump Start

MSOP Start

TGOP Start (Bearing Oil pressure)

TGOP Start (Main Oil Pump discharge pressure)

knowt flashcard image
20
New cards

GCC Notification Requirements

(Step 3)

knowt flashcard image
21
New cards

How to Close Bypass Valves?

(Step 5)

knowt flashcard image
22
New cards

Transferring Steam Dumps to Pressure Control Mode

(Step 23)

Notice, Rods already in MANUAL per previous step

<p>Notice, Rods already in MANUAL per previous step</p>
23
New cards

Lowering power below 150MWe

(Step 24 and RNO)

knowt flashcard image
24
New cards

MVAR Status when Tripping Turbine

(Step 26)

knowt flashcard image
25
New cards

Refresher

Turbine Coast down

(Step 28)

knowt flashcard image
26
New cards

How to maintain a Critical Reactor or Shutdown the Reactor

(Step 29 & 30)

knowt flashcard image
27
New cards

Maintaining FWS with the Reactor Critical

(Step 33)

knowt flashcard image
28
New cards

Attachment 1 RCS Boration during Downpower

Note and Caution

(Step 1)

knowt flashcard image