1
New cards

Refrigeration is defined as the process of moving __________ from one location to another by use of a refrigerant in a closed cycle.

heat

2
New cards

Halocarbon refrigerants are categorized into four groups: chlorofluorocarbons (CFCs), hydrochlorofluorocarbons (HCFCs), __________, and hydrofluoroolefins (HFOs).

hydrofluorocarbons (HFCs)

3
New cards

The __________ Agreement, revised in 20162016, marks a commitment to regulate HFC refrigerants as controlled substances due to their global warming potential (GWP).

Kigali

4
New cards

Because halocarbon refrigerants are heavier than air, leak detection sensors should typically be placed __________ from the floor.

300mm300\,mm

5
New cards

The recommended design velocity for a suction line is between __________.

4.54.5 to 20m/s20\,m/s

6
New cards

Liquid drain lines from condensers to receivers should be sized for a velocity of __________ or less to ensure positive gravity flow.

0.5m/s0.5\,m/s

7
New cards

When sizing refrigerant lines, the system is typically sized for pressure losses of __________ or less for each segment of the discharge, suction, and liquid lines.

1K1\,K

8
New cards

The primary measure for determining pressure drops in refrigeration piping is a given change in __________.

saturation temperature

9
New cards

A __________ is used in the suction line to return oil at minimum loads without causing excessive pressure drop at full load.

double suction riser

10
New cards

In ammonia systems, the intermediate vessel between the high and low stages used to cool discharge gas and subcool high-pressure liquid is called a(n) __________.

intercooler

11
New cards

Ammonia has a specific acute toxicity exposure limit (ATEL) of __________ according to ANSI/ASHRAE Standard 3434-20192019.

320mg/kg320\,mg/kg

12
New cards

The phenomenon in two-phase ammonia systems where gas is compressed until it condenses and allows a liquid slug to impact an end cap is called __________.

condensation-induced hydraulic shock (CIHS)

13
New cards

The temperature at which CO2CO_2 (R-744744) reaches its critical point is __________.

31°C31°C

14
New cards

The equilibrium point where solid, liquid, and vapor states of CO2CO_2 coexist is known as the __________.

triple point

15
New cards

In a __________ cycle, the compressor raises the operating pressure above the critical pressure and heat is rejected by cooling the gas without condensation.

transcritical

16
New cards

The reaction between ammonia and carbon dioxide resulting from internal leakage in a cascade heat exchanger typically forms a white crystalline salt called __________.

ammonium carbamate

17
New cards

In a liquid overfeed system, the mass ratio of liquid delivered to the evaporator to the amount of liquid vaporized is called the __________.

circulating rate

18
New cards

A(n) __________ receiver allows liquid to flow to the expansion valve without exposure to refrigeration in the receiver, keeping it subcooled.

surge-type

19
New cards

The behavior of zeotropic blended refrigerants where phase change occurs over a range of temperatures is known as __________.

temperature glide

20
New cards

When calculating superheating at the evaporator exit for a zeotropic refrigerant, the __________ temperature represents the saturation point.

dew-point