where are the reliable instruments in regards to a control room fire? what makes them reliable?

B train in the remote shutdown panel

reliable due to isolators in their circuits

2
New cards

what actions are taken prior to evacuating the CR during a CR fire?

TRIP THE RX (SPTAs are not performed)

check power lowering

check all FSCEAs have inserted

initiate an MSIS to prevent SG overfill (90 second time critical action)

3
New cards

what actions are taken at the remote shutdown panel during a CR fire?

determine the status of PBB-S04, evaluate if B train is powered from off site, the EDG, or de-energized

4
New cards

how is pressure control maintained during a CR fire?

B class B/U PZR heaters controlled from RSP or with local breaker operation

control of the B aux spray valves

5
New cards

during a CR fire which AFW pump will be used?

AFW pump B will be used

6
New cards

what are the time critical actions associated with a CR fire?

90 seconds initiate an MSIS

5 minutes ADV disconnects in local

disable charging pumps A and E to prevent draining the VCT

(times taken from when VCT is isolated)

14 min for 3 pumps

22 min for 2 pumps

44 min for 1 pump