1/30
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced |
---|
No study sessions yet.
When can you close in a concealed gas line?
Only after inspection (Clause 6.22)
What are the minimum sizes and requirements for threaded gas piping?
Natural gas: Minimum 1/2" unless using Schedule 80 and class 300 malleable iron fittings
Propane: Can be less than 1/2" (as small as 3/8") only if it’s a branch line to a single appliance and ≤25ft (cannot be concealed if less than 1/2")
What types of joints and fittings are permitted on steel, copper, and plastic gas lines?
Steel pipe joints: threaded, flanged, welded, press-connect, compression type (Dresser)
Joints over 2": must be welded by a class B pressure welder
Pipe dope: must be approved for pressure/temp
Gaskets: synthetic only (no natural rubber)
Copper/steel tubing: flared (forged flare nuts), brazed (over 1000°F), double ferrule compression (Swagelok), or press-connect
Bushings: must be steel/malleable iron (aluminum only for valve installation), no nested bushings
What are the requirements for appliance connectors and quick disconnects?
Max flex length: 2ft (vented), 6ft (unvented)
Connectors cannot pass through any wall, ceiling, floor, or partition
Quick disconnect must have a gas cock immediately upstream (proper flow direction)
What is the preferred practice for piping outlets and pipe protrusions?
Preferred: install a gas cock with nipple and cap for future use
Pipe protruding from wall: minimum 1" unthreaded
From floor: minimum 2" unthreaded (allows for backing wrench)
What are the requirements for drip and dirt pockets?
Not required on risers
Required at bottom of final drop to appliance
Minimum depth: 3" or pipe diameter (whichever greater)
Nipple diameter: same as pipe served or 2" (whichever less)
What practices are prohibited in gas line installation?
Cannot use defective materials
Cannot nest bushings
Only field bend if using proper bender
No street tees, street elbows, or close nipples
No unions/swing joints in concealed locations
Cannot use piping/tubing for electricity or grounding (except appliance controls)
What are the requirements for underground piping/tubing?
Minimum 15" deep (24" if under driveway/parking)
If under >25ft of paving/concrete: requires vent or inspection sleeve
Plastic pipe: must have above-ground shutoff, tracer wire
Allowed joining: welding, compression, flared, or heat fusion
Must contact Utility Safety Partners before excavation
How do you protect piping/tubing from damage?
In corrosive atmosphere: paint/coat
Must move freely without abrasion
Tubing <1.75" from inside wall: must have striker plates
Plastic: protect from direct sunlight
Outdoor tubing near traffic: protect with posts/guardrails
How is gas piping/tubing identified in residential, commercial, and public installations?
Residential: every 6ft (painted yellow, yellow bands, or “gas/propane” markings)
Commercial: every 20ft (same options)
Public: APWA color code (gas = orange); any other color must be labeled every 20ft
Where must shutoff valves be installed and what are the rules?
On final drop or rise as close as possible to appliance
Residential: can be on horizontal finish piping if within 2ft of appliance
May be up to 50ft away if clearly labeled and accessible
Can be waived in some manifold installations (commercial/room heaters <50ft from furthest appliance)
0.5psig and 1” or larger: must be ball, eccentric, or lubricated plug valve
Required when piping/tubing extends from one building to another (at both exit and entry)
What are the rules for gas hoses and fittings?
Hose not allowed on vented appliances (except radiant tube heaters)
Allowed on unvented/mobile appliances
Hose cannot pass through walls
Permanent hose: max 10ft
Temporary (construction heater): 15-75ft
What are the requirements for rooftop gas piping/tubing?
Allow for expansion/contraction (Annex G)
Supported on treated wood block or approved supports
All threaded fittings must be individually supported
Tubing must be continuously supported
What is required for inspection of plastic gas systems?
Plastic materials and fusion joints must be inspected by qualified personnel before going into service
What is the maximum spacing for pipe hangers/supports?
1/2” or less, horizontal: 6ft
3/4” to 1”, horizontal: 8ft
1-1/4” to 2-1/2”, horizontal: 10ft
1-1/4” or larger, vertical: every floor, max 125% of horizontal spacing
All tubing: 6ft
Rule of thumb: leave 3/4”–1” space between pipe and structure
Can’t support by another pipe or appliance; hanger always at top of drop/riser
How is gas piping tested before service?
Test rough-in using air, CO₂, or inert gas (not gas)
Pressure/duration per Table 6.3, no drop allowed
Remove/replace devices that can’t withstand test pressure (e.g. remove regulator, insert spool piece)
Never pressure test against control valves
All shutoffs open during test
Min 15 psig for 15 min on rough-in
Finished piping never pressure tested—use soapy water & meter dial
Pressure gauge: min 3” diameter, 2 psig increments or 2% of max, max gauge range 15–300% over test pressure
Additions <20ft and <0.5psig may be soap tested only
How is gas line purged after testing?
Purge point vented ≥10ft from building/air intake/ignition sources
Competent person must attend
Valve with handle within 5ft of purge point; cannot use appliance shutoff
Large lines: purge with inert gas before introducing NG/propane
Small lines: may not require purge (see Table 6.4)
<400MBH appliances: purge to burner if not in combustion chamber
What is a standing pressure test and when is it used?
Test with only pilot running (downstream of service or 2nd stage reg, upstream of appliance reg)
Shows regulator adjustment
Typical values: MFG gas 6”wc, NG 7”wc, propane/butane 11”wc
What is an operating pressure test and when is it used?
Test with main burners at full fire (downstream of service reg, upstream of appliance reg)
Same location as standing pressure
Check pressure drop does not exceed Table 6.1 max:
- NG 7”wc: max 1” drop
- Propane/Butane 11”wc: max 1” drop
- High-pressure NG/propane/butane: max 50% of gauge pressure
If over max, line is undersized
What is manifold pressure?
Pressure at the burner; typically NG 3.5”wc, propane/butane 11”wc (check appliance nameplate)
Who is responsible for leak checks and pressure tests?
The gasfitter is responsible for all checks and tests before service