1/21
Looks like no tags are added yet.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai | Chat |
|---|
No analytics yet
Send a link to your students to track their progress
Minimum width of any means of egress
915mm
Corridors are not allowed to pass through any intervening rooms other than corridors, lobbies and other spaces permitted to be open to corridor
True
When two exits are required, they shall be located at a distance from one another not less than ______ of the length of the maximum overall diagonal dimension of the building
1/2
In buildings protected by approved supervised automatic sprinkler system, the minimum separation distance between 2 exits shall not be less than _____ the length of the maximum overall diagonal dimension of the building
1/3
Hallways, corridors that exceeds _____ shall not have any dead-end
6m
Minimum door openings in means of egress
710mm
Maximum single door width
1.22m
A building with a basement level has a stairway designated as a means of egress. The stairway needs to be continuous from the uppermost level down to what level?
Ground Floor Level
Minimum width of stairs with occupant load of < 2,000 persons
1120mm
Minimum width of stairs with occupant load of > 2,000 persons
1420mm
Maximum height of risers for new stairs used as means of egress
180mm
Maximum height of risers for existing stairs used as means of egress
205mm
Maximum height between landings for stairs
3660mm
Minimum tread depth for new stairs used as means of egress
280mm
Minimum tread depth for existing stairs used as means of egress
230mm
Winders are allowed in staircases
True
Minimum clearance of handrails from the wall
38mm
Every stairway required to be more than ____ in width shall have intermediate handrails dividing the stairway
2.23m
Maximum height of handrails on stairs
865mm
Minimum height of handrails on stairs
760mm
Minimum width clear of all obstructions for new ramps
1120mm
Minimum width of Fire Escape Stairs
600mm