1/101
Flashcards covering building classifications, fire safety system maintenance, flammable liquid storage regulations, and exit requirements based on fire code standards.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai | Chat |
|---|
No analytics yet
Send a link to your students to track their progress
Automatic fire detector repair/replacement
A system directly connected to a city alarm box must be repaired or replaced within 24 Hours if it causes two or more false alarms within any 48 hour period.
Flammable liquid classification basis
All flammable liquids are divided into three classes according to their Flashpoint.
Flammable liquid licensing threshold
A license is required when 30 gallons or more of flammable liquids with a flashpoint below 200 Degrees F are kept on hand or stored for use in any business.
Exempt occupancies for flammable liquid licenses
Gasoline filling stations, Dry cleaners, Paint factories, Paint stores, and Fuel oil dealers are not obligated to purchase a license if licensed under other provisions of the Code.
Class I Flammable liquids
Flammable liquids with a flashpoint below 100 degrees F.
Class II Flammable liquids
Flammable liquids having a flashpoint from 100 degrees F to a flashpoint below 140 degrees F.
Class III Flammable liquids
Flammable liquids having a flashpoint from 140 degrees F and below 200 degrees F.
Fire pump testing requirements
The pump shall discharge from the highest connection for at least five minutes and deliver rated capacity through a manifold or wall hydrant for at least 15 minutes.
Standard exit width (stairs and corridors)
Required width shall be not less than 44 inches.
Reduced exit width (low occupancy)
For stories with not more than 40 persons, stairs and corridors shall be not less than 36 inches in width.
Minimum exit door width
All doors required as exits shall be not less than 36 inches wide.
Emergency generator requirement for tall buildings
All buildings over 400 feet tall must have a diesel-driven emergency generator to supply the fire pump.
Interior stairwell fire resistance (more than three stories)
Enclosures must provide fire resistance of two hours.
Interior stairwell fire resistance (less than three stories)
Enclosures must provide fire resistance of 1 hour.
Standpipe water supply capacity
Minimum capacity of 500 gpm, with an additional 250 gpm required for each additional standpipe.
Maximum gas pump hose length
The dispensing hose from a gas pump shall not be longer than 16 Feet.
Fire drill system reset failure
If a system cannot be reset after a drill, the FAO and Battalion Chief must be notified.
Multi-standpipe floor height requirement
Any building over 275 feet tall requires more than one standpipe.
Class J Building
Classification for miscellaneous building and structures.
Class I Building
Classification for hazardous use units.
Class H Building
Classification for storage units.
Class G Building
Classification for Industrial units.
Class F Building
Classification for Mercantile units.
Class E Building
Classification for Business units.
Class D Building
Classification for Open Air Assembly units.
Class C Building
Classification for Assembly Units.
Class B Building
Classification for institutional Units.
Class A Building
Classification for Residential Units.
Authority for Fixating Building Classification
The Commissioner of Inspectional Services shall consult with the Deputy Fire Commissioner of Fire Prevention.
Open Air Assembly exit requirement (under 1000 persons)
The minimum number of exits required is two.
Auxiliary Use
Rooms and spaces incidental to the principal use of the building and under the same management and control.
Class G-2 Unit
Classification for a Moderate Hazard Unit.
Subway interface protection
Every wall opening between a subway and an adjoining building interior must be protected by a Class A door.
C-1 Large Assembly
Assembly units having a capacity of 300 persons or more.
Small mercantile classification (e.g., small restaurants)
Restaurants, bars, and taverns with a capacity not exceeding 100 persons are classified as Class F Mercantile.
Aviation Fields classification
Classified as Class D Open Air Assembly.
Auxiliary use percentage limit
Auxiliary use is generally limited to 5 Percent of the principal use.
Type III A construction column dimensions
Columns must have a minimum dimension of 8 Inches.
Heavy Timber Construction
Another name for Type III A construction.
Masonry wall lintel fire protection
Fire protection is not required for lintels over openings not exceeding 5 Feet in clear width.
Location of grounds and furring
These are found in wall construction.
Class I fire alarm requirement (Dormitories)
Required in dormitories 2 stories or more unless 25 or fewer people sleep above the second floor.
Exhibition Area standpipe coverage
A standpipe location must be able to cover an area up to 130 Feet away.
Floor area increase for sprinklers
The floor area may be increased by 100 Percent when an approved automatic sprinkler system is equipped.
Fire escape door minimum width
The minimum width of a door leading to a fire escape shall be 30 Inches Wide.
Fire escape maintenance frequency
Fire escapes shall be scraped and painted every three years.
Exit capacity increase for sprinklers
Exit capacity may be increased by 50 Percent in buildings equipped throughout with approved automatic sprinklers.
Business unit door swing exemption
Doors from offices with capacity not exceeding 100 persons are not required to swing in the direction of exit travel.
Exit sign illumination
Must be internally illuminated by a 10 watt or larger incandescent electric lamp.
Escalators as stairs
Escalators are permitted to be used as stairs.
Escalator flight vertical travel limit
An escalator flight shall have a vertical travel of not more than 35 Feet.
Escalator angle of inclination limit
The angle of inclination shall not exceed 30 Degrees from the horizontal.
Elevator Recall height exemptions
Not required in buildings 80 feet or less in height or hospitals 55 feet or less in height.
Smoke detector placement rules
Located on ceiling (min. 4 inches from wall) or wall (6 to 12 inches from ceiling) and within 15 Feet of sleeping rooms.
Siamese connection placement height
Siamese shall be no less than 18 inches and no more than 5 Feet above grade.
Industrial hazardous use unit protection
Required to be protected with Automatic Sprinklers regardless of height, area, or construction.
Requirement for one siamese connection
Permitted when two adjacent street exposures equal less than 250 Feet.
Requirement for three siamese connections
A building with two street exposures totaling >250 feet and one exposure >250 feet.
Requirement for four siamese connections
Two adjacent street exposures each dimension greater than 250 feet, with two on each exposure spaced 200 feet apart.
Siamese connection spacing (same exposure)
Two fittings on the same exposure shall be spaced a minimum of 200 Feet apart.
Extinguisher visibility distance
Must be visible from a distance of 50 feet.
Extinguisher travel distance limit
Travel distance to an extinguisher shall not exceed 75 feet.
Extinguisher mounting rule (under 40 lbs)
The top of the extinguisher shall be hung 5 feet from the floor if it weighs less than 40 pounds.
Standpipe system inspection frequency
Must be inspected Semi-Annually.
Maximum number of siamese connections
A building is limited to a maximum of four fire department connections.
Flammable liquid container grounding
Containers must be Electrically Grounded when drawing flammable liquids in a flammable liquid room.
Gravity feed of flammable liquids
Prohibited within a building except inside a Flammable Liquid Room.
Flammable liquid vault sill height
The sill on a vault used for flammable liquid storage must be 6 Inches.
Above ground tank capacity limit (Class I)
Maximum capacity is 15,000 Gallons.
Fuel oil storage floor drains
Drains to city sewers are permitted when storage is 550 Gallons or less.
Paint spraying booth requirement threshold
Required when using more than 1 Gallon of paint in 24 hours.
Semi-Trailer tank car inspection frequency
Must be inspected Semi-Annually.
Above ground tank diking requirement
Every above ground storage tank containing flammable liquids shall be Diked.
Dry cleaning building separation distance
Must be located no nearer than 100 Feet to any institutional, assembly, or open air assembly unit.
Flammable liquid cabinet door hardware
Must be constructed with a three joint lock.
Open storage limit (Class I liquid)
Ten gallons maximum in sealed containers or safety cans in Type I, II, or III construction.
Open storage limit (Class II liquid)
60 gallons maximum in safety cans (max 5 gal each), barrels, or drums in Type I, II, or III construction.
Open storage limit (Class III liquid)
120 gallons maximum in sealed containers (max 5 gal each), barrels, drums, or tanks in Type I, II, or III construction.
Wood frame construction storage limits (Class I/II)
In Type IV A or IV B construction, restricted to a maximum of 5 gallons stored in 1 gallon cans.
Flammable liquid Storage Cabinet requirement
Required for storage in excess of 10 gallons and less than 50 gallons.
Flammable liquid Storage Room requirement
Required for any storage of flammable liquids in excess of 50 gallons.
Flammable Liquid Room Sprinkler Authority
Determined by the Engineering Section.
Flammable Liquid Room Fire Ratings
1 hour (up to 200 gal), 2 hour (201 to 400 gal), 3 hour (401 to 600 gal), and 4 hour (>600 gal).
Flammable Liquid Room basin capacity
Must hold 121 times the capacity of the room; sewer drains are not permitted.
Flammable Liquid Room door requirements
1 and 2 hour rooms require Class B self-closing; 3 and 4 hour rooms require Class A doors.
Requirements for two handrails
Requested when the width of a stair is 44 inches or more.
Industrial building stair materials
Stairs in Type I or Type II industrial buildings must be constructed of Non-Combustible materials.
Stair landing door opening clearance
75 percent of the required exit width must be maintained beyond the edge of a door when opened in any position.
Exit (Definition)
A means of egress including outside exits, vertical exits, horizontal exits, and exit connections.
Vertical Exit (Definition)
A means of exit for ascension/descension between levels including stairways, smokeproof towers, ramps, escalators, and fire escapes.
Horizontal Exit (Definition)
A protected opening through a two-hour fire partition, fire wall, or bridge connecting two buildings.
Outside Exit (Definition)
An exit to a public way, an open area leading to one, or an enclosed fire-resistive passage leading to one.
Exit Connections (Definition)
Doorways, aisles, corridors, and lobbies leading to a vertical, horizontal, or outside exit.
Smokeproof tower height requirement
At least one must be provided in every building with a height exceeding 264 Feet.
Hazardous unit travel distance limit
The maximum travel distance to an exit is 75 Feet.
Travel distance increase for sprinklers
May be increased by 50 percent in buildings equipped throughout with a standard sprinkler system.
Assembly unit emergency latch pressure
Exit doors serving more than 200 persons must release under a pressure of 15 pounds.
Fire escape doorway width
Access through the interior must be through a doorway flush with the floor and at least 30 inches wide.
Fire escape window access limit
Permitted for serving not more than 20 persons; window must be 30 inches wide by 36 inches high.
Paint spraying room requirement threshold
Required when spraying more than 10 gallons of paint within a 24 hr period.