Chapter 3 Properties of Refrigerants

0.0(0)
studied byStudied by 0 people
0.0(0)
full-widthCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/13

encourage image

There's no tags or description

Looks like no tags are added yet.

Study Analytics
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai

No study sessions yet.

14 Terms

1
New cards

What is one advantage to having evaporator pressures higher than atmospheric pressure?

{c.} Higher pressures keep air out of the system. ref (3-5)

2
New cards

What are two refrigerants that are blended to create a new refrigerant with its own properties called?

{b.} A zeotrope or an azeotrope. ref (3-1, 3-2)

3
New cards

Discharge temperature should not be so high it...

{b.} causes breakdown of the compressor lubricating oil. ref (3-6, 3-7)

4
New cards

What factor do you multiply the mass flow rate (lbs./min.) by to determine the vapor flow rate through the compressor?

{b.} Specific volume (cubic ft./lb.). ref (3-10, 3-11)

EQ: lb./min x ft^3/lb. = ft^3/min (CFM)

5
New cards

Three factors to consider when choosing a refrigerant are...

{c.} cost, availability, and safety. ref (3-4, 3-11, 3-12)

6
New cards

How much does the pressure of trapped ammonia liquid change?

{b.} 100 to 150 psi per degree Fahrenheit increase. ref (3-14)

7
New cards

What is one positive characteristic of most halocarbon refrigerants?

{b.} They are not generally flammable. ref (3-19)

8
New cards

A slight leak in a fitting on a HCFC-22 system causes the halide torch flame to...

{c.} turn green. ref (3-21)

9
New cards

If a system using reciprocating compressors has the evaporator temperature decreased, what happens to the theoretical discharge temperature? (Assume constant condensing pressure).

{a.} Discharge temperature rises. Ref (3-9)

10
New cards

What would the theoretical discharge temperature be for an ammonia system with an evaporator temperature of 0°F and a condensing temperature of 93°F?

{d.} 242°. ref (3-9)

11
New cards

TRUE/FALSE: Decreased evaporating temperature is a direct symptom of air in an ammonia system?

{d.} False. ref (2-17)

12
New cards

Which refrigerant was the first to be phased out by Montreal Protocol?

{b.} CFC-12. ref (3-22, 3-23)

13
New cards

As the ratio between the evaporator and condensing pressure increases, ...

{c.} the theoretical discharge temperature increases. ref (3-9)

14
New cards

Refrigerant leaks are detected using either X on ammonia or Y for CFCs and HCFCs.

{b.} a sulfur stick and an electronic leak detector. ref (3-18, 3-21)