The branch circuit overcurrent device and conductors for a — gallon or less water heater must have a rating of not less than — % of the rating of the water heater 422.13
120, 125
The length of a cord for supplying waste disposers is between — and — inches. 422.16(B)(1)(1)
18, 36
The length of a cord for supplying range hoods is between — and — inches 422.16(B)(4)(1)
18, 36
A cord and plug connected range hood need to be on its own — 422.16(B)(4)(3)
circuit
Cords supplying trash compactors must be between — and — feet long. 422.16(B)(2)(1)
3, 4
Cords supplying built in dishwashers must be between — and — ft long 422.16(B)(2)(2)
3, 6.5
The receptacle for a built in dishwasher must be located in the space — to the space containing the dishwasher. 422.16(B)(2)(5)
adjacent
The cord that goes through the partition between the dishwasher and receptacle must have a — or — 422.16(B)(2)(5)
bushing, gramit
For non-motor appliances rated over 300 VA, the branch circuit breaker may serve as the required disconnect as long as its within — or is capable of being — , open. 422.31(B)
sight, locked
Fixed electric space heating equipment shall be supplied with conductors rated for — % of the heater rating. 424.4(B)
125
Heating cables must be kept at least, — inches from outlet boxes. 424.39
8
— of heating cable must provide labels for posting at the panelboard. 424.47
manufacturers
Heating elements in electric furnaces must be sub-divided if the load is more than — amps. 424.22(B)
48
Outdoor snow melting equipment must have GROUND FAULT PROTECTION OF — 426.28
equipment
An — emergency disconnect is required for generators at one and two family dwelling 445.18(D)
outdoor